Uploaded by igor barmut

Tube Plugs

advertisement
SERVICE
Servicing Coolers and Condensers — When cool-
er heads and partition plates are removed, tube sheets are
exposed showing the ends of tubes. The 30HX units use a
flooded cooler design. Water flows inside the tubes.
TUBE PLUGGING — A leaky tube in one circuit can be
plugged until retubing can be done. The number of tubes
plugged determines how soon the cooler must be retubed. All
tubes in the 30HX coolers and condensers can be removed.
Loss of unit capacity and efficiency as well as increased pump
power will result from plugging tubes. Failed tubes should be
replaced as soon as possible. Up to 10% of the total number of
tubes per pass can be plugged before retubing is necessary. Figure 22 shows an Elliott tube plug and a cross-sectional view of
a plug in place. The same components for plugging and rolling
tubes can be used for all coolers and 30HXC condensers. See
Table 31. If tube failure is in both circuits, using tube plugs will
not correct problem. Contact your Carrier representative for
assistance.
PIN
RING
TUBE SHEET
PIN
CAUTION
Use extreme care when installing plugs to prevent damage
to the tube sheet section between the holes.
TUBE
RING
RETUBING (See Table 32) — When retubing is to be done,
obtain service of qualified personnel experienced in boiler
maintenance and repair. Most standard procedures can be
followed when retubing the 30HX heat exchangers. Care must
be taken as the tubes are rolled in the center tube sheet and
require special pulling tools. A 7% crush is recommended
when rolling replacement tubes into the tubesheet. A 7% crush
can be achieved by setting the torque on the gun at 48 to 50 in.lb (5.4 to 5.6 N-m).
Place one drop of Loctite No. 675 or equivalent on top of
tube prior to rolling. This material is intended to “wick” into
the area of the tube that is not rolled into the tube sheet, and
prevent fluid from accumulating between the tube and the tube
sheet. New tubes must also be rolled into the center tube sheet
to prevent circuit-to-circuit refrigerant leakage.
PIN AND RING INSTALLED
Fig. 22 — Tube Plugging
TIGHTENING COOLER/CONDENSER HEAD BOLTS
O-Ring Preparation — When reassembling cooler and condenser heads, always check the condition of the O-ring(s) first.
The O-ring should be replaced if there are any visible signs of
deterioration, cuts or damage. Apply a thin film of grease to the
O-ring before installation. This will aid in holding the O-ring
into the groove while the head is installed. Torque all bolts
to the following specification and in the sequence shown in
Fig. 23.
3/ -in. Diameter Perimeter and
4
Plate Bolts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 to 225 ft-lb
(271 to 305 N-m)
1. Install all bolts finger tight.
2. Follow numbered sequence shown for head type being
installed. This will apply even pressure to the O-ring.
3. Apply torque in one-third steps until required torque is
reached. Load all bolts to each one-third step before
proceeding to the next one-third step.
4. No less than one hour later, retighten all bolts to required
torque values.
5. Restore water/brine flow and check for leaks. Fix leaks as
necessary. Replace insulation (on cooler heads only).
Table 31 — Plugging Components
COMPONENTS FOR PLUGGING
For Tubes
Brass Pin
Brass Ring
For Holes without Tubes
Brass Pin
Brass Ring
Roller Extension
Loctite
Locquic
PART NUMBER
853103-1*
853002-640* or -657†
853103-1A*
853002-738*
S82-112/11
No. 675**
“N”**
*Order directly from: Elliott Tube Company, Dayton, Ohio.
†Measure tube ID before ordering.
**Can be obtained locally.
Table 32 — Tube Diameters
ITEM
Tube sheet hole diameter:
Tube OD
Tube ID after rolling:
(includes expansion
due to clearance)
INCHES
0.756
0.750
0.650
to
0.667
Inspecting/Cleaning Heat Exchangers
COOLERS — Inspect and clean the cooler tubes at the end of
the first operating season. Because these tubes have internal
ridges, a rotary-type tube cleaning system is necessary to fully
clean the tubes. Tube condition in the cooler will determine the
scheduled frequency for cleaning, and will indicate whether
water treatment is adequate in the chilled water/brine circuit.
Inspect the entering and leaving thermistors for signs of corrosion or scale. Replace the sensor if corroded or remove any
scale if found.
MILLIMETERS
19.20
19.05
16.51
to
16.94
NOTE: Tubes replaced along heat exchanger head partitions must
be flush with tube sheet.
50
Download