Загрузил forvard.02

LINC232

Реклама
Universal LINC232
INSTALLATION MANUAL
NEW RELEASE
Form 450.20-N17 (702)
Universal LINC232
Universal LINC232 UCS
UNIVERSAL
LINC232 UCS
STATUS
OFF
CTS
GND
TX
RX
TX
RX
RS232
P1 P2
OFF OFF
ON OFF
OFF ON
ON ON
PARITY
NONE
SPACE
ODD
EVEN
B1 B2
OFF OFF
ON OFF
OFF ON
BAUD
4800
9600
19K2
CS OFF 19K2 LAN
CS ON 50K LAN
P1
P2
B1
B2
1
2
4
8
16
32
64
CS
ON
SCREEN
P3
P2
GND
RX 5VDC
TX
LAN
FORM 450.20-N17 (702)
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
During installation, operation, maintenance or
service, individuals may be exposed to certain
components or conditions including, but not limited
to: refrigerants, oils, materials under pressure,
rotating components, and both high and low voltage.
Each of these items has the potential, if misused or
handled improperly, to cause bodily injury or death.
It is the obligation and responsibility of operating/
service personnel to identify and recognize these
inherent hazards, protect themselves, and proceed
safely in completing their tasks. Failure to comply
with any of these requirements could result in serious
damage to the equipment and the property in which it
is situated, as well as severe personal injury or death
to themselves and people at the site.
This document is intended for use by owner-authorized operating/service personnel. It is expected that
this individual possesses independent training that
will enable them to perform their assigned tasks
properly and safely. It is essential that, prior to
performing any task on this equipment, this individual shall have read and understood this document
and any referenced materials. This individual shall
also be familiar with and comply with all applicable
governmental standards and regulations pertaining to
the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:
2
DANGER indicates an imminently
hazardous situation which, if not
avoided, will result in death or
serious injury.
CAUTION identifies a hazard which
could lead to damage to the machine, damage to other equipment
and/or environmental pollution.
Usually an instruction will be given,
together with a brief explanation.
WARNING indicates a potentially
hazardous situation which, if not
avoided, could result in death or
serious injury.
NOTE is used to highlight additional
information which may be helpful to
you.
YORK INTERNATIONAL
FORM 450.20-N17 (702)
CHANGEABILITY OF THIS DOCUMENT
In complying with YORK’s policy for continuous
product improvement, the information contained in
this document is subject to change without notice.
While YORK makes no commitment to update or
provide current information automatically to the
manual owner, that information, if applicable, can be
obtained by contacting the nearest YORK Sales,
Service and Authorized Distributor offices.
It is the responsibility of operating/service personnel
as to the applicability of these documents. If there is
any question in the mind of operating/service personnel as to the applicability of these documents, then,
prior to working on the equipment, they should verify
with the owner whether the equipment has been
modified and if current documentation is available.
REFERENCE INSTRUCTIONS
DESCRIPTION
Universal LINC232 Specification Sheet
YORK INTERNATIONAL
FORM NO.
450.20-S29
3
FORM 450.20-N17 (702)
TABLE OF CONTENTS
GENERAL SAFETY GUIDELINES .......................................................................................................... 2
SAFETY SYMBOLS ................................................................................................................................ 2
REFERENCE INSTRUCTIONS ............................................................................................................... 3
LIST OF FIGURES .................................................................................................................................. 6
LIST OF TABLES..................................................................................................................................... 6
SECTION 1 – GENERAL INFORMATION ............................................................................................... 7
Overview ............................................................................................................................................ 7
Description ................................................................................................................................... 7
SECTION 2 – NETWORK TOPOLOGY .................................................................................................. 9
General .............................................................................................................................................. 9
Communication Method ..................................................................................................................... 9
Background vs. Foreground Communications ................................................................................. 11
Speed of Communications............................................................................................................... 11
Summary of ISN Network Restrictions ............................................................................................ 11
SECTION 3 – INSTALLATION ............................................................................................................... 13
Installation Guidelines ...................................................................................................................... 13
Environment ............................................................................................................................... 13
Electrical ..................................................................................................................................... 13
Electrical Noise .......................................................................................................................... 13
Ground/Earth ............................................................................................................................. 14
Protection of Communication Ports ........................................................................................... 14
Cable Specifications ........................................................................................................................ 14
Power Cables ............................................................................................................................. 14
Network and Sensor Cables ...................................................................................................... 14
Summary of Mounting Recommendations ................................................................................ 16
Hardware Configuration ................................................................................................................... 16
DIN Rail Mounting ...................................................................................................................... 16
Panel Mounting .......................................................................................................................... 16
Power Connections .......................................................................................................................... 17
Universal LINC Connection ........................................................................................................ 17
5 VDC Power Supply Connection .............................................................................................. 17
4
YORK INTERNATIONAL
FORM 450.20-N17 (702)
TABLE OF CONTENTS (CONTINUED)
Wire Connections ............................................................................................................................. 19
RS232 Connection ..................................................................................................................... 19
LAN Connection ......................................................................................................................... 19
Switch Settings ................................................................................................................................ 20
Continuity and Isolation Checks ...................................................................................................... 24
SECTION 4 – MAINTENANCE .............................................................................................................. 25
LEDs ................................................................................................................................................ 25
Status LED ................................................................................................................................. 25
Port LEDs ................................................................................................................................... 25
APPENDIX ............................................................................................................................................. 28
Universal LINC232 Specifications ................................................................................................... 28
YORK INTERNATIONAL
5
FORM 450.20-N17 (702)
LIST OF FIGURES
Figure 1. Universal LINC232 ................................................................................................................................ 8
Figure 2. Typical Network Configurations ........................................................................................................... 10
Figure 3. DIN Rail Mounting Options .................................................................................................................. 16
Figure 4. DIN Rail Removal ................................................................................................................................ 17
Figure 5. USB-Style Patch Cable ....................................................................................................................... 17
Figure 6. Dimensions and Mounting Points ........................................................................................................ 18
Figure 7. Typical RS232 Wire Connection .......................................................................................................... 20
Figure 8. Typical RS485 LAN Connections ......................................................................................................... 21
Figure 9. Universal LINC232 Components ......................................................................................................... 22
Figure 10. Universal LINC232 DIP Switch Settings ............................................................................................ 23
LIST OF TABLES
Table 1 – Recommended Cable Specifications .................................................................................................. 15
Table 2 – Recommended Parity Settings............................................................................................................ 20
6
YORK INTERNATIONAL
GENERAL INFORMATION
FORM 450.20-N17 (702)
SECTION 1
GENERAL INFORMATION
Overview
The Universal LINC232 allows peripheral devices to
be attached to the ISN network to receive and send
data. The Universal LINC232 provides a connection
point for:
VT100 Terminal Emulation (PC connection)
Modem
Printer
1
Along with this upgrade some of the switches were
modified and the baud rates were upgraded to offer
higher speeds. These items are covered more specifically in the Installation section.
NOTE: This manual will refer to both
versions as the Universal LINC232
unless specific differences apply. When
specific differences in operation apply,
they will be referenced at that time.
Facility Manager/YES/IcE/TUP/ISNTools
A variety of mounting configurations provide a very
adaptable device. A 5 VDC Power Supply is also
available to power the Universal LINC232 or it can
be powered via the LAN connector on newer controllers equipped with a USB-style connector. The power
supply also includes the same flexible mounting
options as the Universal LINC232.
The original Universal LINC232 was designed
around the Rev. 77 and older networks. While
communication to newer, UCS-based products
(TDCE, IDC, UDC, etc.) is functional, the save or
restore functions within Facility Manager did not
operate correctly. The IcE engineering tool also does
not accommodate the UDC software in the on-line
edit mode or the save and restore functions.
To accommodate products using the newer UCS
software, the Universal LINC232 was enhanced. This
product is differentiated from the original by the
name “Universal LINC232 UCS” on the metalwork
or the printed circuit board number of
031-02424-001.
NOTE: The Universal LINC232 supports on-line monitoring only and does
not support remote alarm delivery. For
remote alarm delivery, a LINC Guardian Modem is required.
The Universal LINC232 uses a bank of DIP switches
to select communication parameters and node address. The selectable communication parameters are
parity and transfer rate.
NOTE: The Universal LINC232 can
only be powered via the LAN connection on products equipped with a USBstyle connector. Products not equipped
with the USB-style connector must be
powered from the optional 5 VDC Power
Supply.
The Universal LINC232 requires a 5 VDC power
source. If located within 39 in. (1 m) of a controller
equipped with the USB-style connector, sufficient
power can be supplied through the LAN connection
point, either the screw terminals or USB-style
connector. For older style controllers, i.e., those not
equipped with a USB-style connector, or if the
mounting location is not within 39 in. (1 m) of any
controller, the 5 VDC Power Supply must be used to
power the Universal LINCs.
Description
The Universal LINC232 is a small footprint device
which can be located inside most enclosures or
positioned as a stand-alone device within a building.
The Universal LINC232, as well as the optional
5 VDC Power Supply, includes a housing with a DIN
rail mounting clip. Either device can be removed
from the housing and attached directly to a panel or
YORK INTERNATIONAL
7
GENERAL INFORMATION
FORM 450.20-N17 (702)
Universal
LINC232
UNIVERSAL
LINC232 UCS
STATUS
OFF
CTS
GND
TX
RX
TX
RX
PARITY
NONE
SPACE
ODD
EVEN
B1 B2
OFF OFF
ON OFF
OFF ON
BAUD
4800
9600
19K2
CS OFF 19K2 LAN
CS ON 50K LAN
RS232
Plastic
Housing
P1 P2
OFF OFF
ON OFF
OFF ON
ON ON
P1
P2
B1
B2
1
2
4
8
16
32
64
CS
Universal
LINC232
ON
SCREEN
P3
TX
P2
GND
RX 5VDC
LAN
DIP
Switches
Plastic
Housing
DIN Rail
Mounting
Figure 1. Universal LINC232
enclosure. In addition, if the power supply is used,
the LINC can attach to the power supply in a “piggyback” style.
ing power supply. The enclosure also works for
mounting other YORK devices, such as a TDC8E or
TDC9E.
An enclosure with a DIN rail is also available as a
mounting option. This enclosure provides for easy
installation of one Universal LINC and accompany-
The Universal LINC232 has two ports. The LAN port
always connects to the LAN or controller. The RS232
port always connects to the RS232 device.
Two LEDs indicate communication status for each
port. A single STATUS LED indicates the condition
of the device.
8
YORK INTERNATIONAL
NETWORK TOPOLOGY
FORM 450.20-N17 (702)
SECTION 2
NETWORK TOPOLOGY
General
The full range of ISN control products (UDC, TDCE,
FDC, etc.) are able to reside on a Local Area Network
(LAN) with full peer-to-peer communications. The
network architecture supports a potential of 8372
controllers, each one able to communicate to any
number of other controllers on the LAN and outside
of the LAN via a modem to remote facilities.
The entire building or complex may be linked together to form a Building Automation System (BAS)
or Building Management System (BMS).
YORK’s proprietary network protocol is the Integrated System Network (ISN). The ISN network is
RS485, utilizing ethernet principles and background
and foreground communication levels. The data
transfer speed is either 19.2 or 50 kbaud, depending
upon the version of software used. Newer versions of
software allow transfer speed selection to be backward-compatible with older networks.
All ISN controllers have the ability to communicate
directly to all other ISN controllers or devices on a
network or any subnetwork – this is known as “peer
to peer” communication.
Due to the volume of traffic which may be present on
a network, it is often beneficial to divide the network
into subnetworks. Local messages remain contained
within the subnetwork. Full network communication
is then limited to only the data relevant to the other
subnetworks, greatly reducing the network traffic.
A variety of devices may be attached to the ISN
network to enhance usability and functionality. Some
of these devices are:
• The Universal LINC485 configured as a repeater
amplifies the network signal to extend the
physical length of a network or subnetwork
cable. They also extend the number of ISN
controllers by segmenting the network.
• The Universal LINC485 configured as a router
separates subnetworks from the main network.
• The LINC Fiber Optics interfaces the ISN
network with fiber optic cable.
YORK INTERNATIONAL
• The LINC Guardian manages the remote transmission of multiple alarms from the ISN network.
• The Universal LINC232 allows communication
to RS232 devices such as modems, serial
printers, terminals or PC’s.
2
NOTE: The PC must be running a
VT100 emulation program, York Icon
Engineering Software (IcE) or York
Facility Manager for Windows™
software.
Physically, a twisted-pair (2-core) shielded cable is
daisy-chained between the network devices.
Communication Method
The ISN network communicates on a “contention”
basis. Every ISN controller on the network can
transmit a message but only the designated receiving
controller(s) acknowledge receipt. Each receiving
controller sends a receipt back to the sending controller as acknowledgment of the transmission. A calculated checksum is used to verify the integrity of each
message.
If no acknowledgment is received, the message is
automatically retransmitted up to 3 times. After 3
attempts to communicate, the sending controller
starts to increase the amount of time between transmissions. The time increases in intervals of 10
seconds, 15 seconds, 30 seconds, 1 minute, 15
minutes, 30 minutes and then 1 hour if unsuccessful.
Retransmission of the message then occurs automatically every hour until receipt is acknowledged. No
message is ever lost, although message delivery may
be slowed on high traffic networks if not segmented
properly.
If an external device is connected to the RS232 port,
such as a modem through the Universal LINC232,
the retransmission interval between failed communications changes from 1 minute to 15 minutes to 30
minutes to 1 hour, 2 hours, 4 hours and then 6 hours.
Retransmission of the message then automatically
occurs every 6 hours until receipt is acknowledged.
9
NETWORK TOPOLOGY
FORM 450.20-N17 (702)
Subnetwork
TM
ISN
YORK
Ò
TM
ISN
Repeater
Router
UNIVERSAL
LINC485
UNIVERSAL
LINC485
Controller
Controller
Repeater
UNIVERSAL
LINC485
Router
UNIVERSAL
LINC485
Universal LINC485
w/ Power Supply
UNIVERSAL
LINC485
Universal LINC485
w/ Power Supply
Controller
Universal LINC485
w/ Power Supply
Controller
Router
Repeater
UNIVERSAL
LINC485
UNIVERSAL
LINC232
UNIVERSAL
LINC485
Universal LINC485
w/ Power Supply
Universal LINC485
w/ Power Supply
Segment
Modem
Universal LINC232
w/ Power Supply
Universal LINC485
w/ Power Supply
Repeater
Maximum of 30 nodes
and 4000 ft. (1220 m)
Base Network
Controller
Universal LINC485
w/ Power Supply
Base Network
Universal LINC485
w/ Power Supply
UNIVERSAL
LINC485
Ò
Repeater
YORK
Controller
Repeater
Controller
UNIVERSAL
LINC485
Universal LINC232
Facility Manager
USB Cable
UNIVERSAL
LINC232
Universal LINC485
w/ Power Supply
Base Network
Maximum of 91 nodes
and 12,000 ft. (3660 m)
UNIVERSAL
LINC232
Printer
Universal LINC232
w/ Power Supply
Figure 2 – Typical Network Configurations
10
YORK INTERNATIONAL
NETWORK TOPOLOGY
FORM 450.20-N17 (702)
Background vs. Foreground
Communications
The ISN network uses both “Background” and
“Foreground” communication to ensure essential data
is transmitted without delay.
Background communication supports multiple source
messages at the same time, although the speed of
communication may be affected if large quantities of
data are transmitted around the network.
Examples of background communication are:
• Automatic transfer of digital states and analog
values between ISN controllers.
• Analog and Digital alarms to a Universal
LINC232 connected to a PC running the York
Facility Manager for Windows™ software.
• Using a PC running the York Facility Manager
for Windows™ software to read and write data
to and from an ISN controller via a Universal
LINC232.
• Analog and Digital alarms to a LINC Guardian.
Only one foreground communication to a specific
ISN controller can occur at any one time. A “busy”
message is displayed if the ISN controller is already
communicating with another device using this
method. Background communication can occur
simultaneously with foreground communication.
Examples of foreground communications are:
• Manual communications between ISN controllers using the optional keypad/display or Windows™ HyperTerminal software running on a
PC connected to the RS232 port of an ISN
controller.
• Using a PC running the York Facility Manager
for Windows™ software to write data into an
ISN controller via a Universal LINC232.
• Printing of Analog and Digital alarms to a
Universal LINC232 connected to an RS232
printer.
YORK INTERNATIONAL
• Using a PC running the York IcE to Save or
Load an ISN controller Configuration via a
Universal LINC232.
• Using a PC running the York Facility Manager
for Windows™ to Save or Load an ISN controller Configuration via a Universal LINC232.
Speed of Communications
The ISN network communicates at either a 19.2 or 50
kbaud rate. The Universal LINC232 is switch selected to communicate at 4800, 9600, or 19,200
(19k2) baud rates through the serial RS232 port.
The typical response time between ISN controllers
for automatic transfer of data or alarms is
100 milliseconds.
Each Universal LINC485 Repeater and Router
increases the typical response time by
100 milliseconds.
Summary of ISN Network Restrictions
• The maximum single length of a network or
subnetwork is 4000 ft. (1200 m). This can be
extended to 12,000 ft. (3600 m) using two
Universal LINC485 devices configured as
repeaters. This provides a maximum combined
network end-to-end length of 36,000 ft. (10,800
m).
• A Universal LINC485 configured as a repeater is
required every 4000 ft. (1200 m) or 32 nodes. A
node is any device which uses an RS485 driver,
such as an ISN controller, Universal LINC485 or
Universal LINC232.
• The maximum number of nodes on a main
network is 92 plus two Universal LINC485
devices configured as repeaters. A maximum of
91 plus two Universal LINC485 devices are
allowed on a subnetwork.
• When the main network or subnetworks are
extended between different buildings, the
ground/earth voltage of the buildings must be at
11
2
NETWORK TOPOLOGY
FORM 450.20-N17 (702)
the same potential. If this cannot be guaranteed,
the network connection between building(s)
should be a fiber optic cable with a LINC Fiber
Optic device fitted in each building to interface
onto the ISN network.
• The LINC Guardian should be used where it is
expected multiple alarms will be transmitted via
a modem to a remote Facility Manager for
Windows™ or multiple destinations. It acknowledges receipt of any alarm to a transmitting ISN
controller and can store up to 20 alarms in each
of the 8 standard ISN Alarm Classes.
• All node numbers connected to the LAN Port 1
of a Universal LINC485 configured as a repeater
must be lower than the node address of the
repeater. All node numbers connected to the
12
LAN Port 2 of a Universal LINC485 configured
as a repeater must be higher than the node
address of the repeater.
• Each ISN controller must have the node switch
set to a unique address number between 1 and 98
per subnetwork. The node switches are used for
filtering messages at a Universal LINC485
configured as a repeater which also must have a
unique node number. The node switches on a
Universal LINC485 configured as a router set
the subnetwork address and must be between 1
and 98, with the main network automatically
being network address 99. Communications
between ISN devices on the same network or
subnetwork(s) should use network 0 (zero) as the
network address.
YORK INTERNATIONAL
INSTALLATION
FORM 450.20-N17 (702)
SECTION 3
INSTALLATION
Installation Guidelines
This manual assumes the installer is competent in
environments with moving machinery, and is able to
recognize and protect against any inherent hazards,
such as, but not limited to, refrigerants, oil, corrosive
chemicals or gases, materials under pressure, rotating
parts, and both high and low voltages. Each of these
items has the potential, if misused or handled improperly, to cause bodily injury or death.
It is the obligation and responsibility of the operating/
service personnel to identify and recognize inherent
hazards, protect themselves, and proceed safely in
completing their tasks. Failure to comply with any of
these requirements could result in serious damage to
the equipment, as well as severe personal injury or
death. In addition to following standard local, state
and country codes and procedures, it is recommended
that a lockout procedure be used to prevent inadvertent start up of equipment during installation and
maintenance procedures.
All wiring should be carried out in a safe and neat
manner and should always comply in all respects to
the latest edition of any local, state or country codes
that may be applicable. The wiring should be installed in a manner that does not cause a hazard and
is protected against electrical and mechanical damage.
Care should also be taken when mounting enclosures
so access to other equipment within the vicinity is not
restricted.
Environment
YORK ISN equipment must be installed in an
environment that is protected from the direct influence of the elements and is within the following:
Temperature: 32 to 122° F (0 to 50° C).
Humidity: 10% to 95% non-condensing.
The unit should never be mounted outside the confines of a building. If this cannot be avoided, it may
be mounted inside an enclosure rated at IP65/NEMA
4X or greater. In addition to protection against the
YORK INTERNATIONAL
elements, the enclosure must be capable of maintaining the circuit boards at the required temperature and
humidity. This may require the addition of a fan or
heater to maintain the temperature and humidity
inside the enclosure.
WARNING: Never install the components in an element that does not
meet the minimum environmental
requirements.
3
Electrical
Refer to the table titled Recommended Cable Specifications to determine suitable wire sizes to connect the
line voltage feed the devices. The line voltage power
source should be “clean,” separately fused (for either
110 or 240 VAC), and isolated, (using a control
transformer) from other equipment in the plant room
that may generate EMI interference.
Electrical Noise
All electrical equipment has the risk of being affected
by external electrical noise. This noise may take the
form of Radio Frequency Interference (RFI) or
Electro-Magnetic Interference (EMI). To minimize
the affects of electrical noise, mount equipment in a
location away from all possible RFI and EMI
sources. These include high voltage cables, high
voltage transformers, breakers, and high frequency
drives.
Keep line voltage switching loads a minimum of 6 in.
(152 mm) away. Any high voltage equipment, such as
transformers, high horsepower electric motors or high
frequency drives, should be kept a minimum of 30 ft.
(9.1 m) away.
All high voltage wiring (>75 volts) must be run in
conduit and kept separate from low voltage communications wiring. This greatly reduces network
communication problems.
13
INSTALLATION
FORM 450.20-N17 (702)
Ground/Earth
All ISN controllers are designed to use the building
ground (earth) as a reference
point. This electrical orientation helps maintain all electronic components communicating to the controller within
their specified voltage limits.
Protection of Communication Ports
GRD.
RAM 5
CAUTION: The controller must
connect to a true building ground.
Failure to do so may cause equipment damage and will void all
warranty claims.
Electrical grounding also protects network devices
from the effects of lightning strikes. When lightning
strikes near an ISN installation, it alters the potential
of the building’s ground. If an ISN controller has
been properly grounded, it will respond to this
change much faster than if the ground connection is
inadequate. Controllers that are poorly grounded
provide a lower resistance path through their signal or
power connections than the actual ground of the
building. Under these circumstances large surge
currents may flow through the controller and result in
component failure.
An example of a poor ground would be a galvanized
steel cold water pipe. As the pipe corrodes it no
longer acts as a true ground. The corrosion acts as an
insulator, raising the potential of the pipe with respect
to earth ground.
YORK strongly recommends that the building’s
ground be checked prior to the start of the installation. The power distribution panel should be checked
to ensure that it is not connected to a corroded or
galvanized pipe. As a minimum, it must be connected
with 14 AWG wire.
The most common circuits damaged are communication components, such as RS485 and RS232 drivers.
When using RS485 technology it is possible that
electrical disturbances, such as voltage spikes, can
damage a circuit board. Newer ISN controllers
include tranzorbs at the RS485 ports to protect
against damaging electrical spikes and stray voltage.
It is recommended that all devices on an RS485
network be equipped with protection against electrical disturbance.
Cable Specifications
Power Cables
CAUTION: Aluminum wire is
absolutely not acceptable.
The power cable should be at least an 18 AWG
copper wire rated for 10 amps per core at 250 volt
AC. If the power cable uses three conductors, the
ground conductor must be, as a minimum, the same
size with the same current carrying capacity as the
live and neutral conductors.
All ISN devices should be wired to a non-switched,
fused spur to prevent the power from being turned off
accidently. The supply spur should be protected with
a either a suitable fuse or an approved power breaker.
The input line supply voltage should be fused. For a
115-volt line voltage use a 10-amp fuse or breaker.
For a 230-volt line voltage use a 5-amp fuse.
The fuse or breaker should be located within a
reasonable distance to the controller so the power can
be turned off any time the unit is serviced.
Network and Sensor Cables
Cables come in many types. A balance between cost
of the wire and the simplicity of the project determines the variety of wires used. Quite often a single
type of wire or cable may be used for nearly all
wiring on a project, even though it greatly exceeds
the requirements for a particular sensor or application.
14
YORK INTERNATIONAL
INSTALLATION
FORM 450.20-N17 (702)
Table 1 – Recommended Cable Specifications
Analog, Digital, RS485 (ISN &
Digital Outputs Pulse Inputs and
York Talk 2
Analog Outputs
Networks)
RS232 (Devices to
LINCs and
Controllers; York Talk
1 & 3 Networks)
Line Voltage
Power Supply
Number of Cores
2 (or n for
multicore)
2 (or n for
multicore)
2 Twisted
3
3 w/Outer Sheath
0.31- 0.41 in.
(7.8-10.3 mm)
dia.
Minimum Conductor
Gauge – AWG (CSA)
22
(0.34 mm2)
22
(0.34 mm2)
20
(0.52 mm2)
22
(0.34 mm2)
16
(1.5 mm2)
Conductor Material
Tinned Copper
Tinned Copper
Tinned Copper
Tinned Copper
Plain Copper
Strand/Strand gauge
AWG (CSA)
7/30
(7/0.2 mm)
7/30
(7/0.2 mm)
7/28
(16/0.2 mm)
7/30
(7/0.2 mm)
19/27
(30/0.25)
Voltage Rating – Uo/U
300
300
300
300
300/600
Nominal Current per
Core – amps
1
2.5
N.A.
N.A.
10
Shield
Unshielded
100% Overall
Beldfoil
Conductor Insulation
Round PVC
Round PVC
Round PVC
Round PVC
PVC
Core Insulation
PVC
PVC
PVC
PE
PVC
Nominal Capacitance
between Conductors –
pF/m
N.A.
80
64.6
75
N.A.
Characteristic
Impedance – ohms
N.A.
N.A.
78
N.A.
N.A.
Maximum Run Length
– ft (m)
1000 (305)
1000 (305)
Refer to Section
2
32 (10)
N.A.
Belden Number
8442
8761
9272
9533
N.A.
100% Overall
Beldfoil or 93% 100% Overall Beldfoil
Overall Braided
3
N.A.
N.A. – Not applicable.
NOTE: Whenever possible, use cabling which meets or exceeds the equivalent of the Belden specification.
The table titled Recommended Cable Specifications
provides a guide to one major wire manufacturer’s
product line. These are the minimum requirements.
Use them as a guide. If questions arise, most wire
supply companies can cross-reference between
YORK INTERNATIONAL
manufacturers and help determine if a particular wire
meets the requirements.
NOTE: Be sure cables are securely
attached without tensile load.
15
INSTALLATION
FORM 450.20-N17 (702)
To attach any of the devices, hook the lip of the
mount over the edge of the DIN rail. Press the bottom
of the device until the mount “snaps” over the lower
lip of the DIN rail.
Summary of Mounting Recommendations
• Always mount ISN devices inside the confines
of a building or inside an enclosure suitably
rated for exposure to weather.
To remove a module, pull the lower lip of the mount,
which is exposed below the housing, down until the
lower lip of the DIN rail is clear. Tilt the device and
lift it off the top lip of the DIN rail.
• Never mount ISN devices under or beside pipes
carrying water or chemicals.
• Never mount ISN devices near high voltage
cables, high voltage transformers or breakers, or
close to high frequency drives.
In some situations it may be desirable to remove the
Universal LINC from the housing and attach it to the
5 VDC Power Supply. The housings are modular and
can be separated by using a screwdriver pressed
between sections. When the Universal LINC is
removed from the housing it may be attached to the
5 VDC Power Supply using the two 2.5M x 5 screws
located on the top surface of the power supply. The
assembled unit may then be clipped to a DIN rail.
• Never mount ISN devices in a location where
the environment could be outside the specified
operating specifications.
• Never mount ISN devices on a vibrating surface
without first employing some form of mechanical dampening.
Hardware Configuration
Panel Mounting
DIN Rail Mounting
When a DIN rail mount is not desired, the Universal
LINC may be removed from the plastic housing by
separating the sections of the housing. The Universal
LINC may then be attached directly to a suitable
panel using 1/8 in. (4 mm) screws. Likewise, the
power supply may also be removed from the plastic
housing and attached directly to a suitable panel. The
option to attach the Universal LINC to the top of the
The Universal LINC232 provides several different
options for installing within a network. Each device
is shipped within a plastic housing with a DIN rail
mounting clip. The optional 5 VDC Power Supply
also uses a plastic housing with DIN rail mounting
clip.
Universal LINC
Universal LINC
DIN Rail
DIN Rail
Plastic Housing
Plastic Housing
Power Supply
Figure 3. DIN Rail Mounting Options
16
YORK INTERNATIONAL
INSTALLATION
FORM 450.20-N17 (702)
USB-style Plug
Patch
Cable
WHITE
SCREEN
GREEN
RED
BLACK
Patch Cable
Color Codes
SCREEN
P3
P2
GND
5VDC
Universal LINC
Terminations
Figure 4. DIN Rail Removal
Figure 5. USB-Style Patch Cable
Power Supply also applies to panel mounting of the
Power Supply.
5 VDC Power Supply Connection
Refer to the figure titled “Dimensions and Mounting
Points” for hole spacing requirements.
Power Connections
Universal LINC Connection
Because the Universal LINC is a small device, power
can be drawn from a controller if located within
39 in. (1 m) of the controller. When a Universal
LINC is not located within 39 in. (1 m) of a controller a separate power supply must be used. The
terminals GND and 5VDC at the LAN port should be
connected directly to the 5 VDC Power Supply.
An alternative method of connecting a Universal
LINC is to use a patch cable (Part No.
371-01429-000). This patch cable takes advantage of
the additional, USB-style connector on the newer
controllers. The patch cable combines the power and
communication wires into a single cable and doesn’t
require disconnection of the existing network cables
from the standard LAN connector.
3
The optional 5 VDC Power Supply is supplied as
either 115 or 230 ±10% volts AC at 50/60 Hz frequencies. Maximum output of the Power Supply
Module is 300 mA at 5 volts DC.
A properly color-coded wire must be obtained locally
to conform to local, state and country regulations for
connection of the 115/230 VAC line voltage. Two
leads, red and black, from the power supply connect
to the Universal LINC.
DANGER: Disconnect any line
voltage power supply at the source
before attaching wiring to prevent
possible electrocution.
The line voltage power supply should be wired to a
non-switched fused spur to prevent the power from
being turned OFF accidentally. A fuse or breaker
rated at 5 amps (115 VAC input) or 3 amps (230 VAC
input) should protect the controller from overload.
The 5 VDC Power Supply requires a 3-conductor,
power cable for the line voltage power supply, similar
to the one used by most computers. It may use a
typical plug in connector (ideal for connecting to the
Auxiliary Power Outlet in a UDC) or have bare wire
YORK INTERNATIONAL
17
INSTALLATION
0.16 in.
(4 mm)
FORM 450.20-N17 (702)
0.58 in.
(15 mm)
0.58 in.
(15 mm)
2.48 in. (63 mm)
0.98 in.
(25 mm)
A
UNIVERSAL
LINC232 UCS
STATUS
CTS
GND
TX
RX
TX
RX
RS232
PARITY
NONE
SPACE
ODD
EVEN
B1 B2
OFF OFF
ON OFF
OFF ON
BAUD
4800
9600
19K2
P1
P2
B1
B2
1
2
4
8
16
32
64
CS
CS OFF 19K2 LAN
CS ON 50K LAN
2.75 in. (70 mm)
2.32 in. (59 mm)
OFF ON
P1 P2
OFF OFF
ON OFF
OFF ON
ON ON
SCREEN
P3
TX
P2
GND
RX 5VDC
LAN
OFF ON
0.16 in.
(4 mm)
A
2.16 in. (55 mm)
on DIN rail
3.93 in. (100 mm)
0.51 in.
(13 mm)
0.51 in.
(13 mm)
2.48 in. (63 mm)
B
0.16 in.
(4 mm)
Optional Power Supply
1.77 in.
(45 mm)
Universal
LINC232
3.66 in. (93 mm)
C
B
A – Mounting Hole for Universal LINC; 0.16 in. (4 mm) diameter
B – Mounting Hole for Power Supply; 0.16 in. (4 mm) diameter
C – 2.5M x 5 stud for mounting Universal LINC on Power Supply
Power Supply
Mounting
Plate
0.16 in.
(4 mm)
C
2.95 in. (75 mm)
on DIN rail
Figure 6. Dimensions and Mounting Points
18
YORK INTERNATIONAL
INSTALLATION
FORM 450.20-N17 (702)
at the other end (for connection to a circuit breaker
box). It is recommended that the line voltage supply
cable be installed within suitable conduit if it is run
outside the enclosure. Ensure that all wiring meets
local, state and country codes, as well as follows
NEC recommendations.
To install the Power Supply Module:
DANGER: Always disconnect the
power before working inside or
around an electrical enclosure.
1. Mount the 5 VDC Power Supply using either
the DIN rail or panel mounting method.
2. Attach the black power lead from the 5 VDC
Power Supply to the GND terminal and the red
power lead to the 5 VDC terminal of the LAN
port.
3. Install conduit, if necessary to meet code,
between the device and an appropriate line
voltage power supply at a circuit breaker or
fuse box.
4. Install a 5 amp (115 volt line voltage) or 3 amp
(230 volt line voltage) fuse or circuit breaker in
the line voltage spur. Be sure to place a label on
the circuit breaker indicating the Universal
LINC power shut-off point.
5. Plug the line voltage cable into the receptacle
on the 5 VDC Power Supply. The plug is keyed
for correct orientation.
6. Either plug the line voltage cable into a standard receptacle (such as is used in the UDC) or
attach each conductor to the fuse or circuit
breaker according to regulations.
Wire Connections
The Universal LINC232 has two ports. The LAN port
is for connection directly to the network as a node or
to a controller as an external device. The LAN port
utilizes the RS485 standard. The RS232 port is for
connection to serial devices using the RS232 standard.
RS232 Connection
The RS232 standard requires a 3-core shielded cable
for transferring data. However, not all serial devices
transmit data in the same manner. In particular,
printers use the CTS pin. Also, there are two types of
connector; a 9-pin and 25-pin.
NOTE: The old style Universal
LINC232 requires the DIP switch
settings to match the type of device and
connector type to communicate with a
serial device.
To properly connect the cable to the RS232 port, refer
to the figure titled “Typical RS232 Wire Connections.” Determine the type of device and connector
style and attach the appropriate wires. Be sure to
attach the shield/screen to the GND terminal.
LAN Connection
The RS485 standard uses a twisted-pair, shielded
cable to transfer data. A 5 volt DC signal is used as
the signal and, if located within 39 in. (1 m) of a
controller (signal generator), can be used to power the
Universal LINC.
An optional patch cable (Part No. 371-01429-000) is
available to simplify connection to the LAN. (This
cable is included with the Universal LINC232
Commissioning.) This patch cable allows quick
connection to the LAN when using newer controllers,
such as the TDCE, IDC and UDC.
To connect the patch cable to the USB-style socket on
the controller, simply insert the USB-style plug into
the socket on the controller. At the Universal LINC
end, remove the standard screw terminal connector
and attach the patch cable. The patch cable is prewired to simplify connection.
The figure titled “Typical RS485 LAN Connections”
provides shows the different methods for connecting
the LAN. Note the different methods for connecting
YORK INTERNATIONAL
19
3
INSTALLATION
FORM 450.20-N17 (702)
the GND and 5VDC terminals. Power is always
connected to the LAN side.
When making RS485 connections, the cable shield
(screen) should be connected at one end to a ground
and left open (unconnected) at the other. Ideally, the
shield continues as close as possible to the device
unless the device is inside an enclosure. The Universal LINC232 provides a terminal for this purpose
labelled SCREEN.
Inside an enclosure, the shield should be connected to
a ground point as soon as possible after the cable
enters the enclosure. In this case, do not use the
SCREEN (or USHL if connecting to a controller)
terminal but connect to the closest ground/earth point.
Switch Settings
In order to provide the most flexibility with the least
amount of effort required, the Universal LINC232
uses a set of DIP switches to configure the device. As
the DIP switches are positioned, the software makes
adjustments to ensure proper operation for the
selected functions.
The Universal LINC232 (Board No. MR022) and
Universal LINC232 UCS (Part No. 371-03785-001 or
371-03876-001) differ in the terminology used for the
switch settings, particularly regarding parity. With the
Universal LINC232, the parity settings were based on
a particular device and therefore labelled by device
type. For the Universal LINC232 UCS, the parity
settings are selectable by the user and not tied specifically to a device. In addition, the transfer rates were
also increased to more accurately reflect typical baud
rates.
There are 12 DIP switches on the Universal
LINC232. They are categorized by Parity or Device
Type, Device Baud Rate, Node Address, and Communication Rate.
Parity or Device Type
The parity can be selected to accommodate virtually
any device that communicates on an RS232 protocol.
To determine specifically what the setting should be
for each device, consult the documentation for that
device. There are some typical settings which can be
used in lieu of documentation. The original Universal
LINC232 used these typical settings without specifically calling out the parity settings.
Most devices allow the parity to be set as desired.
The Universal LINC232 UCS allows the parity to be
set to match the device instead of forcing the device
to be adjusted to the Universal LINC. The following
table shows recommended settings for various YORK
products. These can, however be modified as desired.
Table 2 – Recommended Parity Settings
Device
Recommended Parity
Modem
NONE
Terminal
NONE
Facility Manager
ODD
IcE
NONE
YES*
ODD
* The Parity is not configurable in YES
9-Pin
Device
Printer Cable
25-Pin
Device
19
7
3
9-Pin
Device
7
2
3
Modem/Terminal Cable
5
2
3
Facility Manager/YES/IcE Cable
CTS
GND
TX
RX
CTS
GND
TX
RX
CTS
GND
TX
RX
Figure 7. Typical RS232 Wire Connections
20
YORK INTERNATIONAL
INSTALLATION
FORM 450.20-N17 (702)
NOTE: The position of the Parity
switches are only checked when the
Universal LINC232 is booted up. Any
changes will not take effect unless
power is reapplied.
Select the appropriate switch setting for the specific
device using the P1 and P2 (or S1 and S2) switches.
When the device type is changed, the STATUS LED
flashes once to indicate the change.
NOTE: The Modem capability is for
dial-in access to the network. For dialout capability, a LINC Guardian
Modem device is required.
The wiring must be connected as shown in the figure
titled “RS232 Wire Connections” for the Universal
LINC232 to communicate properly. The connector
styles vary with each device but typically use the
following connector style:
Printer – DB-25 Connector
Modem – DB-9 Connector
VT100 Terminal – DB-9 Connector
3
Facility Manager/YES/IcE – DB-9 Connector
Shield
(Open)
T
EX
N DE
TO NO
STATUS
Shield
(Open)
Controller
NODE SWITCH
S1
Any ISN Controller
w/ 5 VDC Power Supply
5 VDC
GND
P2
P3
USHL
SCREEN
P3
TX
P2
GND
RX 5VDC
MODE
1
2
4
8
16
32
64
CS
LAN
IN
OFF ON
LAN
PORT
Red
Black
LINC
Power
Supply
Shield
(Open)
T
EX
N DE
TO NO
T
EX
N DE
O
T NO
STATUS
Shield
(Open)
Controller
NODE SWITCH
S1
New Controller Equipped
with USB-style Connector
w/ 5 VDC from LAN
5 VDC
GND
P2
P3
USHL
SCREEN
P3
TX
P2
GND
RX 5VDC
MODE
1
2
4
8
16
32
64
CS
LAN
IN
OFF ON
LAN
PORT
T
EX
N DE
TO NO
STATUS
Controller
NODE SWITCH
S1
New Controller Equipped
with USB-style Connector
using Patch Cable
SCREEN
P3
TX
P2
GND
RX 5VDC
MODE
1
2
4
8
16
32
64
CS
OFF ON
LAN
IN
LINC
TO NEXT
NODE
TO NEXT
NODE
5 VDC
GND
P2
P3
USHL
LAN
PORT
Shield
(Open)
Figure 8. Typical RS485 LAN Connections
YORK INTERNATIONAL
21
INSTALLATION
FORM 450.20-N17 (702)
Universal LINC232 UCS
Network Status LEDs
Red LED (TX) ON – LINC
is transferring data.
Green LED (RX) ON – LINC
is receiving data.
Status LED (Red)
DOUBLE FLASH Unit OK
OFF Unit failure or loss or power
UNIVERSAL
LINC232 UCS
RS232
Device
Connection
STATUS
Network
Connection
OFF ON
CTS
GND
TX
RX
TX
RX
P1 P2
OFF OFF
ON OFF
OFF ON
ON ON
PARITY
NONE
SPACE
ODD
EVEN
B1 B2
OFF OFF
ON OFF
OFF ON
BAUD
4800
9600
19K2
CS OFF 19K2 LAN
CS ON 50K LAN
RS232
P1
P2
B1
B2
1
2
4
8
16
32
64
CS
SCREEN
P3
TX
P2
GND
RX 5VDC
LAN
RS232 Device Status LEDs
Red LED (TX) ON – LINC
is transferring data.
Green LED (RX) ON – LINC
is receiving data.
DIP Switches
Status LED (Red)
ON Unit OK
OFF Unit failure or loss or power
CONTINUOUS FLASH – Node
address set to zero (0).
Universal LINC232 (Original)
Note: A single flash indicates
the device settings are reset.
UNIVERSAL
LINC232
CTS
GND
TX
RX
TX
RX
RS232
PORT 2
S1 S2
OFF OFF
ON OFF
OFF ON
ON ON
LINC
PRINTER
FM
MODEM
TERMINAL
B1 B2
BAUD
OFF OFF 1200
ON OFF 2400
OFF ON 4800
ON ON 9600
CS OFF 19K2 LAN
CS ON 50K LAN
STATUS
OFF ON
S1
S2
B1
B2
1
2
4
8
16
32
64
CS
SCREEN
P3
TX
P2
GND
RX 5VDC
LAN
PORT 1
Figure 9. Universal LINC232 Components
22
YORK INTERNATIONAL
INSTALLATION
FORM 450.20-N17 (702)
Device Baud Rate
Communication Switch
The transfer rate of the devices which can be connected to the Universal LINC232 vary. To select the
appropriate transfer rate, use switches B1 and B2.
Four transfer rates are available, from 1200 to 9600
baud, for the original Universal LINC232 and three
rates are available, from 4800 to 19,200 (19k2) baud,
for the current, UCS variant.
The Communication Switch (CS) sets the Universal
LINC232 to communicate at the network transfer
speed. This can be either 19.2 or 50 kbaud. Set
switch CS to OFF to operate at 19.2 kbaud and ON to
operate at 50 kbaud.
NOTE: If connecting to an existing
network using Rev. 76 software or
earlier, LAN transfer rates are limited to
19.2 kbaud. For new installations, Rev.
77, and UCS software, the transfer rate
should be set to 50 kbaud.
Node Address
Each device on an ISN network must have a unique
identifier or node address. This node address can be
any number between 1 and 98.
Switches 1 through 64 are used to set the node
address. These are binary switches which, when
summed, add up to the node address.
The CS switch position is only examined when the
device is first powered up. Any changes made to the
CS switch are ignored unless power is removed and
re-applied.
Device Transfer Rate (UCS)
B1
OFF
ON
OFF
ON
B2
OFF
OFF
ON
ON
Baud Rate
4800
9600
19,200
Not Used
Device Transfer Rate (Original)
B1
OFF
ON
OFF
ON
B2
OFF
OFF
ON
ON
Baud Rate
1200
2400
4800
9600
LAN Transfer Rate
CS
OFF
ON
Parity (UCS)
Switch Settings
P1
P2
B1
B2
1
2
4
8
16
32
64
CS
P1
P2
B1
B2
1
2
4
8
16
32
64
CS
Parity or Device Type (S1)
Parity or Device Type (S2)
Device Transfer Rate
Device Transfer Rate
Node Address
Node Address
Node Address
Node Address
Node Address
Node Address
Node Address
LAN Transfer Rate
OFF ON
19.2 kbaud
50 kbaud
NOTE: Baud rate selection is
only read at power up of the unit.
Any changes during operation
will not take effect until next
power up.
P1
OFF
ON
OFF
ON
P2
OFF
OFF
ON
ON
Parity
None
Space
Odd
Even
Device Type (Original)
S1
OFF
ON
OFF
ON
S2
OFF
OFF
ON
ON
Device
Printer
Facility Manager/YES
Modem
Terminal
Node Address
Set the node DIP switches to a unique
valid address between 1 and 92. Sum
the values of each switch in the ON
position to determine the address
setting, i.e., 1 + 4 + 64 = 77
Figure 10. Universal LINC232 DIP Switch Positions
YORK INTERNATIONAL
23
3
INSTALLATION
FORM 450.20-N17 (702)
Continuity and Isolation Checks
CAUTION: Always check for isolation and continuity before applying
power to a network.
A common cause of failure of network devices is
incorrect wiring. Incorrect wiring typically causes
short circuits along the network wiring resulting in
defective RS485 transceivers. Other possible symptoms of faulty wiring are open circuits and the
presence of voltage collected by the shielding.
devices on the network. With the LAN connectors
removed from any devices:
1. Check for open circuits on the P2 and P3
conductors. Resistance should be low between
the ends of each conductor. If not, check for
breaks in the wire.
2. Check for short circuits by observing resistance
between the P2 and P3 conductors, P2 and
ground/earth, and P3 and ground/earth. The
presence of a resistance other than infinity
indicates a break in the wire.
To ensure proper wiring there are several checks that
should be completed before applying power to any
24
YORK INTERNATIONAL
MAINTENANCE
FORM 450.20-N17 (702)
SECTION 4
MAINTENANCE
LEDs
Port LEDs
The Universal LINCs are equipped with LEDs to aid
in troubleshooting operation and communications.
Each port has two Comms LEDs to signify the
module is receiving (RX) or transmitting (TX) data.
The RX LED is green and the TX LED is red.
Status LED
A red Status LED indicates operating condition. The
Universal LINC232 UCS follows the UCS LED
conventions for flash rates.
The TX LED indicates that the Universal LINC232 is
transferring data. Likewise, the RX LED indicates
data is being received by the Universal LINC232.
This applies to either port.
FLASHING – Normal operation of the Universal
LINC232. Since there is no “configured”
software, the Universal LINC232 indicates that
the software is not configured but it functions
properly. (For a controller, the software must be
configured.)
4
OFF – The device has failed or lost power.
For the original Universal LINC232, there are three
operational states for the Status LED.
ON – The device is on and operating normally.
FLASHING – The Node switch is set to 0, which
is an invalid address.
OFF – The device has failed or has lost power.
NOTE: The Status LED flashes once
whenever the device type is changed to
indicate reset.
YORK INTERNATIONAL
25
MAINTENANCE
FORM 450.20-N17 (702)
SYMPTOM
Green LED for a single device is
constantly ON.
PROBABLE CAUSE
Transceiver is damaged.
SOLUTION
Ensure LAN cable is wired correctly.
Disconnect LAN cable with power
ON. If light remains on, replace
LINC.
Network voltage levels exceeded.
Measure voltage between P2 and
P3. If greater than 5 VDC, isolate
network devices and determine
cause.
Measure voltage between P2 and
ground/earth and between P3 and
ground/earth. If greater than 12 or
less than -7 VDC, isolate networks
devices and determine cause.
Red and green LEDs for a single
device are constantly ON.
Transceiver is damaged.
Disconnect LAN cable with power
ON. If light remains on, replace
LINC.
Green LED on for all network
devices.
Multiple transceivers damaged.
Disconnect LAN devices one at a
time until fault indication disappears. Repair/replace faulty device.
Short circuit between shield and P3. Remove power and disconnect the
LAN cable at both ends. Ensure
resistance between P3 and shield is
infinite. If not, replace cable.
Status LEDs are normal but units do Multiple transceivers damaged.
not communicate.
Disconnect LAN devices one at a
time until fault indication disappears. Repair/replace faulty device.
Short circuit between P2 and P3.
Remove power and disconnect the
LAN cable at both ends. Ensure
resistance between P2 and P3 is
infinite. If not, replace cable.
Short circuit between shield and P2. Remove power and disconnect the
LAN cable at both ends. Ensure
resistance between P2 and shield is
infinite. If not, replace cable.
Network voltage levels exceeded.
Measure voltage between P2 and
P3. If greater than 5 VDC, isolate
network devices and determine
cause.
Measure voltage between P2 and
ground/earth and between P3 and
ground/earth. If greater than 12 or
less than -7 VDC, isolate networks
devices and determine cause.
26
YORK INTERNATIONAL
MAINTENANCE
FORM 450.20-N17 (702)
SYMPTOM
Green LEDs dimly lit on all devices.
PROBABLE CAUSE
Electrical noise on the network.
SOLUTION
Disconnect LAN devices one at a
time until fault indication disappears. Reroute LAN cable away
from noise source (VSDs etc.).
Polarity of P2 and P3 crossed in the Disconnect all LAN devices and
LEDs occasionally are not operating network.
check continuity.
properly (stay ON).
4
YORK INTERNATIONAL
27
APPENDIX
FORM 450.20-N17 (702)
Universal LINC232 SPECIFICATIONS
General
Electrical
Primary Power Source
Frequency
Power Consumption
Storage Temperature
Operating Environment
Maximum Altitude
Size (H x W x D)
Size (H x W x D)
Weight
5 VDC, (±5%)
N/A
Nominal 180 mA; Current limited to 250 mA
-40 to 160° F (-40 to 70° C)
32 to 122° F (0 to 50° C)
10 to 95% RH non-Condensing
6500 ft. (2000 m) above sea level
3.93 x 2.75 x 2.17 in. (100 X 70 X 55 mm) on DIN rail
3.25 x 2.00 x 0.88 in. (83 X 51 X 22 mm) Pocket Version
0.44 lb. (0.20 kg)
Processor
Memory PROM
Memory RAM
NEC V25 Operating at 8 MHz
256 kbytes of CMOS EPROM
128 kbytes of CMOS RAM
User Functions Port 1
Port 2
Terminations
Status LEDs
Switch Selections
Network Cable
RS485 LAN/USB Cable (19.2 or 50 kbaud)
RS232 Device Port (4800, 9600 or 19,200 baud)
Removable Terminal Strips. Max Cable Size 16 AWG (1.5 mm² CSA)
System Status; LAN Status; Device (RS232) Status
Device Type; Device Transfer Rate; Node Address (1-98); LAN Transfer Rate
Twisted-Pair Shielded (Belden 9272 or Equivalent)
Optional Power Supply Kit
Power
Frequency
Power Consumption
Maximum Power Output
Size (H x W x D)
Weight
115/230 VAC (±10%)
50/60 Hz (±10%)
Nominally 2VA
300 mA
3.66 x 3.78 x 2.95 in. (93 X 96 X 75 mm) on DIN rail
1.1 lb. (0.5 kg)
Optional USB Cable
Cable Length
39 in. (1 m)
Ordering Information
Universal LINC232 UCS
Universal LINC232COM UCS
5 VDC Power Supply 115 VAC Input
5 VDC Power Supply 230 VAC Input
Patch Cable
Small Enclosure with DIN Rail
Agency
28
371-03785-001
371-03876-001
371-04130-001
371-04130-002
371-01429-000
371-04131-000
UL 916 Pending
FCC Part 15 Conducted and Radiated
LVD Standard EN60950
Emission Standard EN55022; 1994 Class A
CE (Satisfying all the relevant EMC directives) and IEC950/EN60950 (Safety directive)
YORK INTERNATIONAL
APPENDIX
FORM 450.20-N17 (702)
YORK INTERNATIONAL
29
P.O. Box 1592, York, Pennsylvania USA 17405-1592
Tele. 800-861-1001 website: www.york.com
Copyright © by York International Corporation 2002
Form 450.20-N17 (702)
New Release
Unit 1, Red Shute Hill, Hermitage, Newbury, Berks RG18 9QL United Kingdom
Tele: +44 (0)1635 202200 e-mail: [email protected]
Subject to change without notice. Printed in USA
ALL RIGHTS RESERVED
Скачать