Загрузил dertygon

energies-14-01535-v2

реклама
energies
Article
Simulation of the Optimal Refrigerated Floor Design for
Ice Rinks
Wenjie Zhou 1,2 , Zhihua Gan 1, * and Lei Han 3
1
2
3
*
Institute of Refrigeration and Cryogenics, Zhejiang University, Hangzhou 310027, China;
[email protected]
Hangzhou Forstar Special Material Corporation, Hangzhou 310018, China
School of Mechanical and Electrical Engineering, Wenzhou University, Wenzhou 325035, China;
[email protected]
Correspondence: [email protected]; Tel./Fax: +86-517-87951930
Abstract: A good design of the ice rink floor could save a great deal of capital and operational costs for
hockey arenas. This ice rink floor design focuses on a cost-effective tube arrangement and an optimal
concrete coverage over the tubes that could provide sufficient heat transfer rate between the coolant
and the freezing ice. This paper reports a theoretical model to simulate the heat transfer characteristic
of a different tube diameter, spacing distance, and thickness of the concrete coverage of the tubes of
an ice rink. In addition, calcium chloride and ethylene glycol with water solutions are compared to
figure out the pros and cons of these two secondary coolants. This model prediction is compared to
the typical ice floor arrangement in order to determine the best floor construction scenario.
Keywords: heat transfer; optimal floor design; ice rink
Citation: Zhou, W.; Gan, Z.; Han, L.
Simulation of the Optimal
Refrigerated Floor Design for Ice
Rinks. Energies 2021, 14, 1535.
https://doi.org/10.3390/en14061535
Academic Editor: Alessandro Mauro
Received: 4 February 2021
Accepted: 6 March 2021
Published: 10 March 2021
Publisher’s Note: MDPI stays neutral
with regard to jurisdictional claims in
published maps and institutional affiliations.
Copyright: © 2021 by the authors.
Licensee MDPI, Basel, Switzerland.
This article is an open access article
distributed under the terms and
conditions of the Creative Commons
Attribution (CC BY) license (https://
creativecommons.org/licenses/by/
4.0/).
1. Introduction
Ice rinks are among the most energy consuming public facilities needing refrigeration,
heating, ventilation, and air conditioning. The refrigeration system accounts for almost
43% of the total operational cost for a typical ice rink arena [1]. Increasing the efficiency
of the refrigeration system could potentially save a large amount of annual energy cost.
There are several loads in the ice rink [2–4]: envelope, radiation, lighting, comfort cooling,
heating, convection, re-condensation heat transfer to the ice slab, etc. The optimal ice rink
refrigerated floor design could save capital investment cost as well as energy and long-term
operational cost.
Recently, there have been several studies focusing on improving the energy efficiency
of the ice rink. Nilsson [5] investigated the performance of carbon dioxide as secondary
coolant for the ice rink refrigeration system. Ahmed [6] presented three theoretical models
to predict the heat transfer, the airflow patterns, and the humidity distribution in a 3D
section for an ice rink. Their simulations are consistent with published Computational
Fluid Dynamics (CFD) and experimental results. Krarti, Mun, and Lin [7–10] published
several papers about the heat transfer behavior and thermal insulation layer beneath the
ice rink floors. Their models and study approaches demonstrate a good explanation of the
heat transfer phenomenon underneath the ice rink floors. Hepbasli and Caliskan [11] used
energy and exergy analysis for ice rink buildings at varying reference temperatures. The
total exergy input rate is 253.66 kW with the exergy destruction rate of 227.45 kW from the
simulation. Radermacher and Wang [12] reviewed the secondary loop refrigeration system
with carbon dioxide as the coolant. Galanis and Seghouani [13,14] studied a case of the
interaction between an ice rink and its refrigeration system. They found that it is possible
to save energy by reducing the ceiling emissivity and increasing the coolant temperature
without affecting the quality of the ice. Zmeureanu and Teysedou [15,16] developed a
benchmarking model to simulate the operational parameters of a commissioning ice rink
Energies 2021, 14, 1535. https://doi.org/10.3390/en14061535
https://www.mdpi.com/journal/energies
Energies 2021, 14, 1535
2 of 12
facility. Kuyumcu [17] reported the energy performance of the swimming pool and ice rink
coupled system. The previous research focuses on the model simulation and experimental
study of the entire ice rink arena. Although the American Society of Heating Refrigerating
and Air-conditioning Engineers (ASHRAE) refrigeration handbook provides some rough
recommendations on the cooling load of the ice rink, researchers rarely reported optimal
ice rink floor arrangement that delivered a sufficient amount of cooling during the steady
state operation. In addition, in the construction phase of the refrigerating concrete floor, it
is often difficult to tell whether the designed floor piping arrangement could potentially
deliver enough cooling and save the owner’s capital and operational costs. Therefore, it is
worthwhile to conduct a theoretical study of the heat transfer behavior of the pipe floor
at the steady state condition so that it can provide guidance for the ice rink construction
and operation.
The paper provides a good sample study of the best ice rink floor refrigeration design,
promoting both economical operation and easy maintenance of the hockey arena. There
are four sections in this paper including this Introduction. Section 2 provides a theoretical
heat transfer model for the pipe, secondary coolant, concrete, and ice. Section 3 analyzes
the cooling capacity influenced by the material and diameter of the pipe and distance
between the pipes. The cooling performance affected by the thickness of the concrete and
different refrigerant is also discussed in Section 3. Section 4 delivers the preliminary results
of the study.
2. Ice Rink Discrete Thermal Resistance Circuit Model
The refrigeration system is regarded as the core of the ice rink because it is responsible
for the quality of the ice. The ice rink refrigeration system could be direct, indirect, or a
combination of both called a partly indirect system. In the direct system, the refrigerant
is pumped directly below the ice pad, and all of the primary coolant pipes are regarded
as a huge evaporator. The direct system is less often used because there is a need for
a massive refrigerant charge such as R22, R407C, R510A, or ammonia. R22 is banned
now in many countries because of its large global warming potential and ozone depletion
potential. Ammonia has a charge limit because of its hazards and cannot be used in a large
system including the ice rink direct system. The indirect system consists of primary and
secondary refrigeration systems. This is the most conventional approach for an ice rink.
The secondary coolant is known as “brine”. It is pumped below the ice pad and returned to
the evaporator. The partly indirect system has either an evaporator or condenser connected
to the sink or source by a secondary fluid for heat exchange. In a partly indirect system,
some portion of the cooling is also provided by a direct system.
For the typical hockey rink, as shown in Figure 1, the total length of the ice-covered
space is 61 m and the width is 26 m [18]. Its area is around 1586 m2 . The half layout of
the typical hockey rink is shown in Figure 1. The insulation pad is installed between the
low temperature concrete and the normal temperature concrete to prevent cooling loss
from ice to the curb. Either steel or polyethylene pipes are embedded underneath the
ice surface inside the concrete to provide continuous cooling to the solid ice to ensure
that the high-quality ice is evenly distributed. The secondary coolant in the pipes is
typically ethylene glycol or brine water solution. Both have a low freezing point and good
thermal properties. The pipe delivering the secondary coolant to the ice pad serves as a
heat exchanger between ice and coolant. The geometry, characteristics of the fluid, and
the concrete are important parameters affecting the performance of the embedded heat
exchanger. In the ice-rink experiments, some parameters need to be measured, such as
temperatures, geometry parameters, and the mass flow of the secondary coolant etc. Other
parameters such as thermal properties of the materials can be determined by the standard
properties. A thermal resistance network heat transfer model is proposed to study the
performance of this heat exchanger. The cross-section area of the pipe is shown in Figure 2.
The thickness of the ice is shown as thice . The rink pipes are embedded inside the concrete,
and their surface is thcu away from the top of concrete. The two layers of vapor retarder are
Energies 2021, 14, 1535
3 of 12
built on the top and bottom surface of the isolation material, as shown in Figure 2, and are
used to prevent the moisture migrating to the freezing concrete. The insulation material
underneath the refrigerated concrete isolates the heated concrete and the refrigerated
concrete. The warm glycol or brine pipe is embedded in the heated concrete to avoid
heaving of the ice rink.
Figure 1. Typical hockey rink geometry parameters (half layout).
Figure 2. Cross section area of typical ice rink.
The largest cooling load demand, typically around 560 kW, is during the last period of
the hockey game. Figure 3 illustrates the discrete thermal resistance network model for
the ice rink. The model conducts a steady state heat transfer model for the largest load
demand. The radiation load from the ceiling, the convection heat transfer between air and
ice pad, and the envelop load are not modeled here because the model is built to simulate
the steady state condition for the maximum load demand. These loads affect the ice surface
temperature which is the highest concern for the hockey game. Therefore, the ice surface is
maintained at −3 ◦ C and concrete temperature is around −5 ◦ C. The secondary coolant
temperature is set at −9.5 ◦ C with the return temperature at −6 ◦ C. All the cooling capacity
required is provided by the secondary coolant.
Energies 2021, 14, 1535
4 of 12
Figure 3. Discrete heat transfer model for embedded rink pipes.
In Figure 3, one pair of coolant pipes is modeled in detail to demonstrate the thermal
resistance circuit. The heat transfer is split into three parts: the cooling from coolant pipe
.
.
to ice rink (qup ), the cooling from supply coolant to return coolant (qh ); and the cooling
.
from glycol pipe to bottom concrete (qd ). Therefore, the total cooling required can be
expressed as:
.
.
.
.
qtot = qup + qd + qh
(1)
.
qup could be considered as the heat transfer from the top of the ice rink to the secondary
.
coolant in the pipe; therefore, qup is shown in Equation (2)
.
qup =
Tice − Tin
Tice − Tout
+
Rc,u + R p + Rin + Rice
Rc,u + R p + Rin + Rice
(2)
Here, Tice stands for the ice surface temperature, Tin represents the average glycol
temperature in the pipe. Rc,u , Rp , Rin , and Rice are the thermal resistance between glycol
and ice, which are illustrated in Equations (3)–(5) and Equation (7):
Rc,u =
thcu
k con · Lrink · St
(3)
thcu is the thickness of the concrete from top of the glycol pipe to the bottom of the ice
which usually is set as 25 mm or 32 mm. kcon is the thermal conductivity of the concrete.
Lrink stands for the length of the ice rink which is 61 m. St is the pitch of one pair of glycol
pipe measured from the center of the supply glycol pipe to the center of the return glycol
pipe, which is typically set as 89 mm or 101 mm.
ln D+D2·th
Rp =
(4)
2 · π · Lrink · k p
Rp represents the thermal resistance of the pipe, which separates the coolant liquid
with the concrete. D is the pipe inner diameter, th is the thickness of the pipe, and kp is the
pipe thermal conductivity.
1
Rin =
(5)
hin · π · D · Lrink
Energies 2021, 14, 1535
5 of 12
Rin stands for the convection thermal resistance from the glycol refrigerant side. hin is
the convection heat transfer coefficient, which can be determined by the Reynolds number,
Prandtl number, and Nusselt number [19] of the glycol. The flow in the pipe is mostly in
the turbulence region since the Reynolds number is 12046 in the pipe [19].
hin ·
D
f /8 · Pr · (Re − 1000)
p
=
k in
(1 + 12.7 · (Pr0.67 − 1) · f /8)
(6)
where kin is the thermal conductivity of the secondary coolant. f is the pipe flow friction
factor affected by the roughness and Reynolds number. Pr is the Prandtl number and Re
stands for the Reynolds number inside the pipe.
Rice =
thice
k ice · Lrink · St
(7)
Rice is thermal resistance of the ice on the surface of the concrete. kice stands for the
thermal conductivity of the refrigerate ice. By adding the thermal resistance together, the
total heat transfer from ice to the coolant could be calculated using the ice temperature,
coolant inlet, and outlet temperature differential.
.
qd =
Tins − Tin
T − Tout
+ ins
Rc,d
Rc,d
(8)
Another important heat transfer is from the bottom of the concrete to the coolant pipe,
which is shown in Equation (8). In the equation, Tins stands for the temperature in the
insulation material, Tin is the supply coolant temperature, and Rc,d represents the thermal
resistance from the pipe to the insulation material.
Rc,d =
thc,d
k con · Lrink · St
(9)
The conduction heat transfer resistance is shown in Equation (9). thc,d is the distance
between the bottom of the coolant pipe and the bottom of the concrete. kcon is the conductivity of the concrete and krink is the length of the ice rink. st represents the pitch space
between the pipes.
.
Tout − Tin
qh =
(10)
Rh
The last portion of the heat transfer happens between the supply glycol pipe and the
return glycol pipe. This expression is shown in Equation (10). The horizontal conduction
resistance through concrete to the pipe is shown in Equation (11). This has a similar format
as the conduction up to the ice surface.
Rh =
St − D − 2 · th
k con · ( D + 2 · th) · Lrink
(11)
By combining these three parts of the heat load, the total cooling capacity of the typical
ice rink can be calculated as 560 kW, which is a typical load of most of the ice rinks in the
USA and Canada.
3. Model Prediction Results
The modeling results are comparable to the ASHRAE Handbook of Refrigeration
2014 [20] recommended ice rink geometry. However, the ASHRAE handbook does not
provide the detailed construction parameters for the ice rink. This paper delivers the ice
rink cooling load change with the variation of pipe pitch, pipe diameter, pipe material,
concrete thickness, and the type of secondary coolant. Therefore, the results can be a guide
to optimize the ice rink floor arrangement for designers and contractors.
Energies 2021, 14, 1535
6 of 12
The calculated cooling load by the simple heat transfer model is shown in Table 1. St
in the table stands for the pitch distance. Ntot is the pair of tubes installed in the concrete.
.
qtot is the total cooling capacity supplied from the glycol side. With an 89 mm pipe pitch,
the supplied cooling power is 562 kW. This requires 290 pieces of coolant tubes. If the pitch
increases to 102 mm, the cooling power is decreased to 560 kW but with 35 fewer pieces
of pipes.
Table 1. Cooling capacity and thermal resistance change with the different tube pitches.
.
.
.
.
St
(mm)
Ntot
-
qtot
(kW)
qup
(kW)
qd
(kW)
qh
(kW)
Ru
(K/W)
Rice
(K/W)
Rin
(K/W)
Rp
(K/W)
50.8
64
76
89
102
115
127
140
152
510
405
340
290
255
226
204
185
170
585
570
565
562
560
559
558
558
558
392
392
392
392
392
392
392
392
391
164
164
164
164
164
164
164
164
164
29
14
8.8
5.8
4.2
3.2
2.5
2
1.7
5× 10−3
4× 10−3
4× 10−3
3× 10−3
3× 10−3
2× 10−3
2× 10−3
2× 10−3
2× 10−3
4× 10−3
3× 10−3
2× 10−3
2× 10−3
2× 10−3
2× 10−3
1× 10−3
1× 10−3
1× 10−3
1× 10−4
9× 10−5
7× 10−5
6× 10−5
5× 10−5
5× 10−5
4× 10−5
4× 10−5
4× 10−5
7× 10−6
7× 10−6
7× 10−6
7× 10−6
7× 10−6
7× 10−6
7× 10−6
7× 10−6
7× 10−6
The provided cooling power to the ice rink drops from approximately 580 to 550 kW
as the pipe pitch increases from 50.8 mm to 152.4 mm, as shown in Figure 4. When the
ice rink is operating at steady state condition, the heat transfer to the top ice and bottom
insulation keeps almost constant with the increasing of the pitch between pipes. The large
heat resistance to the top ice and bottom insulation relies on the conductivity and thickness
of the concrete. Therefore, varying the pitch has little effect on the heat transfer to the top
ice. However, as the pitch goes up, there is less heat transfer from the return pipe to the
supply pipe causing a decreasing of the total cooling capacity on the slab. The best pitch is
around 89 mm or 102 mm, as shown in Figure 4. This could provide approximately 560 kW
cooling power to the freezing slab.
Figure 4. Cooling capacities at different locations with various pipe pitches.
Figure 5 illustrates the concrete and ice thermal resistance change with the change of
the pipe pitch. As the pitch space increases, both the concrete and ice thermal resistance
decreases due to the rising of the heat transfer cross section area. The thermal resistance
Energies 2021, 14, 1535
7 of 12
of the pipe wall and fluid in the pipe are at least two orders of magnitude smaller than
the concrete and ice resistance. Therefore, the concrete and ice are the dominant thermal
resistance for cooling the freezing ice. The change of the pitch space does not affect the total
cooling capacity of the secondary coolant pipes. The results could provide good guidance
for contactors or designers to reduce the number of steel tubes and further reduce the
capital cost of the ice rink.
Figure 5. Thermal resistance at the different pitch spaces.
Figure 6 shows the model calculation of the cooling capacity to different parts of the
ice rink. The cooling to the ice is responsible for approximately 69% of the total cooling
load, 29% of the cooling goes to the bottom of the concrete, and 2% flows between the glycol
supply pipe and return pipe. If there is a fairly large amount of cooling transferring to the
bottom of the concrete, one may consider increasing the insulation thickness underneath
the concrete arena to save operation energy.
Figure 6. Proportion of heat transfer to ice, concrete, and between pipes.
The tube inner diameter is also a crucial parameter for the cooling capacity. Figure 7
demonstrates the total required cooling power with the change of the inner diameter of the
pipes. The pitch of the secondary coolant tubes is usually set at 89 mm or 102 mm. The
cooling capacity is around 560 kW with 13 mm inner diameter tube. It does not increase
significantly until the inner diameter reaches 70 mm. With these results, one might consider
using 13 mm inner diameter tubes to create the ice rink; however, smaller pipes would
Energies 2021, 14, 1535
8 of 12
require more pump power and more pressure loss, which might increase the operational
cost in the future. Therefore, it is recommended to use 25 mm or 38 mm diameter tubes
for the best practice application. This shows that the cooling capacity does not change
significantly (around 560 kW) with 25 mm or 38 mm tube inner diameters as long as the
other geometry parameters and operational characteristics remain the same.
Figure 7. Total cooling capacity with different pipe inner diameters.
Typical ice rink pipes are carbon steel or polyethylene. These two types of pipe have
very different physical characteristics; therefore, the capital cost, installation cost, and heat
transfer performance of these two tubes are key factors to be taken into consideration.
Typically, the polyethylene pipe has less capital cost, but the installation cost may be
expensive and require difficult maintenance in the future. In addition, the polyethylene
material has relatively low stiffness, which might cause failure and leakage in the concrete.
Figure 8 illustrates the cooling performance comparison for different pipe materials.
Figure 8. Cooling performance with different types of tube material.
Energies 2021, 14, 1535
9 of 12
In Figure 8, the carbon steel has a high thermal conductivity of 54 W/(m×K) and,
therefore, has better heat transfer performance. The polyethylene has a low thermal
conductivity of 0.33 W/(m×K) and worse heat transfer characteristics. Figure 8 shows
the cooling performance map for different material tubes. With the same configuration,
the carbon steel pipe could deliver 560 kW cooling, while the polyethylene tube can only
deliver 491 kW cooling. However, in Figure 8, the cooling curve has a relatively steep
slope at low thermal conductivity values less than 1 W/(m×K). The cooling power goes
to a steady state around 560 kW as long as thermal conductivity rises to 5 W/(m×K).
Consideration could be given to using a type of pipe which has less thermal conductivity
than carbon steel but has thermal property of at least 5 W/(m×K). This is a good selection
from a thermal efficiency perspective. Nevertheless, designers also need to consider the
capital cost, maintenance, lifetime operation, etc. for the pipe material selection. Therefore,
the carbon steel pipe may be the best practical selection for the ice rink application.
The concrete between the pipe and the ice is another thermal resistance for the ice rink.
The function of the concrete is to hold the ice and produce a flat surface for the rink. This
also inherently creates the thermal resistance between the coolant pipe and the ice rink.
Figure 9 shows the cooling performance of the ice rink with different concrete thickness.
As the thickness of the concrete increases from 13 mm to 102 mm, the total cooling power
drops from 735 kW to 315 kW. The thicker is the concrete layer, the less cooling power is
received from the coolant pipe. The typical ice rink requires approximately 560 kW cooling;
therefore, the reasonable concrete thickness is around 25 mm. The change in the thickness
does not affect the horizontal cooling or cooling transfer to the bottom of the concrete, as
shown in Figure 9.
Figure 9. Cooling performance with different concrete thickness.
The ice rink typically uses a secondary coolant which is cooled by the primary refrigerant and then cycled through a series of pipes to the ice and back to the refrigeration system.
The ice quality depends highly on the heat transfer between the secondary coolant and ice.
The typical secondary coolant usually requires some basic characteristics, such as positive
thermal conductivity, high specific heat, low viscosity, quality chemical corrosion inhibitor,
stable, non-toxic, and non-flammable. Glycol and calcium chloride solutions are usually
adopted as the second refrigerant for the typical ice rink in North America. The heat transfer
performance of these two solutions is studied to understand the performance differences.
Figure 10 shows the cooling capacity comparison with 30% glycol and 20% CaCl2
water solution. The pitch between pipes varies from 50.8 mm to 152.4 mm (2–6 inches),
Energies 2021, 14, 1535
10 of 12
while the remaining of parameters stay same. The glycol pipe performance is always
better than the brine water performance. With the same geometry of the secondary coolant
piping, the same amount of the coolant delivered through the system, and a similar velocity,
the cooling performance still varies significantly because of the distinctive properties of
the fluids.
Figure 10. Cooling performance at various pitch distances with glycol and CaCl2 as coolant.
Table 2 shows the property comparison of these two fluids. Glycol fluid has Reynolds
number 12,849, indicating the flow is in the turbulence flow region, providing a sufficient
heat transfer coefficient. The Reynolds number of the brine solution is 7142, indicating the
flow is less disturbed than the glycol solution, resulting in a lower heat transfer coefficient.
Because this is only one pair of pipes (there are around 300 pairs), the accumulative effect
further differentiates the cooling performance between glycol and brine. In Table 2, the
dynamic viscosity of glycol is almost 46% less than that of the brine solution. The brine
has higher thermal conductivity than the glycol solution and higher density. Thus, if using
brine as secondary coolant, one may consider increasing the flow rate to ensure that the
system is working under turbulence flow region to maintain good cooling performance.
Table 2. Properties of glycol and brine solution.
(kg/m3 )
Dynamic
Viscosity
(pa×s)
Thermal
Conductivity
(W/(m×K))
1110
1207
0.003
0.0055
0.2579
0.5244
Parameters
Specific Heat
Density
Unit
(J/(kg×K))
30% Glycol
20% CaCl2
3726
3019
In addition, the specific heat of glycol is approximately 23% higher than that of the
brine. With the same mass flow rate and same temperature change, the cooling capacity
of brine should be around 23% less than that of glycol. Due to the lower specific heat and
higher viscosity of brine, under the same flow conditions, the brine provides 25% less
cooling capacity compared with glycol solution.
Energies 2021, 14, 1535
11 of 12
4. Conclusions and Discussion
There are several combinations for the ice rink piping geometry. In this study, a
discrete theoretical heat transfer model was built to simulate the optimal ice rink floor
piping arrangement. The best practical ice rink arena arrangement is recommended in
Table 3.
Table 3. The best practical ice rink floor arrangement.
.
Parameters
St
(mm)
D
(mm)
Material
(-)
thcon
(mm)
Coolant
(-)
qtot
(kW)
This work
102
38
Carbon
steel
25
Glycol
560
Traditional
arrangement
89
25
-
25
Glycol or
brine
560
As shown in Table 3, the 102 mm pitch space with 38 mm diameter carbon steel pipe
could provide 560 kW cooling capacity while saving the capital cost of the secondary
refrigeration system. In addition, the pumping work will be smaller with larger diameter
pipes saving operational costs in the long term. The glycol solution shows better heat
transfer and flow performance for cooling the ice pad than that of the brine water solution.
This study demonstrates a potential method to save the capital cost and operational cost in
the long term for the typical ice rink arena.
Author Contributions: Conceptualization, W.Z.; methodology, W.Z.; software, W.Z. and L.H.; validation, W.Z.; Z.G. and L.H.; formal analysis, L.H.; investigation, W.Z.; resources, W.Z.; data curation,
L.H.; writing—original draft preparation, W.Z.; writing—review and editing, Z.G. and L.H.; visualization, L.H.; supervision, Z.G.; project administration, W.Z.; funding acquisition, Z.G. All authors
have read and agreed to the published version of the manuscript.
Funding: This research was funded by the National Natural Science Foundation of China, grant
number 51806191 and Zhejiang Provincial Natural Science Foundation of China, grant number
LY21E060003.
Institutional Review Board Statement: Not applicable.
Informed Consent Statement: Not applicable.
Data Availability Statement: Not applicable.
Conflicts of Interest: The authors declare no conflict of interest.
Abbreviations
D = diameter of pipe, mm
f = friction factor of the pipe
h = convection heat transfer coefficient, W/m2 -K
k = thermal conductivity, W/m-K
L = length of ice rink, m
N = number of pipe pairs
Pr = Prandtl number
.
q = cooling capacity rate, W
R = thermal resistance, K/W
Re = Reynolds number
S = pitch space between one pair of pipe, mm
T = temperature, K
th = wall thickness, mm
Energies 2021, 14, 1535
12 of 12
Subscripts:
con = concrete
c,d = down through the concrete
c,u = up through the concrete
d = down to the insulation pad
h = horizontal
ice = ice surface
in = inside the pipe
ins = insulation
out = outside
p = pipe
rink = ice rink
tot = total
t = pitch distance
up = up to the ice surface
References
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
Chuangchid, P.; Krarti, M. Foundation heat loss from heated concrete slab-on-grade floors. Build. Environ. 2001, 36, 637–655.
[CrossRef]
Bellache, O.; Ouzzane, M.; Galanis, N. Coupled conduction, convection, radiation heat transfer with simultaneous mass transfer
in ice rinks. Numer. Heat Trans. Part A 2005, 48, 219–238. [CrossRef]
Bellache, O.; Ouzzane, M.; Galanis, N. Numerical prediction of ventilation and thermal processes in ice rinks. Build. Environ.
2005, 40, 417–426. [CrossRef]
Bellache, O.; Galanis, N.; Ouzzane, M.; Sunyé, R.; Giguère, D. Two-Dimensional transient model of airflow and heat transfer in
ice rinks (1289-RP). ASHRAE Trans. 2006, 112, 706–716.
Nilsson, J.; Sawalha, S.; Shahzad, K. Ice rink refrigeration system with carbon dioxide as secondary fluid copper tubes. In
Proceedings of the Seventh IIR-Gustav Lorentzen Conference on Natural Working Fluids, Trondheim, Norway, 29–31 May 2006.
Daoud, A.; Galanis, N.; Bellache, O. Calculation of refrigeration loads by convection, radiation and condensation in ice rinks
using a transient 3D zonal model. Appl. Therm. Eng. 2008, 28, 1782–1790. [CrossRef]
Somrani, R.; Mun, J.; Krarti, M. Heat transfer beneath ice-rink floors. Build. Environ. 2008, 43, 1687–1698. [CrossRef]
Mun, J.; Krarti, M. An ice rink floor thermal model suitable for whole-building energy simulation analysis. Build. Environ. 2011,
46, 1087–1093. [CrossRef]
Mun, J.; Krarti, M. Optimal insulation for ice rink floors. Energy Build. 2015, 108, 358–364. [CrossRef]
Lin, J.; Chuah, Y. Prediction of infiltration rate and the effect on energy use for ice rinks in hot and humid climates. Build. Environ.
2010, 45, 189–196. [CrossRef]
Caliskan, H.; Hepbasli, A. Energy and exergy analyses of ice rink buildings at varying reference temperatures. Energy Build. 2010,
42, 1418–1425. [CrossRef]
Wang, K.; Eisele, M.; Hwang, Y.; Radermacher, R. Review of secondary loop refrigeration systems. Int. J. Refrig. 2010, 33, 212–234.
[CrossRef]
Seghouani, L.; Daoud, A.; Galanis, N. Prediction of yearly energy requirements for indoor ice rinks. Energy Build. 2009, 41,
500–511. [CrossRef]
Seghouani, L.; Daoud, A.; Galanis, N. Yearly simulation of the interaction between an ice rink and its refrigeration system: A case
study. Int. J. Refrig. 2011, 34, 383–389. [CrossRef]
Teyssedou, G.; Zmeureanu, R.; Giguère, D. Benchmarking model for the ongoing commissioning of the refrigeration systemof an
indoor ice rink. Autom. Constr. 2013, 35, 229–237. [CrossRef]
Khalid, W.; Rogstam, J. Energy usage prediction model comparing outdoor vs. indoor ice rinks. Energy Build. 2013, 67, 195–200.
[CrossRef]
Kuyumcu, M.E.; Tutumlu, H.; Yumrutaş, R. Performance of a swimming pool heating system by utilizing waste energy rejected
from an ice rink with an energy storage tank. Energy Convers. Manag. 2016, 121, 349–357. [CrossRef]
IIHF. Technical Guide of an Ice Rink; Report from the International Ice Hockey Federation; Zurich, 2006; Volume 3.
Nellis, G.; Klein, S. Heat Transfer; Cambridge, Madison, WI, USA, 2012.
ASHRAE. ASHRAE Handbook of Refrigeration; American Society of Heating, Refrigerating and Air Conditioning Engineers:
Washington, DC, USA, 2018.
Скачать