U-Series Molded Case Circuit Breaker HYUNDAI U-Series Molded Case Circuit Breaker CONTENTS 04 Introduction • 06 Features • 11 Quick Selection Table 135 Characteristic Curves & Dimensions • • 187 Accessories 245 Handling Instruction | Inspection and Maintenance 15 Rating Overview • • 33 Specifications and Standard Order Codes 221 Technical Information • 236 Order Information for YOU & being NEW The design concepts of U-Series MCCB pursue advanced technology in size, customized characteristic in range and powerful capability in specification. All come out from our sincerity to be close to you. HYUNDAI U-Series Molded Case Circuit Breaker ADVANCED TECHNOLOGY in size [ UAB type ] CUSTOMIZED CHARACTERISTIC in range [ UCB type ] POWERFUL CAPABILITY in specification [ UPB type ] U-Series / Molded Case Circuit Breaker Introduction | Wide and powerful range | UAB, UCB Type [ up to 1600AF ] | Compact size | Wide and powerful range • High breaking capacity in 60mm depth, up to 250AF • 50, 125, 250, 400, 630, 800, 1000, 1250, 1600AF • Application of current-limiting technology • Fixed or adjustable thermal trip mechanism up to 800AF • UAB type • Double protected electronic trip mechanism for 1600AF - up to 25kA at AC380/415V in W75 x H130 x D60mm • UCB type - up to 50kA at AC380/415V in W90/105 x H165 x D60mm 4 | Various accessories | Reliable quality • Motor operator and operating handles for smooth operation • Terminal cover and terminal busbar for safety • Type-tested by KEMA Netherlands • DIN rail adapter and mounting base for easy installation • Switches and trip devices for control by signals MCCB | Modern and customized design | UPB, HBL Type Miniature Type | High breaking capacity | Industrial and residential application • Up to 150kA at AC380/415V • Based on current-limiting technology • Ics = 100% Icu • Mini molded case circuit breaker • Mini earth leakage circuit breaker • Up to 100A, 10kA | Reliable quality | Various protection • Type-tested by international test authorities • KEMA for IEC standard, KERI for NEMA standard • Short-circuit and overload • Earth leakage protection | Diverse trip mechanism and application | Internal accessories • Fixed & adjustable thermal, electronic • Motor protection, nuclear power plant • Auxiliary switch • Trip alarm switch • Shunt trip [ 125, 160, 250, 400, 630AF ] [ 30, 50, 100AF ] Molded Case Circuit Breaker_ 5 U-Series / Molded Case Circuit Breaker Features | Adjustable rating in full range with diverse trip mechanisms | •U-Series MCCB adopts adjustable rating function in full range from 50 to 1600AF. With diverse trip mechanisms of U-Series MCCB, you will be provided with wide options for system design and more flexible load fluctuations. [ UAB, UCB type ] Fixed thermal Adjustable thermal [ UPB type ] Fixed thermal Adjustable thermal 6 Electronic Adjustable instantaneous for motor protection MCCB | Wide and powerful production range | •U-Series MCCB supplies you with wide and powerful production range; 3 to 1600A, 5 to 150kA at AC415V from general distribution boards to nuclear power plants. U-Series MCCB also completely covers Hi-Series MCCB range with better characteristics. Thermal magnetic type Icu 150 kA 130 kA 100 kA 85 kA 50 kA 42 kA 36 kA 30 kA 25 kA 18 kA 10 kA 5 kA (at 415V) Hydraulic magnetic Fixed thermal Adjustable thermal UPB160X UPB100X UPB160L UPB100L UPB100H UPB160H UPB100S UPB160S UCB100L UCB160L UCB160H UCB100H UCB50L UCB50H UCB100S UAB100S UAB100R, UCB100R UAB50H UAB50S, UCB50R UAB30R UAB50R UAB30C UAB50C 30AF UPB250X UCB630L UPB250L UCB800L UCB630H UCB400L UPB250H UCB800H UPB250S UCB400H UCB630S UCB800S UCB800R UCB630R UCB250L (45kA) (45kA) UCB250H UCB400S UCB250N UCB400R UCB250S UCB250R UAB60R UAB100C UAB60C 50AF 60AF 100AF 125AF 160AF 250AF 400AF 630AF 800AF Electronic type Icu 150 kA 130 kA 100 kA 85 kA UPB100X UPB160L UPB100L UPB100H UPB100S UPB250X UPB160X UPB160H UPB250L UPB400H UPB250S UPB630L UPB400L UPB250H UPB160S UPB630X UPB400X UPB630H UCB1000L UCB1000S UCB1250L UCB1250S UPB630S UPB400S UCB1600S 65 kA (at 415V) 125AF 160AF 250AF 400AF 630AF 1000AF 1250AF 1600AF Miniature type Fixed Thermal Icu 10 kA 5 kA 2.5 kA UMB50H, UDB50H UMG50H, UDG50H UMB30H, UDB30H UMG30H, UDG30H UMB30S, UDB30S UMG30S, UDG30S UMB50S, UDB50S UMG50S, UDG50S UDB100H UDG100H UDB100S UDG100S UMB30R UMG30R (at 220V) 30AF 50AF 100AF Motor protection - UPB type 125-250AF Q-class HBL type - 100-225AF Switch disconnector - UAD type 50-100AF, UCD type 50-1250AF, UPD type 125-630AF Molded Case Circuit Breaker_ 7 U-Series / Molded Case Circuit Breaker Features | High breaking capacity, realized by advanced technology and optimized design | •Our optimized design by advanced current-limiting technology allows U-Series MCCB to realize high breaking capacity in a smaller size compared to Hi-Series MCCB, contributing to compact design of system. Same breaking capacity in 30% smaller size High breaking capacity in same size •The current-limiting characteristic of U-Series MCCB also minimizes the effects from fault currents and offers cost-effectiveness. [UPB type] Handle Trip button Trip(OCR) unit Arc-chamber unit Terminal Mechanism Moving contact device Fixed contact device Maximized repulsive-force trip mechanism Realized by twin contact structure (two contacts in fixed contact device, other two in moving contact device), up-down direction repulsion at both sides of rotary structure, and u-shaped terminal structure of fixed contact. Contribute to increase of main contact travel distance, prevention of arc re-ignition, and correct lead of arc projection to arc chute. Arc pressure actuator (APA) Arc pressure occurred by short-circuit current can be detected through APA and operates trip mechanism before the response of trip sensor. Minimizing total breaking time, Maximizing current-limiting performance 8 MCCB | Standardization of dimensions | •U-Series MCCB minimizes the difference in size of each model, so that they can be easily replaced whenever the specifications of the system changes. 50mm 50AF 125AF •UAB type : 30-100AF 250AF 60mm •UCB type : 50-250AF | Reliable quality and various applications | •U-Series MCCB is type-tested by international test authorities such as KEMA and KERI as well satisfying IEC60947-2 and NEMA AB-1 standards. It also acquired various marine classes and certificates for nuclear power plants. Molded Case Circuit Breaker_ 9 U-Series / Molded Case Circuit Breaker Features | Modern and refined design | Model name Line side terminal •UPB : Type •250 : Ampere frame size •X : Recognition code for order Rated frequency Utilization category Ampere frame size Suitability of isolation Rated current Main characterisitics •Ui : Rated insulation voltage •Uimp : Rated impulse withstand voltage •Ue : R ated operational voltage •Icu : R ated ultimate short-circuit breaking capacity •Ics : R ated service short-circuit breaking capacity Standard Trip unit Trip button Load side terminal Approvals and certificates 10 Quick Selection Table + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + U-Series / Molded Case Circuit Breaker Quick Selection Table | UAB type / 30-100AF | Ampere frame 30 50 60 100 Model Number of poles Rated current (A) UAB30C UAB30R UAB50C UAB50R UAB50S UAB50H UAB60C UAB60R UAB100C UAB100R UAB100S 2, 3 2, 3 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 3, 5, 10, 15, 20, 30 5, 10, 15, 20, 30 5, 10, 15, 20, 30, 40, 50 5, 10, 15, 20, 30, 40, 50 15, 16, 20, 25, 30, 32, 40, 50 15, 16, 20, 25, 30, 32, 40, 50 5, 10, 15, 20, 30, 40, 50, 60 5, 10, 15, 20, 30, 40, 50, 60 5, 10, 15, 20, 30, 40, 50, 60, 75, 100 15, 16, 20, 25, 30, 32, 40, 50, 60, 63, 75, 80, 100 15, 16, 20, 25, 30, 32, 40, 50, 60, 63, 75, 80, 100 Breaking capacity [Icu] (kA r.m.s.) Trip mechanism & Characteristics AC220V AC380V AC440V AC600V Hydraulic AC240V AC415V AC460V AC660V magnetic 10 25 10 25 42 50 10 25 25 42 50 7.5/5 14/10 7.5/5 14/10 25 30 7.5/5 14/10 14/10 25 30 5 10 5 10 21 25 5 10 10 21 25 2.5 5 2.5 5 7.5 10 2.5 5 5 7.5 10 ○ ○ ○ ○ ○ ○ ○ - Dimensions (mm) Thermal magnetic Fixed Adjustable ○ ○ ○ ○ Width Height Depth 50/75 130 60 50/75/100 130 60 ○1) ○1) ○1) ○1) ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Not applicable to 2P breaker. | UCB type / 50-1600AF | Ampere frame Model UCB50R 50 UCB50H UCB50L UCB100R UCB100S 125 UCB100H UCB100L UCB160H 160 UCB160L UCB250R UCB250S 250 UCB250N UCB250H UCB250L UCB400R UCB400S 400 UCB400H UCB400L UCB630R UCB630S 630 UCB630H UCB630L UCB800R UCB800S 800 UCB800H UCB800L UCB1000S 1000 UCB1000L UCB1250S 1250 UCB1250L 1600 UCB1600S Number of poles Rated current (A) 2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 2, 3, 4 2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 3, 4 3, 4 3, 4 3, 4 3 15, 20, 30, 40, 50 15, 16, 20, 25, 30, 32, 40, 50 15, 16, 20, 25, 30, 32, 40, 50 15, 16, 20, 25, 30, 32, 40, 50, 60, 63, 75, 80, 100, 125 15, 16, 20, 25, 30, 32, 40, 50, 60, 63, 75, 80, 100, 125 15, 16, 20, 25, 30, 32, 40, 50, 60, 63, 75, 80, 100, 125 15, 16, 20, 25, 30, 32, 40, 50, 60, 63, 75, 80, 100, 125 100, 125, 160 100, 125, 160 100, 125, 150, 160, 175, 200, 225, 250 100, 125, 150, 160, 175, 200, 225, 250 100, 125, 150, 160, 175, 200, 225, 250 125, 150, 160, 175, 200, 225, 250 125, 150, 160, 175, 200, 225, 250 250, 300, 320, 350, 400 250, 300, 320, 350, 400 250, 300, 320, 350, 400 250, 300, 320, 350, 400 500, 630 500, 630 500, 630 500, 630 700, 800 700, 800 700, 800 700, 800 505-1,000 505-1,000 630-1,250 630-1,250 640-1,600 Breaking capacity [Icu] (kA r.m.s.) Trip mechanism & Characteristics AC220V AC380V AC440V AC600V AC240V AC415V AC460V AC660V Thermal magnetic Electronic Fixed Adjustable 50 85 100 50 65 85 100 85 100 35 50 65 85 100 35 50 85 125 50 100 100 125 50 100 100 125 100 150 100 150 100 30/25 42 50 30/25 42/36 42 50 42 50 25/18 35/25 42/36 42 50 30 42 65 100 45 65 85 100 45 65 85 100 100 130 100 130 65 25 42 50 25 35 42 50 42 50 18 25 35 42 50 25 35 50 85 35 50 65 85 35 50 65 85 75 100 75 100 45 10 20 25 10 18 20 25 20 25 7.5 10 18 20 25 18 22 25 30 22 25 35 35 25 25 35 35 40 60 40 60 25 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ - ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. 12 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ - ○ ○ ○ ○ ○ Dimensions (mm) Width Height Depth 60/90/120 155 60 90/90/120 155 60 60/90/120 155 60 90/90/120 155 60 105/105/140 165 60 105/105/140 164 60 105/105/140 165 60 140/140/185 257 110 210/210/280 280 110 210/280 210/280 210/280 210/280 210 370 370 370 370 371 110 200 110 200 151 MCCB | UPB type / 125-630AF | Ampere frame 125 160 250 400 630 Model Number of poles Rated current (A) UPB100S UPB100H UPB100L UPB100X UPB160S UPB160H UPB160L UPB160X UPB250S UPB250H UPB250L UPB250X UPB400S UPB400H UPB400L UPB400X UPB630S UPB630H UPB630L UPB630X 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 15, 16, 20, 25, 30, 32, 40, 50, 60, 63, 75, 80, 100, 1251) 15, 16, 20, 25, 30, 32, 40, 50, 60, 63, 75, 80, 100, 1251) 15, 16, 20, 25, 30, 32, 40, 50, 60, 63, 75, 80, 100, 1251) 15, 16, 20, 25, 30, 32, 40, 50, 60, 63, 75, 80, 100, 1251) 100, 125, 1601) 100, 125, 1601) 100, 125, 1601) 100, 125, 1601) 125, 150, 160, 175, 200, 225, 2501) 125, 150, 160, 175, 200, 225, 2501) 125, 150, 160, 175, 200, 225, 2501) 125, 150, 160, 175, 200, 225, 2501) 200-400 200-400 200-400 200-400 320-630 320-630 320-630 320-630 Breaking capacity [Icu] (kA r.m.s.) Trip mechanism & Characteristics AC220V AC380V AC440V AC660V AC240V AC415V AC460V AC690V Thermal magnetic Electronic Fixed Adjustable 100 130 150 200 100 130 150 200 100 130 150 200 100 130 150 200 100 130 150 200 85 100 130 150 85 100 130 150 85 100 130 150 85 100 130 150 85 100 130 150 65 85 100 150 65 85 100 150 65 85 100 150 65 85 100 150 65 85 100 150 10 10 25 25 10 10 25 25 10 10 25 25 10 10 25 25 10 10 25 25 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ - ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ - ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ Dimensions (mm) Width Height Depth 105/140 165 86.5 140/185 255 117 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Rated current of electronic types are as followings; ·UPB100: 50-125A ·UPB160: 63-160A ·UPB250: 100-250A | Motor protection / UPB type 125-250AF | Ampere frame 125 250 Breaking capacity [Icu] (kA r.m.s.) Dimensions (mm) Model Number of poles Rated current (A) AC220V AC240V AC380V AC415V AC440V AC460V AC660V AC690V Width Height Depth UPB100H UPB100L UPB250H UPB250L 3 3 3 3 2.5, 3.2, 6.3, 12.5, 20, 32, 50, 63, 80, 100 2.5, 3.2, 6.3, 12.5, 20, 32, 50, 63, 80, 100 125, 150, 175, 200, 225 125, 150, 175, 200, 225 130 150 130 150 100 130 100 130 85 100 85 100 10 25 10 25 105 165 86.5 ※ The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. | Q-class (for nuclear power plant application) / HBL type 100-225AF | Ampere frame Model HBL103U HBL103UQ 100 HBL103UM HBL103UMQ HBL203U HBL203UQ 225 HBL203UM HBL203UMQ Number of poles Rated current (A) 3 3 3 3 3 3 3 3 15, 20, 30, 40, 50, 60, 75, 100 15, 20, 30, 40, 50, 60, 75, 100 2.5, 3.2, 6.3, 12.5, 20, 32, 50, 63, 80, 100 2.5, 3.2, 6.3, 12.5, 20, 32, 50, 63, 80, 100 125, 150, 175, 200, 225 125, 150, 175, 200, 225 125, 150, 175, 200, 225 125, 150, 175, 200, 225 Breaking capacity [Icu] (kA r.m.s.) Characteristics Dimensions (mm) AC220V AC380V AC440V AC480V AC660V E1 class Motor Width Height Depth AC240V AC415V AC460V AC500V AC690V protection 200 200 200 200 200 200 200 200 150 150 150 150 150 150 150 150 100 100 100 100 100 100 100 100 85 85 85 85 85 85 85 85 25 25 25 25 25 25 25 25 ○ ○ ○ ○ ○ ○ ○ ○ 105 165 86.5 ※ The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. Molded Case Circuit Breaker_ 13 U-Series / Molded Case Circuit Breaker Quick Selection Table | Switch disconnector / 50-1250AF | Type Ampere frame UCD Model Dimensions (mm) Number Rated of poles current (A) Width Height Depth 50 UCD50H 3 50 100 UCD100S 3 100 125 UCD100H 3 125 160 UCD160H 3 160 105 165 UCD250S 3 250 105 164 250 90 155 Type Ampere frame Model Dimensions (mm) Number Rated of poles current (A) Width Height Depth 50 UAD50C 3 UAD50S 3 50 100 UAD100R 3 100 60 125 UPD100S 3 125 60 160 UPD160S 3 160 60 UCD250H 3 250 105 165 60 400 UCD400S 3 400 140 257 110 630 UCD630S 3 630 800 UCD800S 3 800 1000 UCD1000S 3 1,000 1250 UCD1250S 3 1,250 210 280 110 210 370 110 50 UAD UPD 250 UPD250S 3 250 400 UPD400S 3 400 630 UPD630S 3 630 75 130 60 105 165 86.5 140 255 117 | Miniature type / 30-100AF | Type Ampere frame 30 UMB 50 30 UDB 50 100 30 UMG 50 30 UDG 50 100 Model Number of poles Rated current (A) Breaking capacity [Icu] (kA r.m.s.) AC380V AC415V AC440V AC460V Width Height Depth UMB30Ra 2 15, 20, 30 2.5 - - 33 70 42 UMB30Rb 2 15, 20, 30 2.5 - - 33 70 60 UMB30Sg 2 15, 20, 30 5 - - UMB30Hg 2 15, 20, 30 10 - - UMB50Sg 2 15, 20, 30, 40, 50 5 - - 35 80 60 UMB50Hg 2 15, 20, 30, 40, 50 10 - - UDB30S 2, 3 3, 5, 10, 15, 20, 30 5 2.5 2.5 UDB30H 2, 3 5, 10, 15, 20, 30 10 5 5 UDB50S 2, 3 5, 10, 15, 20, 30, 40, 50 5 2.5 2.5 50/75 96 60 UDB50H 2, 3 75 96 60 5, 10, 15, 20, 30, 40, 50 10 5 5 UDB100S ✽2, 3 15, 20, 30, 40, 50, 60, 75, 100 5 2.5 2.5 UDB100H ✽2, 3 15, 20, 30, 40, 50, 60, 75, 100 10 5 5 UMG30Ca 2 15, 20, 30 1.5 - - 33 70 42 UMG30Cb 2 15, 20, 30 1.5 - - 33 70 60 UMG30Ra 2 15, 20, 30 2.5 - - 33 70 42 UMG30Rb 2 15, 20, 30 2.5 - - 33 70 60 UMG30Cd 2 15, 20, 30 1.5 - - UMG30Rd 2 15, 20, 30 2.5 - - 62 82 42 UMG30Sg 2 15, 20, 30 5 - - UMG30Hg 2 15, 20, 30 10 - - UMG50Sg 2 15, 20, 30, 40, 50 5 - - 35 80 60 UMG50Hg 2 15, 20, 30, 40, 50 10 - - UDG30S 2, 3 3, 5, 10, 15, 20, 30 5 2.5 2.5 UDG30H 2, 3 5, 10, 15, 20, 30 10 5 5 UDG50S 2, 3 5, 10, 15, 20, 30, 40, 50 5 2.5 2.5 50/75 96 60 UDG50H 2, 3 75 96 60 5, 10, 15, 20, 30, 40, 50 10 5 5 UDG100S ✽2, 3 15, 20, 30, 40, 50, 60, 75, 100 5 2.5 2.5 UDG100H ✽2, 3 15, 20, 30, 40, 50, 60, 75, 100 10 5 5 ※ - KS certified products. English nameplate and 50Hz marking are not available. - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. 14 Dimensions (mm) AC220V AC240V Rating Overview + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + U-Series / Molded Case Circuit Breaker Rating Overview | UAB type / 30-50AF | Model UAB30 UAB50 Figure Ampere frame size Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Rated current (A) Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Recognition code for order AC600/660V, 50-60Hz Rated AC480/500V, 50-60Hz short-circuit Ultimate AC440/460V, 50-60Hz breaking [Icu] AC380/415V, 50-60Hz capacity (kA r.m.s.) AC220/240V, 50-60Hz IEC 60947-2 DC250V K 60947-2 DC125V Service [Ics] % of [Icu] Hydraulic Fixed thermal, magnetic Fixed instantaneous INST Trip mechanism Fixed thermal, & Protection Thermal Fixed instantaneous INST magnetic Adjustable thermal, LTD characteristics Fixed instantaneous INST Direct mounting by screw for Both line & load side Switchboard Line side only Mounting Plug-in for Distribution board DIN-rail with DIN-rail adaptor Terminal connection Screw Auxiliary switch AUX Trip alarm switch ALT Signal Shunt trip SHT Under voltage trip UVT Operating Surface type TFG handle Extended type TFH Accessories Operating Motor operator MOT Mechanical interlock MIF Padlock plate PLD DIN-rail adaptor DRA Mounting Plug-in mounting base TDM Cage terminal block CTB Terminal Terminal cover TCF Interpole barrier TQQ Durability Mechanical operation (times) Electrical operation Width a d a c b Height Dimensions 2/3/4P b c Depth (mm) d Weight (kg, breaker only) 2/3/4P 30AF 50AF 2, 3 2, 3, 4 2, 3, 4 IP20 IP20 IP20 A A A ○ ○ ○ overload, inst., short-circuit overload, inst., short-circuit overload, inst., short-circuit 3,5,10,15,20,30 5,10,15,20,30 5,10,15,20,30,40,50 15,16,20,25,30,32,40,50 AC690 AC690 AC690 AC660 AC660 AC660 - -DC250 6 6 6 C R C R S H 2.5 5 2.5 5 7.5 10 2.5 7.5 2.5 7.5 7.5 14 510 5 10 21 25 7.5/514/10 7.5/5 14/10 25 30 10 25 10 25 42 50 2.5 5 2.5 5 10 14 510 5 10 15 20 50 50 25 ○ ○ 12×In 12×In - - ○ - 15-32A: 20×In, 40-100A: 10×In - -(0.8-0.9-1)×In - 15-32A: 20×In, 40-100A: 10×In ○ ○ ○ ○1) ○1) ○1) ○1) ○1) ○1) ○1) ○1) ○1) - - ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○1) ○2) ○2) ○1) ○2) ○2) ○ ○ ○ ○1) ○2) ○2) ○ ○ ○ - - ○ ○1) ○1) ○1) ○ ○ ○ ○ ○ ○ ○3) ○3) ○3) 25,000 25,000 25,000 15,000 15,000 15,000 50/75 50/75/100 50/75/100 130 130 130 60 60 60 82 82 82 0.45/0.65 0.45/0.65/0.85 0.6/0.78/0.96 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) Available for 3P, 4P breaker 3) Supplied as standard component 16 MCCB | UAB type / 60-100AF | Model UAB60 UAB100 Figure Ampere frame size Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Rated current (A) Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Recognition code for order AC600/660V, 50-60Hz Rated AC480/500V, 50-60Hz short-circuit Ultimate AC440/460V, 50-60Hz breaking [Icu] AC380/415V, 50-60Hz capacity (kA r.m.s.) AC220/240V, 50-60Hz IEC 60947-2 DC250V K 60947-2 DC125V Service [Ics] % of [Icu] Hydraulic Fixed thermal, magnetic Fixed instantaneous INST Trip Fixed thermal, mechanism & Protection Thermal Fixed instantaneous INST magnetic Adjustable thermal, LTD characteristics Fixed instantaneous INST Direct mounting by screw for Both line & load side Switchboard Line side only Mounting Plug-in for Distribution board DIN-rail with DIN-rail adaptor Terminal connection Screw Auxiliary switch AUX Trip alarm switch ALT Signal Shunt trip SHT Under voltage trip UVT Operating Surface type TFG handle Extended type TFH MOT Accessories Operating Motor operator Mechanical interlock MIF Padlock plate PLD DIN-rail adaptor DRA Mounting Plug-in mounting base TDM Cage terminal block CTB Terminal Terminal cover TCF Interpole barrier TQQ Durability Mechanical operation (times) Electrical operation a Width d a c b Height Dimensions 2/3/4P b c Depth (mm) d Weight (kg, breaker only) 2/3/4P 60AF 100AF 2, 3, 4 2, 3, 4 2, 3, 4 IP20 IP20 IP20 A A A ○ ○ ○ overload, inst., short-circuit overload, inst., short-circuit overload, inst., short-circuit 5,10,15,20,30,40,50,60 5,10,15,20,30,40,50,60,75,100 15,16,20,25,30,32,40,50,60,63,75,80,100 AC690 AC690 AC690 AC660 AC660 AC660 - DC250 6 6 6 C R C R S 2.5 5 5 7.5 10 2.5 7.5 7.5 7.5 14 510 10 21 25 7.5/514/10 14/10 25 30 10 25 25 42 50 2.5 5 5 10 14 510 10 15 20 50 50 25 ○ ○ 12×In 12×In - - ○ - 15-32A: 20×In, 40-100A: 10×In - -(0.8-0.9-1)×In2) - 15-32A: 20×In, 40-100A: 10×In ○ ○ ○ ○ ○ ○ ○1) ○1) ○1) ○1) ○1) ○1) - - ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○2) ○2) ○2) ○2) ○2) ○2) ○ ○ ○ ○2) ○2) ○2) ○ ○ ○ - - ○ ○1) ○1) ○1) ○ ○ ○ ○ ○ ○ ○3) ○3) ○3) 25,000 25,000 25,000 10,000 10,000 10,000 50/75/100 50/75/100 50/75/100 130 130 130 60 60 60 82 82 82 0.45/0.65/0.85 0.45/0.65/0.85 0.6/0.78/0.96 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) Available for 3P, 4P breaker 3) Supplied as standard component Molded Case Circuit Breaker_ 17 U-Series / Molded Case Circuit Breaker Rating Overview | UCB type / 50-125AF | Model UCB50 UCB100 Figure Ampere frame size Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Rated current (A) Rating Rated insulation voltage [Ui] (V) Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Recognition code for order AC600/660V, 50-60Hz Rated AC480/500V, 50-60Hz short-circuit Ultimate AC440/460V, 50-60Hz breaking [Icu] AC380/415V, 50-60Hz capacity (kA r.m.s.) AC220/240V, 50-60Hz IEC 60947-2 DC250V K 60947-2 DC125V Service [Ics] % of [Icu] Fixed thermal, Trip Fixed instantaneous INST mechanism Thermal LTD & Protection magnetic Adjustable thermal, characteristics Fixed instantaneous INST Direct mounting by screw for Both line & load side Mounting Switchboard Line side only Plug-in for Distribution board Terminal connection Screw Auxiliary switch AUX Trip alarm switch ALT Signal Shunt trip SHT Under voltage trip UVT Operating Surface type TFG handle Extended type TFH Accessories Operating Motor operator MOT Mechanical interlock MIF Padlock plate PLD Mounting Plug-in mounting base TDM Cage terminal block CTB Terminal Terminal cover TCF Interpole barrier TQQ Durability Mechanical operation (times) Electrical operation a Width d a c b Height Dimensions 2/3/4P b c Depth (mm) d Weight (kg, breaker only) 2/3/4P 50AF100AF125AF 2, 3, 4 ✽2, 3, 4 2, 3, 4 ✽2, 3, 4 IP20 IP20 IP20 IP20 A A A A ○ ○ ○ ○ overload, inst., overload, inst., overload, inst., overload, inst., short-circuit short-circuit short-circuit short-circuit 15,16,20,25,30,32,40, 15,16,20,25,30,32,40, 15,20,30,40,50 15,16,20,25,30,32,40,50 50,60,63,75,80,100,125 50,60,63,75,80,100,125 AC690 AC690 AC690 AC690 AC660 AC660 AC660 AC660 DC250 DC250 DC250 DC250 6 6 6 6 R H L R S H L 10 20 25 10 18 20 25 14 30 35 14 25 30 35 25 42 50 25 35 42 50 30/25 42 50 30/2542/36 42 50 50 85 100 50 65 85 100 14 25 40 14 18 25 40 20 40 60 20 25 40 60 50 50 50 50 ○ ○ ○ ○ 15-32A: 15×In, 15-32A: 15×In, 10×In 10×In 40-50A: 10×In 40-125A: 10×In -(0.8-0.9-1)×In(0.8-0.9-1)×In (0.8-0.9-1)×In 15-32A: 15×In,15-32A: 15×In, 10×In 40-50A: 10×In 40-125A: 10×In ○ ○ ○ ○ ○1) ○1) ○1) ○1) ○1) ○1) ○1) ○1) 1) 1) 1) ○ ○ ○ ○1) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○2) ○ ○2) ○ ○2) ○ ○2) ○ ○ ○ ○ ○ ○ ○ ○2) ○ ○ ○ ○ ○ ○1) ○ ○1) ○1) ○ ○ ○ ○ ○ ○ ○ ○ ○3) ○3) ○3) ○3) 25,000 25,000 25,000 25,000 10,000 10,000 10,000 10,000 60/90/120 904)/90/120 60/90/120904)/90/120 155 155 155 155 60 60 60 60 84.5 84.5 84.5 84.5 0.7/1.0/1.2 0.9/1.0/1.3 0.7/1.0/1.2 0.9/1.0/1.3 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) Available for 3P, 4P breaker 3) Supplied as standard component 4) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. 18 MCCB | UCB type / 160-250AF | Model UCB160 UCB250 Figure Ampere frame size Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Rated current (A) Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Recognition code for order AC600/660V, 50-60Hz Rated AC480/500V, 50-60Hz short-circuit Ultimate AC440/460V, 50-60Hz breaking [Icu] AC380/415V, 50-60Hz capacity (kA r.m.s.) AC220/240V, 50-60Hz IEC 60947-2 DC250V K 60947-2 DC125V Service [Ics] % of [Icu] Fixed thermal, Trip mechanism Thermal Fixed instantaneous INST & Protection magnetic Adjustable thermal, LTD characteristics Fixed instantaneous INST Direct mounting by screw for Both line & load side Mounting Switchboard Line side only Plug-in for Distribution board Screw Terminal connection Bus bar Auxiliary switch AUX Trip alarm switch ALT Signal Shunt trip SHT Under voltage trip UVT Operating Surface type TFG handle Extended type TFH Accessories Operating Motor operator MOT Mechanical interlock MIF Padlock plate PLD Mounting Plug-in mounting base TDM Terminal bus bar TBB Cage terminal block CTB Terminal Terminal cover TCF Interpole barrier TQQ Durability Mechanical operation (times) Electrical operation a Width d a c b Height Dimensions 2/3/4P b (mm) c Depth d Weight (kg, breaker only) 2/3/4P 160AF 250AF ✽2, 3, 4 ✽2, 3, 4 ✽2, 3, 4 IP20 IP20 IP20 A A A ○ ○ ○ overload, inst., short-circuit overload, inst., short-circuit overload, inst., short-circuit 100,125,160 100,125,150,160,175,200,225,250 125,150,160,175,200,225,250 AC690 AC690 AC690 AC660 AC660 AC660 DC250 DC250 DC250 6 6 6 H L R S N H L 20 25 7.5 10 18 20 25 30 35 10 14 25 30 35 42 50 18 25 35 42 50 42 50 25/18 35/25 42/36 42 50 85 100 35 50 65 85 100 25 40 10 14 18 25 40 40 60 15 20 25 40 60 50 50 50 ○ ○ ○ 10×In 10×In10×In (0.8-0.9-1)×In(0.8-0.9-1)×In(0.8-0.9-1)×In 10×In 10×In10×In ○ ○ ○ ○1) ○1) ○1) ○1) ○1) ○1) ○1) ○1) ○1) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○1) ○1) ○1) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○2) ○2) ○2) 25,000 25,000 25,000 10,000 10,000 10,000 1053)/105/140 1053)/105/1401053)/105/140 165 164 165 60 60 60 84.5 84 84.5 1.1/1.3/1.6 1.1/1.2/1.5 1.1/1.3/1.6 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) Supplied as standard component 3) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. Molded Case Circuit Breaker_ 19 U-Series / Molded Case Circuit Breaker Rating Overview | UCB type / 400-800AF | Model UCB400 UCB630 UCB800 Figure Ampere frame size Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Rated current (A) Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Recognition code for order AC600/660V, 50-60Hz Rated AC480/500V, 50-60Hz short-circuit Ultimate AC440/460V, 50-60Hz breaking [Icu] capacity (kA r.m.s.) AC380/415V, 50-60Hz AC220/240V, 50-60Hz IEC 60947-2 DC250V K 60947-2 DC125V Service [Ics] % of [Icu] Fixed thermal, Trip mechanism Thermal Fixed instantaneous INST & Protection magnetic Adjustable thermal, LTD characteristics Fixed instantaneous INST Direct mounting by screw Mounting Both line & load side for Plug-in Switchboard Line side only Screw Terminal connection Bus bar Auxiliary switch AUX Trip alarm switch ALT Signal Shunt trip SHT Under voltage trip UVT Operating Surface type TFG handle Extended type TFH Motor operator MOT Accessories Operating Mechanical interlock MIF Padlock plate PLD Extension handle THA Mounting Plug-in mounting base TDM Terminal bus bar TBB Cage terminal block CTB Terminal Terminal cover TCF Interpole barrier TQQ Durability Mechanical operation (times) Electrical operation d a Width a c b Height Dimensions b 2/3/4P (mm) c Depth d Weight (kg, breaker only) 2/3/4P 400AF 630AF 800AF ✽2, 3, 4✽2, 3, 4✽2, 3, 4 IP20IP20 IP20 A A A ○ ○ ○ overload, inst., short-circuit overload, inst., short-circuit overload, inst., short-circuit 250,300,320,350,400500, 630700, 800 AC690AC690 AC690 AC660AC660 AC660 DC250DC250 DC250 6 6 6 R S H L R S H L R S H L 18 22 25 30 22 25 35 35 25 25 35 35 18 25 35 65 25 45 50 65 35 45 50 65 25 35 50 85 35 50 65 85 35 50 65 85 30 4265 100 45 6585 100 45 6585 100 35 50 85 125 50 100 100 125 50 100 100 125 14 25 40 40 20 40 40 40 20 40 40 40 20 30 50 60 30 50 50 60 30 50 50 60 5050 50 ○ ○ ○ 10×In10×In 10×In (0.8-0.9-1)×In (0.8-0.9-1)×In (0.8-0.9-1)×In 10×In10×In 10×In ○ ○ ○ ○1) ○1) ○1) ○1) ○1) ○1) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○2) ○2) ○2) 1) 1) ○ ○ ○1) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○2) ○2) ○2) 20,00020,000 10,000 6,0006,000 3,000 1403)/140/185 2103)/210/280 2103)/210/280 257280 280 110110 110 145145 145 4/4.5/5.4 8.7/9.5/12.5 8.7/9.5/12.5 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) Supplied as standard component 3) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. 20 MCCB | UCB type / 1000-1600AF | Model UCB1000 UCB1250 UCB1600 Figure Ampere frame size 1000AF1250AF Number of poles (P) Degree of protection (without terminal bus bar) IP20IP20 Utilization category A A A Suitability of isolation ○○ ○ Protection overload, inst., short-circuit Rating 3, 4 3, 4 overload, inst., short-circuit 1600AF 3 IP20 overload, inst., short-circuit Rated current (A) 505-1,000630-1,250 Rated insulation voltage [Ui] (V) AC750AC750 AC750 Rated operational voltage [Ue] (V) AC690AC690 AC690 Rated impulse withstand voltage [Uimp] (kV) 8 8 Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) IEC 60947-2 K 60947-2 Service [Ics] 640-1,600 8 Recognition code for order S L S L S AC600/660V, 50-60Hz 40 60 40 60 25 AC480/500V, 50-60Hz 75 100 75 100 35 AC440/460V, 50-60Hz 75 100 75 100 45 AC380/415V, 50-60Hz 100130 100130 65 100 150 100 150 100 AC220/240V, 50-60Hz % of [Icu] 5050 Long time delay LTD Short time delay Trip Instantaneous mechanism Electronic Ground fault trip & Protection Pre-trip alarm characteristics I2T lamp STD INST (0.5-1)1)×In (15 setting) (0.5-1)1)×In (15 setting) (2-4-6-8-10)×Ir(2-4-6-8-10)×Ir (3-6-8-10-11)×In 50 (0.4-1)2)×In (8 setting) - (3-6-8-10-11)×In(2-3-4-5-6-7-8-10)×In GFT (0.2-0.3-0.4)×In(0.2-0.3-0.4)×In - PTA 0.9×Ir0.9×Ir - ○ ○ - Pick-up LED Mounting Direct mounting by screw ○○ ○○ ○ Terminal connection ○○ ○ ○ Signal Bus bar ○ Auxiliary switch AUX ○○ Trip alarm switch ALT ○○ - Shunt trip SHT ○○ ○ Under voltage trip ○○ ○ -- ○ - UVT Operating Extended type TFH handle Accessories Operating Motor operator MOT ○○ Padlock plate PLD ○○ - Extension handle THA ○3) ○3) ○3) Terminal bus bar TBB ○4) ○4) ○4) TCF -- ○3) ○ ○ ○3) Terminal Terminal cover Interpole barrier TQQ Durability Mechanical operation (times) Electrical operation 3) 3) 10,00010,000 10,000 3,0003,000 3,000 d a a Width 210/280 210/280 210/280 210/280 210 Dimensions 3/4P b (mm) b Height 370 370 370 370 371 c Depth 110 200 110 200 151 d 159 249 159 249 215 Weight (kg, breaker only) 3/4P 13/17 25/33 13.5/17.525.5/33.5 27 c ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1) 2) (0.4-1): (0.4-0.5-0.6-0.7-0.8-0.9-0.95-1) 3) Supplied as standard component 4) Supplied as standard component that attached in breaker Molded Case Circuit Breaker_ 21 U-Series / Molded Case Circuit Breaker Rating Overview | UPB type / 125-250AF | Model UPB100 UPB160 UPB250 Figure Ampere frame size Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Thermal magnetic type Rated current (A) Electronic type Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Recognition code for order AC660/690V, 50-60Hz Rated AC480/500V, 50-60Hz short-circuit Ultimate AC440/460V, 50-60Hz breaking [Icu] AC380/415V, 50-60Hz capacity (kA r.m.s.) AC220/240V, 50-60Hz IEC 60947-2 DC250V K 60947-2 DC125V Service [Ics] % of [Icu] Fixed thermal, Fixed instantaneous Thermal Trip Adjustable thermal, Fixed inst. magnetic mechanism Adjustable thermal, Adjustable inst. & Protection characteristics Electronic LTD, STD, INST PTA, Pick-up LED Direct mounting by screw Mounting Both line & load side for Plug-in Switchboard Line side only Screw Terminal connection Bus bar Auxiliary switch AUX Trip alarm switch ALT Signal Shunt trip SHT Under voltage trip UVT Operating Surface type TFG handle Extended type TFH Operating Motor operator MOT Accessories Mechanical interlock MIF Padlock plate PLD Mounting Plug-in mounting base TDM Terminal bus bar TBB Cage terminal block CTB Terminal Terminal cover TCF Interpole barrier TQQ Durability Mechanical operation (times) Electrical operation a Width d a c b Height Dimensions 3/4P b (mm) c Depth d Weight (kg, breaker only) 3/4P 125AF160AF 3, 4 3, 4 IP20IP20 A A ○○ overload, inst., short-circuit overload, inst., short-circuit 15,16,20,25,30,32,40,50,60,63,75,80,100,125100,125,160 50-12563-160 AC750AC750 AC690AC690 DC5001) DC5001) 8 8 S H L X S H L X 10 10 25 25 10 10 25 25 50 65 85 85 50 65 85 85 65 85 100 150 65 85 100 150 85 100130 150 85 100130 150 100 130 150 200 100 130 150 200 501) 651) 851) 1001) 501) 651) 851) 1001) 651) 1001) 1001) 1001) 651) 1001) 1001) 1001) 100 100 ○2) ○2) ○2) ○2) -○2) ○2) ○2) ○○ ○ ○ ○3) ○3) ○3) ○3) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○3) ○3) ○ ○ ○ ○ ○ ○ ○4) ○4) 25,00025,000 10,00010,000 105/140105/140 165165 86.586.5 112112 1.8/2.22.0/2.4 250AF 3, 4 IP20 A ○ overload, inst., short-circuit 125,150,160,175,200,225,250 100-250 AC750 AC690 DC5001) 8 S H L X 10 10 25 25 50 65 85 85 65 85 100 150 85 100130 150 100 130 150 200 501) 651) 851) 1001) 651) 1001) 1001) 1001) 100 ○2) ○2) ○2) ○2) ○ ○ ○3) ○3) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○3) ○ ○ ○ ○4) 25,000 10,000 105/140 165 86.5 112 2.0/2.4 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) DC is not applicable for electronic breaker. 2) For the detail protection characteristics, please refer to following pages; ·UPB100: page 90 ·UPB160: page 96 ·UPB250: page 100 3) Available for 3P breaker 4) Supplied as standard component 22 MCCB | UPB type / 400-630AF | Model UPB400 UPB630 Figure Ampere frame size Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Rated current (A) Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Recognition code for order Rated AC660/690V, 50-60Hz short-circuit Ultimate AC480/500V, 50-60Hz breaking [Icu] AC440/460V, 50-60Hz capacity (kA r.m.s.) AC380/415V, 50-60Hz IEC 60947-2 AC220/240V, 50-60Hz K 60947-2 Service [Ics] % of [Icu] LTD, STD, INST Trip mechanism Electronic GFT, I2T lamp & Protection PTA, Pick-up LED characteristics Direct mounting by screw Both line & load side Mounting for Plug-in Switchboard Line side only Screw Terminal connection Bus bar Auxiliary switch AUX Trip alarm switch ALT Signal Shunt trip SHT Under voltage trip UVT Operating Surface type TFG handle Extended type TFH Motor operator MOT Operating Mechanical interlock MIF Accessories Padlock plate PLD Extension handle THA Mounting Plug-in mounting base TDM Terminal bus bar TBB Cage terminal block CTB Terminal Terminal cover TCF Interpole barrier TQQ Durability Mechanical operation (times) Electrical operation a Width d a c b Height Dimensions 3/4P b (mm) c Depth d Weight (kg, breaker only) 3/4P 400AF 630AF 3, 4 3, 4 IP20 IP20 A A ○ ○ overload, inst., short-circuit overload, inst., short-circuit 200-400 320-630 AC750 AC750 AC690 AC690 8 8 S H L X S H L X 10 10 25 25 10 10 25 25 50 65 85 85 50 65 85 85 65 85100 150 65 85 100 150 85 100130 150 85 100 130 150 100 130 150 200 100 130 150 200 100 100 ○1) ○1) ○1) ○1) ○ ○ ○ ○ ○2) ○2) ○2) ○2) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○3) ○3) ○2) ○2) ○ ○ ○ ○ ○ ○ ○3) ○3) 20,000 20,000 6,000 6,000 140/185 140/185 255 255 117 117 159.5 159.5 6.0/7.8 6.0/7.8 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) For the detail protection characteristics, please refer to following pages; ·UPB400: page 106 ·UPB630: page 108 2) Available for 3P breaker 3) Supplied as standard component Molded Case Circuit Breaker_ 23 U-Series / Molded Case Circuit Breaker Rating Overview | Motor protection / UPB type 125-250AF | Model UPB100 UPB250 Figure Ampere frame size Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Rated current (A) Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Recognition code for order AC660/690V, 50-60Hz Rated short-circuit Ultimate AC480/500V, 50-60Hz AC440/460V, 50-60Hz breaking [Icu] AC380/415V, 50-60Hz capacity (kA r.m.s.) AC220/240V, 50-60Hz IEC 60947-2 DC250V K 60947-2 DC125V Service [Ics] % of [Icu] Trip mechanism Thermal Adjustable instantaneous & Protection magnetic characteristics Direct mounting by screw Both line & load side for Mounting Plug-in Switchboard Line side only Screw Terminal connection Bus bar Auxiliary switch AUX Trip alarm switch ALT Signal Shunt trip SHT Under voltage trip UVT Operating Surface type TFG Extended type TFH handle Operating Motor operator MOT Accessories Mechanical interlock MIF Padlock plate PLD Mounting Plug-in mounting base TDM Terminal bus bar TBB Cage terminal block CTB Terminal Terminal cover TCF Interpole barrier TQQ Mechanical operation Durability (times) Electrical operation Width a d a c b Height Dimensions 3P b c Depth (mm) d Weight (kg, breaker only) 3P 125AF 250AF 3 3 IP20 IP20 A A ○ ○ instantaneous, short-circuitinstantaneous, short-circuit 2.5,3.2,6.3,12.5,20,32,50,63,80,100 125,150,175,200,225 AC750 AC750 AC690 AC690 DC500 DC500 8 8 H L H L 10 25 10 25 65 85 65 85 85100 85 100 100130 100 130 130 150 130 150 65 85 65 85 100 100 100 100 100 100 (6-7-8-9-10-11-12-13)×In(5-6-7-8-9-10)×In ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○1) ○1) 25,000 25,000 10,000 10,000 105 105 165 165 86.5 86.5 112 112 1.8 2.0 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Supplied as standard component 24 MCCB | Q-class (for nuclear power plant application) / HBL type 100-225AF | HBL103 Model HBL203 Figure Ampere frame size Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Rated current (A) Rating Rated insulation voltage [Ui] (V) Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Recognition code for order AC660/690V, 50-60Hz Rated AC480/500V, 50-60Hz short-circuit Ultimate AC440/460V, 50-60Hz breaking [Icu] AC380/415V, 50-60Hz capacity (kA r.m.s.) AC220/240V, 50-60Hz DC250V IEC 60947-2 DC125V K 60947-2 Service [Ics] % of [Icu] Trip mechanism Thermal Fixed thermal, Fixed instantaneous INST & Protection characteristics magnetic Adjustable instantaneous Non-E1 Q-class E1 Mounting Direct mounting by screw Screw Terminal connection Bus bar Auxiliary switch AUX Trip alarm switch ALT Signal Shunt trip SHT Under voltage trip UVT Operating Surface type TFG handle Operating Motor operator MOT Accessories Mechanical interlock MIF Padlock plate PLD Mounting Plug-in mounting base TDM Terminal bus bar TBB Cage terminal block CTB Terminal Terminal cover TCF Interpole barrier TQQ Durability Mechanical operation (times) Electrical operation a Width d a c b Height Dimensions b 3P c Depth (mm) d Weight (kg, breaker only) 3P 100AF 225AF 3 3 IP20 IP20 A A ○ ○ overload, inst., short-circuit instantaneous, short-circuit overload, inst., short-circuit instantaneous, short-circuit 15,20,30,40, 2.5,3.2,6.3,12.5, 125,150,175,200,225 50,60,75,100 20,32,50,63,80,100 AC750 AC750 AC690 AC690 DC500 DC500 8 8 UQ1) UM1) UMQ1) U1) UQ1) UM1) UMQ1) U1) 25 25 25 25 25 25 25 25 85 8585 85 85 85 85 85 100 100 100 100 100 100 100 100 150 150 150 150 150 150 150 150 200 200 200 200 200 200 200 200 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 ○ -○ - 10×In -10×In - (6-7-8-9-10-11-12-13)×In(5-6-7-8-9-10)×In ○ - ○ ○ - ○ - ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○2) ○2) ○2) ○2) ○2) ○2) ○2) ○2) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○3) ○3) ○3) ○3) 25,000 25,000 10,000 10,000 105 105 165 165 86.5 86.5 112 112 1.8 2.0 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) ·U: non-E1 class ·UQ: E1 class ·UM: non-E1 class, motor protection ·UMQ: E1 class, motor protection 2) Signal accessories shall be installed in breaker before ex-working. 3) Supplied as standard component Molded Case Circuit Breaker_ 25 U-Series / Molded Case Circuit Breaker Rating Overview | Switch disconnector / UAD type 50-100AF | Model UAD50C UAD50S UAD100R Figure Ampere frame size 50AF Number of poles (P) Degree of protection (with terminal cover) 3 3 IP20 IP20 IP20 Utilization category A A A Suitability of isolation ○ ○ ○ 50 50 100 Conventional thermal current [Ith] (A) Rated current (A) Rated insulation voltage [Ui] (V) 50 50 100 AC690 AC690 AC690 AC660 AC660 AC660 DC250 DC250 DC250 Rated impulse withstand voltage [Uimp] (kV) 6 6 6 Rated short-circuit making capacity [Icm] (kA peak at AC460V) 17 52.5 52.5 Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.) 1 1 1 Mechanical operation (times) 25,000 25,000 25,000 Electrical operation (times) 15,000 15,000 10,000 ○ ○ ○ for Both line & load side Mounting Plug-in Switchboard Line side only ○ ○ ○ ○ ○ ○ ○ ○ ○ Rating Durability Rated operational voltage [Ue] (V) Direct mounting by screw for Distribution board DIN-rail Terminal connection Signal with DIN-rail adaptor - ○ ○ Screw ○ ○ ○ Auxiliary switch AUX ○ ○ ○ Trip alarm switch ALT ○ ○ ○ Shunt trip SHT ○ ○ ○ UVT ○ ○ ○ Operating Surface type handle Extended type Under voltage trip TFG ○ ○ ○ TFH ○ ○ ○ Accessories Operating Motor operator MOT ○ ○ ○ Mechanical interlock MIF ○ ○ ○ Padlock plate PLD ○ ○ ○ DIN-rail adaptor Mounting Plug-in mounting base DRA - ○ ○ TDM ○ ○ ○ Terminal cover Terminal Interpole barrier TCF ○ ○ ○ TQQ ○1) ○1) ○1) a Width 75 75 75 b Dimensions 3P b (mm) c Height 130 130 130 Depth 60 60 60 d 82 82 82 Weight (kg, breaker only) 3P 0.65 0.78 0.78 a d c ※ 1) Supplied as standard component 26 100AF 3 MCCB | Switch disconnector / UCD type 50-250AF | Model UCD50H UCD100S UCD100H UCD160H UCD250S UCD250H Ampere frame size 50AF 100AF 125AF 160AF Number of poles (P) 3 3 3 3 3 3 IP20 IP20 IP20 IP20 IP20 IP20 Figure Degree of protection (with terminal cover) 250AF Utilization category A A A A A A Suitability of isolation ○ ○ ○ ○ ○ ○ 50 100 125 160 250 250 Conventional thermal current [Ith] (A) Rated current (A) Rated insulation voltage [Ui] (V) 50 100 125 160 250 250 AC690 AC690 AC690 AC690 AC690 AC690 AC660 AC660 AC660 AC660 AC660 AC660 DC250 DC250 DC250 DC250 DC250 DC250 6 6 6 6 6 6 Rated short-circuit making capacity [Icm] (kA peak at AC460V) 105 73.5 105 105 73.5 105 Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.) 1 1 1 2 2 2 Mechanical operation (times) 25,000 25,000 25,000 25,000 25,000 25,000 Electrical operation (times) 10,000 10,000 10,000 10,000 10,000 10,000 ○ ○ ○ ○ ○ ○ for Both line & load side Mounting Plug-in Switchboard Line side only ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ for Distribution board ○ ○ ○ ○ ○ ○ Screw ○ ○ ○ ○ ○ ○ Bus bar - - - ○ ○ ○ Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Durability Direct mounting by screw Terminal connection Signal Auxiliary switch AUX ○ ○ ○ ○ ○ ○ Trip alarm switch ALT ○ ○ ○ ○ ○ ○ Shunt trip SHT ○ ○ ○ ○ ○ ○ UVT ○ ○ ○ ○ ○ ○ Operating Surface type handle Extended type Under voltage trip TFG ○ ○ ○ ○ ○ ○ TFH ○ ○ ○ ○ ○ ○ Accessories Operating Motor operator MOT ○ ○ ○ ○ ○ ○ Mechanical interlock MIF ○ ○ ○ ○ ○ ○ Padlock plate PLD ○ ○ ○ ○ ○ ○ TDM - ○ ○ ○ ○ ○ CTB ○ ○ ○ ○ ○ ○ Mounting Plug-in mounting base Cage terminal block Terminal Terminal cover TCF ○ ○ ○ ○ ○ ○ TQQ ○1) ○1) ○1) ○1) ○1) ○1) a Width 90 90 90 105 105 105 b Dimensions 3P b (mm) c Height 155 155 155 165 164 165 Depth 60 60 60 60 60 60 d 84.5 84.5 84.5 84.5 84 84.5 Weight (kg, breaker only) 3P 1 1 1 1.3 1.2 1.3 Interpole barrier d a c ※ 1) Supplied as standard component Molded Case Circuit Breaker_ 27 U-Series / Molded Case Circuit Breaker Rating Overview | Switch disconnector / UCD type 400-1250AF | Model UCD400S UCD630S UCD800S UCD1000S UCD1250S Ampere frame size 400AF 630AF 800AF 1000AF 1250AF Number of poles (P) 3 3 3 3 3 IP20 IP20 IP20 IP201) IP201) Figure Degree of protection (with terminal cover) Utilization category A A A A A Suitability of isolation ○ ○ ○ ○ ○ 400 630 800 1,000 1,250 Conventional thermal current [Ith] (A) Rated current (A) Rated insulation voltage [Ui] (V) 630 800 1,000 1,250 AC690 AC690 AC750 AC750 AC660 AC660 AC660 AC690 AC690 DC250 DC250 DC250 - - 6 6 6 8 8 Rated short-circuit making capacity [Icm] (kA peak at AC460V) 187 187 187 165 165 Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.) 4 6.3 8 10 12.5 Mechanical operation (times) 20,000 20,000 10,000 10,000 10,000 Electrical operation (times) 6,000 6,000 3,000 3,000 3,000 ○ ○ ○ - - Both line & load side Mounting for Plug-in Switchboard Line side only ○ ○ ○ - - ○ ○ ○ - - Screw ○ ○ ○ - - Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Durability Direct mounting by screw Terminal connection Signal Bus bar ○ ○ ○ ○ ○ Auxiliary switch AUX ○ ○ ○ ○ ○ Trip alarm switch ALT ○ ○ ○ ○ ○ Shunt trip SHT ○ ○ ○ ○ ○ Under voltage trip UVT ○ ○ ○ ○ ○ TFG ○ ○ ○ - - TFH ○ ○ ○ - - MOT ○ ○ ○ ○ ○ Operating Surface type handle Extended type Motor operator Accessories Operating Mechanical interlock MIF ○ ○ ○ - - Padlock plate PLD ○ ○ ○ ○ ○ Extension handle THA ○2) ○2) ○2) ○2) ○2) TDM ○ ○ ○ - - TBB ○ ○ ○ ○3) ○3) Cage terminal block Terminal Terminal cover CTB ○ ○ ○ - - TCF ○ ○ ○ - - TQQ ○2) ○2) ○2) ○2) ○2) a Width 140 210 210 210 210 b Dimensions 3P b (mm) c Height 257 280 280 370 370 Depth 110 110 110 110 110 d 145 145 145 159 159 Weight (kg, breaker only) 3P 4.5 9.5 9.5 13 13.5 Mounting Plug-in mounting base Terminal bus bar Interpole barrier a d c ※ 1) Without terminal bus bar 2) Supplied as standard component 3) Supplied as standard component that attached in breaker 28 400 AC690 MCCB | Switch disconnector / UPD type 125-630AF | Model UPD100S UPD160S UPD250S UPD400S UPD630S Ampere frame size 125AF 160AF 250AF 400AF 630AF Number of poles (P) 3 3 3 3 3 IP20 IP20 IP20 IP20 IP20 Figure Degree of protection (with terminal cover) Utilization category A A A A A Suitability of isolation ○ ○ ○ ○ ○ 125 160 250 400 630 Conventional thermal current [Ith] (A) Rated current (A) Rated insulation voltage [Ui] (V) 125 160 250 400 630 AC750 AC750 AC750 AC750 AC750 AC690 AC690 AC690 AC690 AC690 DC500 DC500 DC500 - - 8 8 8 8 8 Rated short-circuit making capacity [Icm] (kA peak at AC460V) 200 200 200 200 200 Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.) 1 1.6 2.5 4 6.3 Mechanical operation (times) 25,000 25,000 25,000 20,000 20,000 Electrical operation (times) 10,000 10,000 10,000 6,000 6,000 ○ ○ ○ ○ ○ Both line & load side Mounting for Plug-in Switchboard Line side only ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ Screw ○ ○ ○ ○ ○ Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Durability Direct mounting by screw Terminal connection Signal Bus bar ○ ○ ○ ○ ○ Auxiliary switch AUX ○ ○ ○ ○ ○ Trip alarm switch ALT ○ ○ ○ ○ ○ Shunt trip SHT ○ ○ ○ ○ ○ Under voltage trip UVT ○ ○ ○ ○ ○ TFG ○ ○ ○ ○ ○ TFH ○ ○ ○ ○ ○ MOT ○ ○ ○ ○ ○ ○ Operating Surface type handle Extended type Motor operator Operating Mechanical interlock Accessories MIF ○ ○ ○ ○ Padlock plate PLD ○ ○ ○ - - Extension handle THA - - - ○1) ○1) Mounting Plug-in mounting base TDM ○ ○ ○ ○ ○ Terminal bus bar TBB ○ ○ ○ ○ ○ Cage terminal block CTB ○ ○ ○ ○ ○ TCF ○ ○ ○ ○ ○ TQQ ○1) ○1) ○1) ○1) ○1) a Width 105 105 105 140 140 b Dimensions 3P b (mm) c Height 165 165 165 255 255 Depth 86.5 86.5 86.5 117 117 d 112 112 112 159.5 159.5 Weight (kg, breaker only) 3P 1.8 2 2 6 6 Terminal Terminal cover Interpole barrier a d c ※ 1) Supplied as standard component Molded Case Circuit Breaker_ 29 U-Series / Molded Case Circuit Breaker Rating Overview | Miniature type / Molded case circuit breaker 30-100AF | Model UMB30 UMB50 UDB30 UDB50 UDB100 Ampere frame size 30AF 50AF 30AF 50AF 100AF Number of poles (P) 2 2 2, 3 2, 3 ✽2,3 Degree of protection IP20 IP20 IP20 IP20 IP20 Utilization category A A A A A overload, short-circuit overload, short-circuit overload, short-circuit overload, short-circuit overload, short-circuit 15, 20, 30 15, 20, 30, 40, 50 31), 5, 10, 15, 20, 30 5, 10, 15, 20, 30, 40, 50 15, 20, 30, 40, 50, 60, 75, 100 Rated insulation voltage [Ui] (V) AC250 AC250 AC460 AC460 AC460 Rated operational voltage [Ue] (V) AC220 AC220 2P: AC220 3P: AC220/460 2P: AC220 3P: AC220/460 2P: AC220 3P: AC220/460 6 6 6 6 6 Figure Protection Rated current (A) Rating Rated impulse withstand voltage [Uimp] (kV) Recognition code for order Ra Rb Sg Hg AC440/460V, 50-60Hz Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) AC380/415V, 50-60Hz IEC 60947-2 K 60947-2 AC220/240V, 50-60Hz Mounting Terminal connection Signal Dimensions (mm) b H S H 2.5 5-10A: 2.53) 2.5 15-30A: 5 5-10A: 2.53) 15-30A: 5 2.5 5 - - 2.5 5-10A: 2.53) 5-10A: 2.53) 2.55 15-30A: 5 15-30A: 5 2.5 5 5 10 5 10 5 10 50 5 5-10A: 53) 15-30A: 10 5 5-10A: 53) 15-30A: 10 50 50 50 - - - ○ - ○ ○ ○ ○ ○ ○ ○ - ○ - - - - - ○ ○ ○ DIN-rail ○ ○ ○ ○ ○ Screw ○ ○ ○ ○ ○ AUX - - ○ ○ ○ Trip alarm switch ALT - - ○ ○ ○ Shunt trip SHT - - ○ ○ ○ TQQ - - ○ ○ ○ d c 2/3P a Width 33 35 35 50/75 50/75 752)/75 b Height 70 80 80 96 96 96 c Depth 42 60 60 60 60 60 60 57 75 76 76 80 80 80 0.1 0.12 0.13 0.15 0.2/0.35 0.2/0.35 0.2/0.35 d Weight (kg, breaker only) 2/3P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) 3A is not applicable for UDB30H. 2) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. 3) It is breaking capacity under 10A. 30 S - Terminal Interpole barrier a H Direct mounting by screw Auxiliary switch Accessories S - 50 Hydraulic magnetic Trip mechanism Thermal magnetic Hg - 2.5 Service [Ics] % of [Icu] Sg MCCB | Miniature type / Earth leakage circuit breaker 30-100AF | Model UMG30 UMG50 UDG30 UDG50 UDG100 Ampere frame size 30AF 50AF 30AF 50AF 100AF Number of poles (P) 2 2 2, 3 2, 3 ✽2,3 Degree of protection IP20 IP20 IP20 IP20 IP20 Figure Utilization category A A A A A earth leakage, overload, short-circuit earth leakage, overload, short-circuit earth leakage, overload, short-circuit earth leakage, overload, short-circuit earth leakage, overload, short-circuit 15, 20, 30 15, 20, 30, 40, 50 31), 5, 10, 15, 20, 30 5, 10, 15, 20, 30, 40, 50 15, 20, 30, 40, 50, 60, 75, 100 Rated residual current [I△n] (mA) 15, 30 15, 30 15, 30 15, 30 30, 100 Rated insulation voltage [Ui] (V) AC250 AC250 AC460 AC460 AC460 AC220 AC220 2P: AC220 3P: AC220/460 2P: AC220 3P: AC220/460 2P: AC220 3P: AC220/460 6 6 6 6 6 0.03 0.03 0.03 0.03 0.03 Protection Rated current (A) Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Rated operating time (sec.) Recognition code for order Ca(Cb) Ra(Rb) Co(Rd) Sg(Hg) Rated AC440/460V, 50-60Hz short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) AC380/415V, 50-60Hz IEC 60947-2 K 60947-2 AC220/240V, 50-60Hz 1.5 Earth leakage detection Earth leakage protection Dimensions (mm) b H H 2.5 5 - - - - 2.5 5-10A: 2.5 15-30A: 5 2.5 5-10A: 2.5 15-30A: 5 2.5 5 5 5-10A: 5 15-30A: 10 5 5-10A: 5 15-30A: 10 5 10 5 10 50 by current transformer by current transformer by current transformer by current transformer by current transformer ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ - - ○ Direct mounting by screw - DIN-rail ○ -(○) - ○(-) ○ ○ - - ○ ○ - - - - ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ AUX - - ○ ○ ○ Trip alarm switch ALT - - ○ ○ ○ - - ○ ○ ○ Screw Auxiliary switch Terminal Interpole barrier a S 5-10A: 2.5 2.5 15-30A: 5 50 Trip mechanism Thermal magnetic Signal S 50 Hydraulic magnetic Accessories H 50 Earth leakage indicator Terminal connection S 50 Earth leakage test button Mounting Hg 5-10A: 2.5 2.5 15-30A: 5 2.5 1.5(2.5) 5(10) Service [Ics] % of [Icu] Sg d c 2/3P a Width 33 33 62 35 35 50/75 50/75 752)/75 b Height 70 70 82 80 80 96 96 96 c Depth 42(60) 42(60) 42 60 60 60 60 60 57(76) 57(76) 58 76 76 80 80 80 0.13/0.15 0.33/0.44 0.33/0.44 0.46/0.63 d Weight (kg, breaker only) 2/3P TQQ 0.1(0.12) 0.1(0.12) 0.21 0.13(0.15) ※ - KS certified products. English nameplate and 50Hz marking are not available. - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) 3A is not applicable for UDG30H. 2) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. Molded Case Circuit Breaker_ 31 Specifications and Standard Order Codes + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UAB type / 30AF | •UAB30C 7.5/5kA •UAB30R 14/10kA UAB30C UAB30R Number of poles (P) 2, 3 Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection overload, inst., short-circuit Rated current (A) 3,5,10,15,20,30 5,10,15,20,30 Rated insulation voltage [Ui] (V) AC690 Rating Rated operational voltage [Ue] (V) AC660 Rated impulse withstand voltage [Uimp] (kV) 6 AC600/660V, 50-60Hz 2.5 5 Rated short-circuit Ultimate AC480/500V, 50-60Hz 2.5 7.5 breaking [Icu] AC440/460V, 50-60Hz 5 10 capacity (kA r.m.s.) AC380/415V, 50-60Hz 7.5/514/10 AC220/240V, 50-60Hz IEC 60947-2 10 25 K 60947-2 Service [Ics] % of [Icu] 50 Trip mechanism Hydraulic ○ Fixed thermal, & Protection magnetic Fixed instantaneous INST characteristics 12×In Direct mounting by screw ○ Both line & load side ○1) for Mounting Switchboard Line side only Plug-in ○1) for Distribution board ○1) Terminal connection Screw ○ Mechanical operation 25,000 Durability (times) Electrical operation 15,000 a Width 50/75 d a c b Height 130 Dimensions 2/3P b (mm) c Depth 60 d 82 Weight (kg, breaker only) 2/3P 0.45/0.65 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip1) Under voltage trip2) 1C, right-hand-side 2C, right-hand-side AUX 10A R1 AUX 10A R2 1C, right-hand-side ALT 10A R1 DC24V DC100-110V SHT 10A A SHT 10A C DC24V DC100-110V ✽UVT 10A J ✽UVT 10A L AC100-120V AC200-230V SHT 10A F AC100-120V AC200-230V ✽UVT 10A N ✽UVT 10A P ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. 34 AC380-415V SHT 10A H AC380-415V ✽UVT 10A Q AC440-480V AC440-480V ✽UVT 10A R MCCB •Operating Power supply direction S type Operating Surface L type 1) handle S type Extended L type Motor operator2) Mechanical interlock Padlock plate3) Upper Right Left TFG 10AS U4 TFG 10AS R4 TFG 10AS L4 TFG 10AL U4 TFG 10AL L4 TFH 10AS TFH 10AL DC24V AC/DC110V AC/DC220V MOT 10A DC24 MOT 10A ADC110 MOT 10A ADC220 2 pole 3 pole - MIF 10A 3 PLD 10UA ※ 1) Available for 3P breaker. For detail type information, please refer to page 195-203. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting Plug-in1) Structure Mounting base Connection 2C contact block 2) 3C contact Conn. block barrier For both line & load side TDM 10AP CBM 10AB 2 CBM 10AB 3 CBM BARR For line side only TDM 10AF - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. •Terminal Cage terminal block Terminal cover1) Interpole barrier 2) 2EA/SET 3EA/SET CTB 10A 3S50 2 pole 3 pole TCF 10AP 2 TCF 10AP 3 TQQ 10A 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Hydraulic magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V 표준품 주문코드 Rated current Code Unit (EA) 3A UAB30C 2PT4S0000C 00003 30 UAB30C 3PT4S0000C 00003 20 5A UAB30C 2PT4S0000C 00005 30 UAB30C 3PT4S0000C 00005 20 UAB30C 10A UAB30C 2PT4S0000C 00010 30 UAB30C 3PT4S0000C 00010 20 7.5/5kA 15A UAB30C 2PT4S0000C 00015 30 UAB30C 3PT4S0000C 00015 20 20A UAB30C 2PT4S0000C 00020 30 UAB30C 3PT4S0000C 00020 20 30A UAB30C 2PT4S0000C 00030 30 UAB30C 3PT4S0000C 00030 20 5A UAB30R 2PT4S0000C 00005 30 UAB30R 3PT4S0000C 00005 20 UAB30R 10A UAB30R 2PT4S0000C 00010 30 UAB30R 3PT4S0000C 00010 20 15A UAB30R 2PT4S0000C 00015 30 UAB30R 3PT4S0000C 00015 20 20A UAB30R 2PT4S0000C 00020 30 UAB30R 3PT4S0000C 00020 20 30A UAB30R 2PT4S0000C 00030 30 UAB30R 3PT4S0000C 00030 20 14/10kA 2 pole 3 pole Code Unit (EA) Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M1 Molded Case Circuit Breaker_ 35 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UAB type / 50AF | •UAB50C 7.5/5kA •UAB50R 14/10kA UAB50C UAB50R Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Rated current (A) Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) AC600/660V, 50-60Hz Rated short-circuit Ultimate AC480/500V, 50-60Hz breaking [Icu] AC440/460V, 50-60Hz capacity (kA r.m.s.) AC380/415V, 50-60Hz IEC 60947-2 AC220/240V, 50-60Hz K 60947-2 Service [Ics] % of [Icu] Trip mechanism Hydraulic Fixed thermal, & Protection magnetic Fixed instantaneous INST characteristics 2, 3, 4 IP20 A ○ overload, inst., short-circuit 5,10,15,20,30,40,50 AC690 AC660 6 2.5 5 2.5 7.5 5 10 7.5/5 14/10 10 25 50 ○ 12×In Direct mounting by screw ○ Both line & load side ○1) for Mounting Switchboard Line side only Plug-in ○1) for Distribution board ○1) Terminal connection Screw ○ Mechanical operation 25,000 Durability (times) Electrical operation 15,000 a Width 50/75/100 d a c b Height 130 Dimensions 2/3/4P b (mm) c Depth 60 d 82 Weight (kg, breaker only) 2/3/4P 0.45/0.65/0.85 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip1) Under voltage trip2) 1C, right-hand-side 2C, right-hand-side AUX 10A R1 AUX 10A R2 1C, right-hand-side ALT 10A R1 DC24V DC100-110V SHT 10A A SHT 10A C DC24V DC100-110V UVT 10A J UVT 10A L AC100-120V AC200-230V SHT 10A F AC100-120V AC200-230V UVT 10A N UVT 10A P ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. 36 AC380-415V SHT 10A H AC380-415V UVT 10A Q AC440-480V AC440-480V UVT 10A R MCCB •Operating Upper Power supply direction TFG 10AS U4 S type Operating Surface TFG 10AL U4 L type handle1) S type Extended L type DC24V Motor operator 2) MOT 10A DC24 2 pole Mechanical interlock Padlock plate3) Right Left TFG 10AS R4 TFG 10AS L4 TFG 10AL L4 TFH 10AS TFH 10AL AC/DC110V AC/DC220V MOT 10A ADC110 MOT 10A ADC220 3 pole 4 pole MIF 10A 3 MIF 10A 4 PLD 10UA ※ 1) Available for 3P, 4P breaker. For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting Plug-in1) Structure Mounting base Connection 2C contact block 2) 3C contact Conn. block barrier For both line & load side TDM 10AP CBM 10AB 2 CBM 10AB 3 CBM BARR For line side only TDM 10AF - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. •Terminal Cage terminal block Terminal cover1) Interpole barrier 2) 2EA/SET 3EA/SET4EA/SET CTB 10A 3S50 CTB 10A 4S50 2 pole 3 pole 4 pole TCF 10AP 2 TCF 10AP 3 TCF 10AP 4 TQQ 10A 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Hydraulic magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V 표준품 주문코드 Rated current 2 pole Code Unit (EA) 3 pole Code Unit (EA) 4 pole Code Unit (EA) Specification Category 5A UAB50C 2PT4S0000C 00005 30 UAB50C 3PT4S0000C 00005 20 UAB50C 4PT4S0000C 00005 16 10A UAB50C 2PT4S0000C 00010 30 UAB50C 3PT4S0000C 00010 20 UAB50C 4PT4S0000C 00010 16 UAB50C 15A UAB50C 2PT4S0000C 00015 30 UAB50C 3PT4S0000C 00015 20 UAB50C 4PT4S0000C 00015 16 20A UAB50C 2PT4S0000C 00020 30 UAB50C 3PT4S0000C 00020 20 UAB50C 4PT4S0000C 00020 16 30A UAB50C 2PT4S0000C 00030 30 UAB50C 3PT4S0000C 00030 20 UAB50C 4PT4S0000C 00030 16 40A UAB50C 2PT4S0000C 00040 30 UAB50C 3PT4S0000C 00040 20 UAB50C 4PT4S0000C 00040 16 50A UAB50C 2PT4S0000C 00050 30 UAB50C 3PT4S0000C 00050 20 UAB50C 4PT4S0000C 00050 16 5A UAB50R 2PT4S0000C 00005 30 UAB50R 3PT4S0000C 00005 20 10A UAB50R 2PT4S0000C 00010 30 UAB50R 3PT4S0000C 00010 20 Screw type terminal connection, UAB50R 4PT4S0000C 00005 16 No option, UAB50R 4PT4S0000C 00010 16 50/60Hz UAB50R 15A UAB50R 2PT4S0000C 00015 30 UAB50R 3PT4S0000C 00015 20 UAB50R 4PT4S0000C 00015 16 20A UAB50R 2PT4S0000C 00020 30 UAB50R 3PT4S0000C 00020 20 UAB50R 4PT4S0000C 00020 16 30A UAB50R 2PT4S0000C 00030 30 UAB50R 3PT4S0000C 00030 20 UAB50R 4PT4S0000C 00030 16 40A UAB50R 2PT4S0000C 00040 30 UAB50R 3PT4S0000C 00040 20 UAB50R 4PT4S0000C 00040 16 50A UAB50R 2PT4S0000C 00050 30 UAB50R 3PT4S0000C 00050 20 UAB50R 4PT4S0000C 00050 16 7.5/5kA 14/10kA MCCB /M1 Molded Case Circuit Breaker_ 37 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UAB type / 50AF | •UAB50S 25kA •UAB50H 30kA UAB50S UAB50H Number of poles (P) Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection 2, 3, 4 overload, inst., short-circuit Rated current (A) 15,16,20,25,30,32,40,50 Rated insulation voltage [Ui] (V) AC690 Rating AC660 Rated operational voltage [Ue] (V) DC250 Rated impulse withstand voltage [Uimp] (kV) 6 AC600/660V, 50-60Hz 7.5 10 Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) AC480/500V, 50-60Hz 7.5 14 IEC 60947-2 K 60947-2 AC440/460V, 50-60Hz 21 25 AC380/415V, 50-60Hz 25 30 AC220/240V, 50-60Hz 42 50 DC250V 10 14 DC125V 15 20 Service [Ics] % of [Icu] 25 ○ Fixed thermal, Trip Fixed instantaneous INST 15-32A: 20×In, 40-100A: 10×In Thermal mechanism & Protection magnetic LTD (0.8-0.9-1)×In 2) Adjustable thermal, characteristics Fixed instantaneous INST 15-32A: 20×In, 40-100A: 10×In Direct mounting by screw ○ Both line & load side for Switchboard Line side only Mounting Plug-in ○1) ○1) DIN-rail Terminal connection ○1) for Distribution board with DIN-rail adaptor ○ Screw ○ Durability Mechanical operation 25,000 (times) Electrical operation 15,000 a Width 50/75/100 Dimensions b Height 130 Depth 60 a d c 2/3/4P (mm) c b d 82 Weight (kg, breaker only) 0.6/0.78/0.96 2/3/4P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) Available for 3P, 4P breaker 38 MCCB ■ Accessories •Signal 1C, right-hand-side Auxiliary switch Trip alarm switch Shunt trip 1) Under voltage trip2) 1C, left-hand-side AUX 10UA R1 AUX 10UA L1 1C, right-hand-side 1C, left-hand-side ALT 10UA R1 ALT 10UA L1 DC24V DC100-110V AC100-120V AC200-230V AC380-415V SHT 10UA A - SHT 10UA F SHT 10UA H SHT 10UA B SHT 10UA D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V UVT 10UA J UVT 10UA L UVT 10UA N UVT 10UA P UVT 10UA Q UVT 10UA R AC440-480V ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. •Operating Upper Right Left TFG 10UAS U4 TFG 10UAS R4 TFG 10UAS L4 - TFG 10UAL L4 Power supply direction Operating Surface handle1) Extended S type L type TFG 10UAL U4 S type L type Motor operator2) TFH 10UAL DC24V AC/DC110V AC/DC220V MOT 10UA DC24 MOT 10UA ADC110 MOT 10UA ADC220 2 pole 3 pole 4 pole - MIF 10UA 3 MIF 10UA 4 PLD 10UA Mechanical interlock Padlock plate3) TFH 10UAS ※ 1) Available for 3P, 4P breaker. For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting DIN-rail adaptor DRA 10UA Structure Mounting base Plug-in1) Connection 2C contact block2) 3C contact Conn. block barrier For both line & load side For line side only TDM 10AP TDM 10AF CBM 10AB 2 - CBM 10AB 3 - CBM BARR - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. •Terminal 3EA/SET4EA/SET Cage terminal block CTB 10A 3S50 CTB 10A 4S50 2 pole Terminal cover1) Interpole barrier2) TCF 10AP 2 2EA/SET 3 pole TCF 10AP 3 4 pole TCF 10AP 4 TQQ 10A 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA Molded Case Circuit Breaker_ 39 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current 15A UAB50S 2PT4S0000C 00015 30 UAB50S 3PT4S0000C 00015 20 UAB50S 4PT4S0000C 00015 16 16A UAB50S 2PT4S0000C 00016 30 UAB50S 3PT4S0000C 00016 20 UAB50S 4PT4S0000C 00016 16 20A UAB50S 2PT4S0000C 00020 30 UAB50S 3PT4S0000C 00020 20 UAB50S 4PT4S0000C 00020 16 UAB50S 25A UAB50S 2PT4S0000C 00025 30 UAB50S 3PT4S0000C 00025 20 UAB50S 4PT4S0000C 00025 16 2 pole Code 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) Specification Category 25kA 30A UAB50S 2PT4S0000C 00030 30 UAB50S 3PT4S0000C 00030 20 UAB50S 4PT4S0000C 00030 16 32A UAB50S 2PT4S0000C 00032 30 UAB50S 3PT4S0000C 00032 20 UAB50S 4PT4S0000C 00032 16 40A UAB50S 2PT4S0000C 00040 30 UAB50S 3PT4S0000C 00040 20 UAB50S 4PT4S0000C 00040 50A UAB50S 2PT4S0000C 00050 30 UAB50S 3PT4S0000C 00050 20 UAB50S 4PT4S0000C 00050 15A UAB50H 2PT4S0000C 00015 30 UAB50H 3PT4S0000C 00015 20 16A UAB50H 2PT4S0000C 00016 30 UAB50H 3PT4S0000C 00016 20 16 Screw type 16 terminal connection, UAB50H 4PT4S0000C 00015 16 No option, UAB50H 4PT4S0000C 00016 16 50/60Hz 20A UAB50H 2PT4S0000C 00020 30 UAB50H 3PT4S0000C 00020 20 UAB50H 4PT4S0000C 00020 16 UAB50H 25A UAB50H 2PT4S0000C 00025 30 UAB50H 3PT4S0000C 00025 20 UAB50H 4PT4S0000C 00025 16 30kA 30A UAB50H 2PT4S0000C 00030 30 UAB50H 3PT4S0000C 00030 20 UAB50H 4PT4S0000C 00030 16 32A UAB50H 2PT4S0000C 00032 30 UAB50H 3PT4S0000C 00032 20 UAB50H 4PT4S0000C 00032 16 40A UAB50H 2PT4S0000C 00040 30 UAB50H 3PT4S0000C 00040 20 UAB50H 4PT4S0000C 00040 16 50A UAB50H 2PT4S0000C 00050 30 UAB50H 3PT4S0000C 00050 20 UAB50H 4PT4S0000C 00050 16 MCCB /M2 50℃ 40 Model / Breaking capacity at AC380/415V Rated current 15A UAB50S 2PT5S0000C 00015 30 UAB50S 3PT5S0000C 00015 20 UAB50S 4PT5S0000C 00015 16 16A UAB50S 2PT5S0000C 00016 30 UAB50S 3PT5S0000C 00016 20 UAB50S 4PT5S0000C 00016 16 20A UAB50S 2PT5S0000C 00020 30 UAB50S 3PT5S0000C 00020 20 UAB50S 4PT5S0000C 00020 16 UAB50S 25A UAB50S 2PT5S0000C 00025 30 UAB50S 3PT5S0000C 00025 20 UAB50S 4PT5S0000C 00025 16 25kA 30A UAB50S 2PT5S0000C 00030 30 UAB50S 3PT5S0000C 00030 20 UAB50S 4PT5S0000C 00030 16 32A UAB50S 2PT5S0000C 00032 30 UAB50S 3PT5S0000C 00032 20 UAB50S 4PT5S0000C 00032 16 40A UAB50S 2PT5S0000C 00040 30 UAB50S 3PT5S0000C 00040 20 UAB50S 4PT5S0000C 00040 50A UAB50S 2PT5S0000C 00050 30 UAB50S 3PT5S0000C 00050 20 UAB50S 4PT5S0000C 00050 15A UAB50H 2PT5S0000C 00015 30 UAB50H 3PT5S0000C 00015 20 UAB50H 4PT5S0000C 00015 16A UAB50H 2PT5S0000C 00016 30 UAB50H 3PT5S0000C 00016 20 UAB50H 4PT5S0000C 00016 16 Screw type 16 terminal connection, 16 No option, 16 50/60Hz 20A UAB50H 2PT5S0000C 00020 30 UAB50H 3PT5S0000C 00020 20 UAB50H 4PT5S0000C 00020 16 UAB50H 25A UAB50H 2PT5S0000C 00025 30 UAB50H 3PT5S0000C 00025 20 UAB50H 4PT5S0000C 00025 16 2 pole Code 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) 30kA 30A UAB50H 2PT5S0000C 00030 30 UAB50H 3PT5S0000C 00030 20 UAB50H 4PT5S0000C 00030 16 32A UAB50H 2PT5S0000C 00032 30 UAB50H 3PT5S0000C 00032 20 UAB50H 4PT5S0000C 00032 16 40A UAB50H 2PT5S0000C 00040 30 UAB50H 3PT5S0000C 00040 20 UAB50H 4PT5S0000C 00040 16 50A UAB50H 2PT5S0000C 00050 30 UAB50H 3PT5S0000C 00050 20 UAB50H 4PT5S0000C 00050 16 Specification Category MCCB /M2 MCCB •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current 15A UAB50S 3PT4S0000C 00015F 16A UAB50S 3PT4S0000C 00016F 20A UAB50S 3PT4S0000C 00020F UAB50S 25A UAB50S 3PT4S0000C 00025F 3 pole Code 4 pole Unit (EA) Code Unit (EA) 20 UAB50S 4PT4S0000C 00015F 16 20 UAB50S 4PT4S0000C 00016F 16 20 UAB50S 4PT4S0000C 00020F 16 20 UAB50S 4PT4S0000C 00025F 16 25kA 30A UAB50S 3PT4S0000C 00030F 20 UAB50S 4PT4S0000C 00030F 16 32A UAB50S 3PT4S0000C 00032F 20 UAB50S 4PT4S0000C 00032F 16 40A UAB50S 3PT4S0000C 00040F 20 UAB50S 4PT4S0000C 00040F 16 50A UAB50S 3PT4S0000C 00050F 20 UAB50S 4PT4S0000C 00050F 16 15A UAB50H 3PT4S0000C 00015F 20 UAB50H 4PT4S0000C 00015F 16 16A UAB50H 3PT4S0000C 00016F 20 UAB50H 4PT4S0000C 00016F 16 20A UAB50H 3PT4S0000C 00020F 20 UAB50H 4PT4S0000C 00020F 16 UAB50H 25A UAB50H 3PT4S0000C 00025F 20 UAB50H 4PT4S0000C 00025F 16 30kA 30A UAB50H 3PT4S0000C 00030F 20 UAB50H 4PT4S0000C 00030F 16 32A UAB50H 3PT4S0000C 00032F 20 UAB50H 4PT4S0000C 00032F 16 40A UAB50H 3PT4S0000C 00040F 20 UAB50H 4PT4S0000C 00040F 16 50A UAB50H 3PT4S0000C 00050F 20 UAB50H 4PT4S0000C 00050F 16 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V Rated current 15A 16A UAB50S 3PT5S0000C 00016F 20 UAB50S 4PT5S0000C 00016F 16 20A UAB50S 3PT5S0000C 00020F 20 UAB50S 4PT5S0000C 00020F 16 UAB50S 25A UAB50S 3PT5S0000C 00025F 20 UAB50S 4PT5S0000C 00025F 16 25kA 30A UAB50S 3PT5S0000C 00030F 20 UAB50S 4PT5S0000C 00030F 16 32A UAB50S 3PT5S0000C 00032F 20 UAB50S 4PT5S0000C 00032F 16 40A UAB50S 3PT5S0000C 00040F 20 UAB50S 4PT5S0000C 00040F 16 50A UAB50S 3PT5S0000C 00050F 20 UAB50S 4PT5S0000C 00050F 16 15A UAB50H 3PT5S0000C 00015F 20 UAB50H 4PT5S0000C 00015F 16 16A UAB50H 3PT5S0000C 00016F 20 UAB50H 4PT5S0000C 00016F 16 20A UAB50H 3PT5S0000C 00020F 20 UAB50H 4PT5S0000C 00020F 16 UAB50H 25A UAB50H 3PT5S0000C 00025F 20 UAB50H 4PT5S0000C 00025F 16 30kA 30A UAB50H 3PT5S0000C 00030F 20 UAB50H 4PT5S0000C 00030F 16 32A UAB50H 3PT5S0000C 00032F 20 UAB50H 4PT5S0000C 00032F 16 3 pole 4 pole Code Unit (EA) Code Unit (EA) UAB50S 3PT5S0000C 00015F 20 UAB50S 4PT5S0000C 00015F 16 40A UAB50H 3PT5S0000C 00040F 20 UAB50H 4PT5S0000C 00040F 16 50A UAB50H 3PT5S0000C 00050F 20 UAB50H 4PT5S0000C 00050F 16 Molded Case Circuit Breaker_ 41 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UAB type / 60AF | •UAB60C 7.5/5kA •UAB60R 14/10kA UAB60C UAB60R 2, 3, 4 Number of poles (P) IP20 Degree of protection (with terminal cover) A Utilization category ○ Suitability of isolation overload, inst., short-circuit Protection 5,10,15,20,30,40,50,60 Rated current (A) AC690 Rated insulation voltage [Ui] (V) Rating AC660 Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) 6 2.5 5 AC600/660V, 50-60Hz Rated 2.5 7.5 AC480/500V, 50-60Hz short-circuit Ultimate breaking 5 10 [Icu] AC440/460V, 50-60Hz capacity 7.5/5 14/10 (kA r.m.s.) AC380/415V, 50-60Hz IEC 60947-2 10 25 AC220/240V, 50-60Hz K 60947-2 Service [Ics] % of [Icu] 50 Trip mechanism Hydraulic Fixed thermal, ○ & Protection magnetic Fixed instantaneous INST 12×In characteristics Direct mounting by screw ○ Both line & load side ○ for Mounting Switchboard Line side only ○ Plug-in 1) ○ for Distribution board ○1) Terminal connection Screw Mechanical operation 25,000 Durability (times) 10,000 Electrical operation 50/75/100 a Width d a c 130 b Height Dimensions 2/3/4P b (mm) 60 c Depth 82 d Weight (kg, breaker only) 0.45/0.65/0.85 2/3/4P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip1) Under voltage trip2) 1C, right-hand-side 2C, right-hand-side AUX 10A R1 AUX 10A R2 1C, right-hand-side ALT 10A R1 DC24V DC100-110V SHT 10A A SHT 10A C DC24V DC100-110V ✽UVT 10A J ✽UVT 10A L AC100-120V AC200-230V SHT 10A F AC100-120V AC200-230V ✽UVT 10A N ✽UVT 10A P ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. 42 AC380-415V SHT 10A H AC380-415V ✽UVT 10A Q AC440-480V AC440-480V ✽UVT 10A R MCCB •Operating Power supply direction S type Operating Surface L type 1) handle S type Extended L type Motor operator 2) Mechanical interlock Upper TFG 10AS U4 TFG 10AL U4 DC24V MOT 10A DC24 2 pole Right TFG 10AS R4 Left TFG 10AS L4 TFG 10AL L4 TFH 10AS TFH 10AL AC/DC110V AC/DC220V MOT 10A ADC110 MOT 10A ADC220 3 pole 4 pole MIF 10A 3 MIF 10A 4 PLD 10UA - Padlock plate3) ※ 1) Available for 3P, 4P breaker. For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting Plug-in1) Structure Mounting base Connection 2C contact 3C contact block2) Conn. block barrier For both line & load side TDM 10AP CBM 10AB 2 CBM 10AB 3 CBM BARR For line side only TDM 10AF - ※ 1) Available for 3P, 4P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. •Terminal Cage terminal block 5-50A 60A Terminal cover1) Interpole barrier2) 2EA/SET 3EA/SET4EA/SET CTB 10A 3S50 CTB 10A 4S50 CTB 10A 3S100 CTB 10A 4S100 2 pole 3 pole 4 pole TCF 10AP 2 TCF 10AP 3 TCF 10AP 4 TQQ 10A 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Hydraulic magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current 2 pole Code Unit (EA) 3 pole Code Unit (EA) 4 pole Code Unit (EA) Specification Category 5A UAB60C 2PT4S0000C 00005 30 UAB60C 3PT4S0000C 00005 20 UAB60C 4PT4S0000C 00005 16 10A UAB60C 2PT4S0000C 00010 30 UAB60C 3PT4S0000C 00010 20 UAB60C 4PT4S0000C 00010 16 15A UAB60C 2PT4S0000C 00015 30 UAB60C 3PT4S0000C 00015 20 UAB60C 4PT4S0000C 00015 16 UAB60C 20A UAB60C 2PT4S0000C 00020 30 UAB60C 3PT4S0000C 00020 20 UAB60C 4PT4S0000C 00020 16 7.5/5kA 30A UAB60C 2PT4S0000C 00030 30 UAB60C 3PT4S0000C 00030 20 UAB60C 4PT4S0000C 00030 40A UAB60C 2PT4S0000C 00040 30 UAB60C 3PT4S0000C 00040 20 UAB60C 4PT4S0000C 00040 16 50A UAB60C 2PT4S0000C 00050 30 UAB60C 3PT4S0000C 00050 20 60A UAB60C 2PT4S0000C 00060 30 UAB60C 3PT4S0000C 00060 20 5A UAB60R 2PT4S0000C 00005 30 UAB60R 3PT4S0000C 00005 20 10A UAB60R 2PT4S0000C 00010 30 UAB60R 3PT4S0000C 00010 20 UAB60R 15A UAB60R 2PT4S0000C 00015 30 UAB60R 3PT4S0000C 00015 20 UAB60C 4PT4S0000C 00050 16 Screw type UAB60C 4PT4S0000C 00060 16 terminal connection, UAB60R 4PT4S0000C 00005 16 No option, UAB60R 4PT4S0000C 00010 16 50/60Hz UAB60R 4PT4S0000C 00015 16 20A UAB60R 2PT4S0000C 00020 30 UAB60R 3PT4S0000C 00020 20 UAB60R 4PT4S0000C 00020 16 14/10kA 30A UAB60R 2PT4S0000C 00030 30 UAB60R 3PT4S0000C 00030 20 UAB60R 4PT4S0000C 00030 16 40A UAB60R 2PT4S0000C 00040 30 UAB60R 3PT4S0000C 00040 20 UAB60R 4PT4S0000C 00040 16 50A UAB60R 2PT4S0000C 00050 30 UAB60R 3PT4S0000C 00050 20 UAB60R 4PT4S0000C 00050 16 60A UAB60R 2PT4S0000C 00060 30 UAB60R 3PT4S0000C 00060 20 UAB60R 4PT4S0000C 00060 16 16 MCCB /M1 Molded Case Circuit Breaker_ 43 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UAB type / 100AF | •UAB100C 14/10kA UAB100C Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Rated current (A) Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) AC600/660V, 50-60Hz Rated short-circuit Ultimate AC480/500V, 50-60Hz breaking [Icu] AC440/460V, 50-60Hz capacity (kA r.m.s.) AC380/415V, 50-60Hz IEC 60947-2 AC220/240V, 50-60Hz K 60947-2 Service [Ics] % of [Icu] Trip mechanism Hydraulic Fixed thermal, & Protection magnetic Fixed instantaneous INST characteristics 2, 3, 4 IP20 A ○ overload, inst., short-circuit 5,10,15,20,30,40,50,60,75,100 AC690 AC660 6 5 7.5 10 14/10 25 50 ○ 12×In ○ ○ ○1) ○1) ○ 25,000 10,000 50/75/100 130 60 82 0.45/0.65/0.85 Direct mounting by screw Both line & load side for Mounting Switchboard Line side only Plug-in for Distribution board Terminal connection Screw Mechanical operation Durability (times) Electrical operation a Width d a c b Height Dimensions 2/3/4P b (mm) c Depth d Weight (kg, breaker only) 2/3/4P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip1) Under voltage trip2) 1C, right-hand-side 2C, right-hand-side AUX 10A R1 AUX 10A R2 1C, right-hand-side ALT 10A R1 DC24V DC100-110V SHT 10A A SHT 10A C DC24V DC100-110V ✽UVT 10A J ✽UVT 10A L AC100-120V AC200-230V SHT 10A F AC100-120V AC200-230V ✽UVT 10A N ✽UVT 10A P ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. 44 AC380-415V SHT 10A H AC380-415V ✽UVT 10A Q AC440-480V AC440-480V ✽UVT 10A R MCCB •Operating Power supply direction Upper S type TFG 10AS U4 Operating Surface L type TFG 10AL U4 handle1) S type Extended L type DC24V Motor operator 2) MOT 10A DC24 2 pole Mechanical interlock Padlock plate3) Right Left TFG 10AS R4 TFG 10AS L4 TFG 10AL L4 TFH 10AS TFH 10AL AC/DC110V AC/DC220V MOT 10A ADC110 MOT 10A ADC220 3 pole 4 pole MIF 10A 3 MIF 10A 4 PLD 10UA ※ 1) Available for 3P, 4P breaker. For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting Plug-in1) Structure Mounting base Connection 2C contact block2) 3C contact Conn. block barrier For both line & load side TDM 10AP CBM 10AB 2 CBM 10AB 3 CBM BARR For line side only TDM 10AF - ※ 1) Available for 3P, 4P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. •Terminal Cage terminal block 5-50A 60-100A Terminal cover1) Interpole barrier2) 2EA/SET 3EA/SET CTB 10A 3S50 CTB 10A 3S100 2 pole TCF 10AP 2 4EA/SET CTB 10A 4S50 CTB 10A 4S100 3 pole 4 pole TCF 10AP 3 TCF 10AP 4 TQQ 10A 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Hydraulic magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V 표준품 주문코드 Rated current 2 pole Code 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) Specification Category 5A UAB100C 2PT4S0000C 00005 30 UAB100C 3PT4S0000C 00005 20 UAB100C 4PT4S0000C 00005 16 10A UAB100C 2PT4S0000C 00010 30 UAB100C 3PT4S0000C 00010 20 UAB100C 4PT4S0000C 00010 16 15A UAB100C 2PT4S0000C 00015 30 UAB100C 3PT4S0000C 00015 20 UAB100C 4PT4S0000C 00015 16 20A UAB100C 30A 14/10kA 40A 50A UAB100C 2PT4S0000C 00020 30 UAB100C 3PT4S0000C 00020 20 UAB100C 4PT4S0000C 00020 16 Screw type UAB100C 2PT4S0000C 00030 30 UAB100C 3PT4S0000C 00030 20 UAB100C 4PT4S0000C 00030 16 terminal connection, UAB100C 2PT4S0000C 00040 30 UAB100C 3PT4S0000C 00040 20 UAB100C 4PT4S0000C 00040 16 No option, UAB100C 2PT4S0000C 00050 30 UAB100C 3PT4S0000C 00050 20 UAB100C 4PT4S0000C 00050 16 50/60Hz 60A UAB100C 2PT4S0000C 00060 30 UAB100C 3PT4S0000C 00060 20 UAB100C 4PT4S0000C 00060 16 75A UAB100C 2PT4S0000C 00075 30 UAB100C 3PT4S0000C 00075 20 UAB100C 4PT4S0000C 00075 16 100A UAB100C 2PT4S0000C 00100 30 UAB100C 3PT4S0000C 00100 20 UAB100C 4PT4S0000C 00100 16 MCCB /M1 Molded Case Circuit Breaker_ 45 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UAB type / 100AF | •UAB100R 25kA •UAB100S 30kA UAB100S UAB100R Number of poles (P) Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection 2, 3, 4 overload, inst., short-circuit Rated current (A) 15,16,20,25,30,32,40,50,60,63,75,80,100 Rated insulation voltage [Ui] (V) AC690 Rating AC660 Rated operational voltage [Ue] (V) DC250 Rated impulse withstand voltage [Uimp] (kV) 6 AC600/660V, 50-60Hz 7.5 10 Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) AC480/500V, 50-60Hz 7.5 14 AC440/460V, 50-60Hz 21 25 AC380/415V, 50-60Hz 25 30 AC220/240V, 50-60Hz 42 50 IEC 60947-2 K 60947-2 DC250V 10 14 DC125V 15 20 Service [Ics] % of [Icu] 25 ○ Fixed thermal, Trip Fixed instantaneous INST 15-32A: 20×In, 40-100A: 10×In mechanism Thermal magnetic & Protection LTD (0.8-0.9-1)×In 2) Adjustable thermal, characteristics Fixed instantaneous INST 15-32A: 20×In, 40-100A: 10×In Direct mounting by screw ○ Both line & load side ○ for Switchboard Mounting Plug-in Line side only ○1) DIN-rail Terminal connection Durability (times) for Distribution board ○1) with DIN-rail adaptor ○ Screw ○ Mechanical operation 25,000 Electrical operation a 10,000 a d c b Dimensions 2/3/4P b (mm) c Width 50/75/100 Height 130 Depth 60 d 82 Weight (kg, breaker only) 0.6/0.78/0.96 2/3/4P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) Available for 3P, 4P breaker 46 MCCB ■ Accessories •Signal 1C, right-hand-side 1C, left-hand-side Auxiliary switch AUX 10UA R1 Trip alarm switch Shunt trip AUX 10UA L1 1C, right-hand-side 1C, left-hand-side 1) Under voltage trip2) ALT 10UA R1 ALT 10UA L1 DC24V DC100-110V AC100-120V AC200-230V AC380-415V SHT 10UA A - SHT 10UA F SHT 10UA H SHT 10UA B SHT 10UA D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V UVT 10UA J UVT 10UA L UVT 10UA N UVT 10UA P UVT 10UA Q UVT 10UA R AC440-480V ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. •Operating Upper Right Left S type TFG 10UAS U4 TFG 10UAS R4 TFG 10UAS L4 L type TFG 10UAL U4 - TFG 10UAL L4 Power supply direction Operating Surface handle1) Extended S type L type Motor operator 2) TFH 10UAL DC24V AC/DC110V AC/DC220V MOT 10UA DC24 MOT 10UA ADC110 MOT 10UA ADC220 2 pole 3 pole 4 pole - MIF 10UA 3 MIF 10UA 4 PLD 10UA Mechanical interlock Padlock plate 3) TFH 10UAS ※ 1) Available for 3P, 4P breaker. For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting DIN-rail adaptor Structure Mounting base Plug-in1) Connection 2C contact block 2) DRA 10UA For both line & load side 3C contact Conn. block barrier For line side only TDM 10AP TDM 10AF CBM 10AB 2 - CBM 10AB 3 - CBM BARR - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. •Terminal 3EA/SET4EA/SET Cage terminal block 15-50A CTB 10A 3S50 CTB 10A 4S50 60-100A CTB 10A 3S100 CTB 10A 4S100 2 pole Terminal cover 1) Interpole barrier 2) TCF 10AP 2 2EA/SET 3 pole TCF 10AP 3 4 pole TCF 10AP 4 TQQ 10A 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA Molded Case Circuit Breaker_ 47 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UAB100R 25kA UAB100S 30kA 2 pole 3 pole Rated current Code Unit (EA) Code Unit (EA) 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A UAB100R 2PT4S0000C 00015 UAB100R 2PT4S0000C 00016 UAB100R 2PT4S0000C 00020 UAB100R 2PT4S0000C 00025 UAB100R 2PT4S0000C 00030 UAB100R 2PT4S0000C 00032 UAB100R 2PT4S0000C 00040 UAB100R 2PT4S0000C 00050 UAB100R 2PT4S0000C 00060 UAB100R 2PT4S0000C 00063 UAB100R 2PT4S0000C 00075 UAB100R 2PT4S0000C 00080 UAB100R 2PT4S0000C 00100 UAB100S 2PT4S0000C 00015 UAB100S 2PT4S0000C 00016 UAB100S 2PT4S0000C 00020 UAB100S 2PT4S0000C 00025 UAB100S 2PT4S0000C 00030 UAB100S 2PT4S0000C 00032 UAB100S 2PT4S0000C 00040 UAB100S 2PT4S0000C 00050 UAB100S 2PT4S0000C 00060 UAB100S 2PT4S0000C 00063 UAB100S 2PT4S0000C 00075 UAB100S 2PT4S0000C 00080 UAB100S 2PT4S0000C 00100 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 UAB100R 3PT4S0000C 00015 UAB100R 3PT4S0000C 00016 UAB100R 3PT4S0000C 00020 UAB100R 3PT4S0000C 00025 UAB100R 3PT4S0000C 00030 UAB100R 3PT4S0000C 00032 UAB100R 3PT4S0000C 00040 UAB100R 3PT4S0000C 00050 UAB100R 3PT4S0000C 00060 UAB100R 3PT4S0000C 00063 UAB100R 3PT4S0000C 00075 UAB100R 3PT4S0000C 00080 UAB100R 3PT4S0000C 00100 UAB100S 3PT4S0000C 00015 UAB100S 3PT4S0000C 00016 UAB100S 3PT4S0000C 00020 UAB100S 3PT4S0000C 00025 UAB100S 3PT4S0000C 00030 UAB100S 3PT4S0000C 00032 UAB100S 3PT4S0000C 00040 UAB100S 3PT4S0000C 00050 UAB100S 3PT4S0000C 00060 UAB100S 3PT4S0000C 00063 UAB100S 3PT4S0000C 00075 UAB100S 3PT4S0000C 00080 UAB100S 3PT4S0000C 00100 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 Rated current Code Unit (EA) Code 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A UAB100R 2PT5S0000C 00015 UAB100R 2PT5S0000C 00016 UAB100R 2PT5S0000C 00020 UAB100R 2PT5S0000C 00025 UAB100R 2PT5S0000C 00030 UAB100R 2PT5S0000C 00032 UAB100R 2PT5S0000C 00040 UAB100R 2PT5S0000C 00050 UAB100R 2PT5S0000C 00060 UAB100R 2PT5S0000C 00063 UAB100R 2PT5S0000C 00075 UAB100R 2PT5S0000C 00080 UAB100R 2PT5S0000C 00100 UAB100S 2PT5S0000C 00015 UAB100S 2PT5S0000C 00016 UAB100S 2PT5S0000C 00020 UAB100S 2PT5S0000C 00025 UAB100S 2PT5S0000C 00030 UAB100S 2PT5S0000C 00032 UAB100S 2PT5S0000C 00040 UAB100S 2PT5S0000C 00050 UAB100S 2PT5S0000C 00060 UAB100S 2PT5S0000C 00063 UAB100S 2PT5S0000C 00075 UAB100S 2PT5S0000C 00080 UAB100S 2PT5S0000C 00100 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 UAB100R 3PT5S0000C 00015 UAB100R 3PT5S0000C 00016 UAB100R 3PT5S0000C 00020 UAB100R 3PT5S0000C 00025 UAB100R 3PT5S0000C 00030 UAB100R 3PT5S0000C 00032 UAB100R 3PT5S0000C 00040 UAB100R 3PT5S0000C 00050 UAB100R 3PT5S0000C 00060 UAB100R 3PT5S0000C 00063 UAB100R 3PT5S0000C 00075 UAB100R 3PT5S0000C 00080 UAB100R 3PT5S0000C 00100 UAB100S 3PT5S0000C 00015 UAB100S 3PT5S0000C 00016 UAB100S 3PT5S0000C 00020 UAB100S 3PT5S0000C 00025 UAB100S 3PT5S0000C 00030 UAB100S 3PT5S0000C 00032 UAB100S 3PT5S0000C 00040 UAB100S 3PT5S0000C 00050 UAB100S 3PT5S0000C 00060 UAB100S 3PT5S0000C 00063 UAB100S 3PT5S0000C 00075 UAB100S 3PT5S0000C 00080 UAB100S 3PT5S0000C 00100 4 pole Code UAB100R 4PT4S0000C 00015 UAB100R 4PT4S0000C 00016 UAB100R 4PT4S0000C 00020 UAB100R 4PT4S0000C 00025 UAB100R 4PT4S0000C 00030 UAB100R 4PT4S0000C 00032 UAB100R 4PT4S0000C 00040 UAB100R 4PT4S0000C 00050 UAB100R 4PT4S0000C 00060 UAB100R 4PT4S0000C 00063 UAB100R 4PT4S0000C 00075 UAB100R 4PT4S0000C 00080 UAB100R 4PT4S0000C 00100 UAB100S 4PT4S0000C 00015 UAB100S 4PT4S0000C 00016 UAB100S 4PT4S0000C 00020 UAB100S 4PT4S0000C 00025 UAB100S 4PT4S0000C 00030 UAB100S 4PT4S0000C 00032 UAB100S 4PT4S0000C 00040 UAB100S 4PT4S0000C 00050 UAB100S 4PT4S0000C 00060 UAB100S 4PT4S0000C 00063 UAB100S 4PT4S0000C 00075 UAB100S 4PT4S0000C 00080 UAB100S 4PT4S0000C 00100 Unit (EA) Specification Category 16 16 16 16 16 16 16 16 16 16 16 16 Screw type 16 terminal 16 connection, No option, 16 50/60Hz 16 16 16 16 16 16 16 16 16 16 16 MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UAB100R 25kA UAB100S 30kA 48 2 pole 3 pole Unit (EA) 4 pole Code 20 UAB100R 4PT5S0000C 00015 20 UAB100R 4PT5S0000C 00016 20 UAB100R 4PT5S0000C 00020 20 UAB100R 4PT5S0000C 00025 20 UAB100R 4PT5S0000C 00030 20 UAB100R 4PT5S0000C 00032 20 UAB100R 4PT5S0000C 00040 20 UAB100R 4PT5S0000C 00050 20 UAB100R 4PT5S0000C 00060 20 UAB100R 4PT5S0000C 00063 20 UAB100R 4PT5S0000C 00075 20 UAB100R 4PT5S0000C 00080 20 UAB100R 4PT5S0000C 00100 20 UAB100S 4PT5S0000C 00015 20 UAB100S 4PT5S0000C 00016 20 UAB100S 4PT5S0000C 00020 20 UAB100S 4PT5S0000C 00025 20 UAB100S 4PT5S0000C 00030 20 UAB100S 4PT5S0000C 00032 20 UAB100S 4PT5S0000C 00040 20 UAB100S 4PT5S0000C 00050 20 UAB100S 4PT5S0000C 00060 20 UAB100S 4PT5S0000C 00063 20 UAB100S 4PT5S0000C 00075 20 UAB100S 4PT5S0000C 00080 20 UAB100S 4PT5S0000C 00100 Unit (EA) Specification Category 16 16 16 16 16 16 16 16 16 16 16 16 Screw type 16 terminal 16 connection, No option, 16 50/60Hz 16 16 16 16 16 16 16 16 16 16 16 MCCB /M2 MCCB •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UAB100R 25kA UAB100S 30kA Rated current 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 3 pole Code UAB100R 3PT4S0000C 00015F UAB100R 3PT4S0000C 00016F UAB100R 3PT4S0000C 00020F UAB100R 3PT4S0000C 00025F UAB100R 3PT4S0000C 00030F UAB100R 3PT4S0000C 00032F UAB100R 3PT4S0000C 00040F UAB100R 3PT4S0000C 00050F UAB100R 3PT4S0000C 00060F UAB100R 3PT4S0000C 00063F UAB100R 3PT4S0000C 00075F UAB100R 3PT4S0000C 00080F UAB100R 3PT4S0000C 00100F UAB100S 3PT4S0000C 00015F UAB100S 3PT4S0000C 00016F UAB100S 3PT4S0000C 00020F UAB100S 3PT4S0000C 00025F UAB100S 3PT4S0000C 00030F UAB100S 3PT4S0000C 00032F UAB100S 3PT4S0000C 00040F UAB100S 3PT4S0000C 00050F UAB100S 3PT4S0000C 00060F UAB100S 3PT4S0000C 00063F UAB100S 3PT4S0000C 00075F UAB100S 3PT4S0000C 00080F UAB100S 3PT4S0000C 00100F Unit (EA) 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 4 pole Code UAB100R 4PT4S0000C 00015F UAB100R 4PT4S0000C 00016F UAB100R 4PT4S0000C 00020F UAB100R 4PT4S0000C 00025F UAB100R 4PT4S0000C 00030F UAB100R 4PT4S0000C 00032F UAB100R 4PT4S0000C 00040F UAB100R 4PT4S0000C 00050F UAB100R 4PT4S0000C 00060F UAB100R 4PT4S0000C 00063F UAB100R 4PT4S0000C 00075F UAB100R 4PT4S0000C 00080F UAB100R 4PT4S0000C 00100F UAB100S 4PT4S0000C 00015F UAB100S 4PT4S0000C 00016F UAB100S 4PT4S0000C 00020F UAB100S 4PT4S0000C 00025F UAB100S 4PT4S0000C 00030F UAB100S 4PT4S0000C 00032F UAB100S 4PT4S0000C 00040F UAB100S 4PT4S0000C 00050F UAB100S 4PT4S0000C 00060F UAB100S 4PT4S0000C 00063F UAB100S 4PT4S0000C 00075F UAB100S 4PT4S0000C 00080F UAB100S 4PT4S0000C 00100F Unit (EA) 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UAB100R 25kA UAB100S 30kA Rated current 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 3 pole Code UAB100R 3PT5S0000C 00015F UAB100R 3PT5S0000C 00016F UAB100R 3PT5S0000C 00020F UAB100R 3PT5S0000C 00025F UAB100R 3PT5S0000C 00030F UAB100R 3PT5S0000C 00032F UAB100R 3PT5S0000C 00040F UAB100R 3PT5S0000C 00050F UAB100R 3PT5S0000C 00060F UAB100R 3PT5S0000C 00063F UAB100R 3PT5S0000C 00075F UAB100R 3PT5S0000C 00080F UAB100R 3PT5S0000C 00100F UAB100S 3PT5S0000C 00015F UAB100S 3PT5S0000C 00016F UAB100S 3PT5S0000C 00020F UAB100S 3PT5S0000C 00025F UAB100S 3PT5S0000C 00030F UAB100S 3PT5S0000C 00032F UAB100S 3PT5S0000C 00040F UAB100S 3PT5S0000C 00050F UAB100S 3PT5S0000C 00060F UAB100S 3PT5S0000C 00063F UAB100S 3PT5S0000C 00075F UAB100S 3PT5S0000C 00080F UAB100S 3PT5S0000C 00100F Unit (EA) 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 4 pole Code UAB100R 4PT5S0000C 00015F UAB100R 4PT5S0000C 00016F UAB100R 4PT5S0000C 00020F UAB100R 4PT5S0000C 00025F UAB100R 4PT5S0000C 00030F UAB100R 4PT5S0000C 00032F UAB100R 4PT5S0000C 00040F UAB100R 4PT5S0000C 00050F UAB100R 4PT5S0000C 00060F UAB100R 4PT5S0000C 00063F UAB100R 4PT5S0000C 00075F UAB100R 4PT5S0000C 00080F UAB100R 4PT5S0000C 00100F UAB100S 4PT5S0000C 00015F UAB100S 4PT5S0000C 00016F UAB100S 4PT5S0000C 00020F UAB100S 4PT5S0000C 00025F UAB100S 4PT5S0000C 00030F UAB100S 4PT5S0000C 00032F UAB100S 4PT5S0000C 00040F UAB100S 4PT5S0000C 00050F UAB100S 4PT5S0000C 00060F UAB100S 4PT5S0000C 00063F UAB100S 4PT5S0000C 00075F UAB100S 4PT5S0000C 00080F UAB100S 4PT5S0000C 00100F Unit (EA) 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 Molded Case Circuit Breaker_ 49 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 50AF | •UCB50R 30/25kA UCB50R Number of poles (P) Degree of protection (with terminal cover) Utilization category Suitability of isolation Protection Rated current (A) Rated insulation voltage [Ui] (V) 2, 3, 4 IP20 A ○ overload, inst., short-circuit 15,20,30,40,50 AC690 AC660 DC250 6 10 14 25 30/25 50 14 20 50 ○ Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) AC600/660V, 50-60Hz Rated AC480/500V, 50-60Hz short-circuit Ultimate AC440/460V, 50-60Hz breaking [Icu] AC380/415V, 50-60Hz capacity (kA r.m.s.) AC220/240V, 50-60Hz DC250V IEC 60947-2 DC125V K 60947-2 Service [Ics] % of [Icu] Trip mechanism Thermal Fixed thermal, & Protection magnetic Fixed instantaneous INST characteristics 10×In ○ ○1) ○1) ○1) ○ Direct mounting by screw Both line & load side for Mounting Switchboard Line side only Plug-in for Distribution board Terminal connection Screw Mechanical operation Durability (times) Electrical operation a Width d a c b Height Dimensions 2/3/4P b (mm) c Depth d Weight (kg, breaker only) 2/3/4P 25,000 10,000 60/90/120 155 60 84.5 0.7/1.0/1.2 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip1) Under voltage trip2) 50 1C, left-hand-side AUX 10B L1 1C, left-hand-side ALT 10B L1 DC24V SHT 10B A DC24V UVT 10B J DC100-110V DC100-110V UVT 10B L AC100-120V AC200-230V SHT 10B F AC100-120V AC200-230V UVT 10B N UVT 10B P ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. AC380-415V SHT 10B H AC380-415V UVT 10B Q AC440-480V AC440-480V UVT 10B R MCCB •Operating Power supply direction S type Operating Surface L type 1) handle S type Extended L type Motor operator 2) Mechanical interlock Padlock plate 3) Upper TFG 10BS U4 TFG 10BL U4 DC24V MOT 10UB DC24 2 pole Right Left TFG 10BS R4 TFG 10BS L4 TFG 10BL L4 TFH 10BS TFH 10BL AC/DC110V AC/DC220V MOT 10UB ADC110 MOT 10UB ADC220 3 pole 4 pole MIF 10UF 3 MIF 10UF 4 PLD 10UF ※ 1) Available for 3P, 4P breaker. For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting Plug-in1) Structure Mounting base Connection 2C contact block2) 3C contact Conn. block barrier For both line & load side TDM 10BP CBM 10AB 2 CBM 10AB 3 CBM BARR For line side only TDM 10BF - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. •Terminal Cage terminal block Terminal cover1) Interpole barrier 2) 2EA/SET 3EA/SET4EA/SET CTB 10B 3S CTB 10B 4S 2 pole 3 pole 4 pole TCF 10BP 2 TCF 10BP 3 TCF 10BP 4 TQQ 10B 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V 표준품 주문코드 Rated current 15A UCB50R 2PT4S0000C 00015 16 UCB50R 3PT4S0000C 00015 10 UCB50R 4PT4S0000C 00015 8 UCB50R 20A UCB50R 2PT4S0000C 00020 16 UCB50R 3PT4S0000C 00020 10 UCB50R 4PT4S0000C 00020 8 30A UCB50R 2PT4S0000C 00030 16 UCB50R 3PT4S0000C 00030 10 UCB50R 4PT4S0000C 00030 8 30/25kA 2 pole Code 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) 40A UCB50R 2PT4S0000C 00040 16 UCB50R 3PT4S0000C 00040 10 UCB50R 4PT4S0000C 00040 8 50A UCB50R 2PT4S0000C 00050 16 UCB50R 3PT4S0000C 00050 10 UCB50R 4PT4S0000C 00050 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M1 50℃ Model / Breaking capacity at AC380/415V 표준품 주문코드 Rated current Code 15A UCB50R 2PT5S0000C 00015 16 UCB50R 3PT5S0000C 00015 10 UCB50R 4PT5S0000C 00015 8 UCB50R 20A UCB50R 2PT5S0000C 00020 16 UCB50R 3PT5S0000C 00020 10 UCB50R 4PT5S0000C 00020 8 30A UCB50R 2PT5S0000C 00030 16 UCB50R 3PT5S0000C 00030 10 UCB50R 4PT5S0000C 00030 8 40A UCB50R 2PT5S0000C 00040 16 UCB50R 3PT5S0000C 00040 10 UCB50R 4PT5S0000C 00040 8 50A UCB50R 2PT5S0000C 00050 16 UCB50R 3PT5S0000C 00050 10 UCB50R 4PT5S0000C 00050 8 30/25kA 2 pole 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M1 Molded Case Circuit Breaker_ 51 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 50AF | •UCB50H 42kA •UCB50L 50kA UCB50H UCB50L Number of poles (P) ✽2, 3, 4 Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection overload, inst., short-circuit Rated current (A) 15,16,20,25,30,32,40,50 Rated insulation voltage [Ui] (V) AC690 AC660 Rating Rated operational voltage [Ue] (V) DC250 Rated impulse withstand voltage [Uimp] (kV) 6 AC600/660V, 50-60Hz 20 25 Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) AC480/500V, 50-60Hz 30 35 AC440/460V, 50-60Hz 42 50 AC380/415V, 50-60Hz 42 50 AC220/240V, 50-60Hz 85 100 IEC 60947-2 K 60947-2 DC250V 25 40 DC125V 40 60 Service [Ics] % of [Icu] 50 ○ Fixed thermal, Trip Fixed instantaneous INST 15-32A: 15×In, 40-50A: 10×In mechanism Thermal magnetic & Protection LTD (0.8-0.9-1)×In Adjustable thermal, characteristics Fixed instantaneous INST 15-32A: 15×In, 40-50A: 10×In Direct mounting by screw ○ Mounting Plug-in Both line & load side ○1) for Switchboard Line side only ○1) for Distribution board ○1) Terminal connection Screw ○ Durability (times) Mechanical operation 25,000 Electrical operation a 10,000 a d c b Dimensions 2/3/4P b (mm) c Width 90 2)/90/120 Height 155 Depth 60 d 84.5 Weight (kg, breaker only) 0.9/1.0/1.3 2/3/4P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. 52 MCCB ■ Accessories •Signal 1C, left-hand-side 2C, left-hand-side Auxiliary switch AUX 12FG L1 AUX 12FG L2 1C, right-hand-side 1C, left-hand-side Trip alarm switch Shunt trip 1) Under voltage trip2) ALT 12FG R1 ALT 12FG L1 DC24V DC100-110V AC100-120V AC200-230V AC380-415V SHT 12FG A SHT 12FG C SHT 12FG F SHT 12FG H SHT 12FG B SHT 12FG D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V UVT 12FG J UVT 12FG L UVT 12FG N UVT 12FG P UVT 12FG Q UVT 12FG R AC440-480V ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. •Operating Upper Right Left TFG 10UFS U4 TFG 10UFS R4 TFG 10UFS L4 - TFG 10UFL L4 Power supply direction Operating Surface handle1) Extended S type L type TFG 10UFL U4 S type L type Motor operator 2) TFH 10UFL DC24V AC/DC110V AC/DC220V MOT 10F DC24 MOT 10F ADC110 MOT 10F ADC220 2 pole 3 pole 4 pole - MIF 10UF 3 MIF 10UF 4 PLD 10UF Mechanical interlock Padlock plate3) TFH 10UFS ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting Structure Mounting base Plug-in1) Connection 2C contact block 2) 3C contact Conn. block barrier For both line & load side For line side only TDM 10BP TDM 10BF CBM 10AB 2 - CBM 10AB 3 - CBM BARR - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. •Terminal 3EA/SET4EA/SET Cage terminal block CTB 10B 3S 2 pole Terminal cover1) Interpole barrier2) TCF 10FP 3 2EA/SET CTB 10B 4S 3 pole TCF 10FP 3 4 pole TCF 10FP 4 TQQ 12FG 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA Molded Case Circuit Breaker_ 53 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current 2 pole 3 pole 4 pole Code Unit (EA) Code Unit (EA) 15A UCB50H 2PT4S0000C 00015 8 UCB50H 3PT4S0000C 00015 8 UCB50H 4PT4S0000C 00015 6 16A UCB50H 2PT4S0000C 00016 8 UCB50H 3PT4S0000C 00016 8 UCB50H 4PT4S0000C 00016 6 20A UCB50H 2PT4S0000C 00020 8 UCB50H 3PT4S0000C 00020 8 UCB50H 4PT4S0000C 00020 6 UCB50H 25A UCB50H 2PT4S0000C 00025 8 UCB50H 3PT4S0000C 00025 8 UCB50H 4PT4S0000C 00025 6 Code Unit (EA) 42kA 30A UCB50H 2PT4S0000C 00030 8 UCB50H 3PT4S0000C 00030 8 UCB50H 4PT4S0000C 00030 6 32A UCB50H 2PT4S0000C 00032 8 UCB50H 3PT4S0000C 00032 8 UCB50H 4PT4S0000C 00032 6 40A UCB50H 2PT4S0000C 00040 8 UCB50H 3PT4S0000C 00040 8 UCB50H 4PT4S0000C 00040 6 50A UCB50H 2PT4S0000C 00050 8 UCB50H 3PT4S0000C 00050 8 UCB50H 4PT4S0000C 00050 6 15A UCB50L 2PT4S0000C 00015 8 UCB50L 3PT4S0000C 00015 8 UCB50L 4PT4S0000C 00015 6 16A UCB50L 2PT4S0000C 00016 8 UCB50L 3PT4S0000C 00016 8 UCB50L 4PT4S0000C 00016 6 20A UCB50L 2PT4S0000C 00020 8 UCB50L 3PT4S0000C 00020 8 UCB50L 4PT4S0000C 00020 6 UCB50L 25A UCB50L 2PT4S0000C 00025 8 UCB50L 3PT4S0000C 00025 8 UCB50L 4PT4S0000C 00025 6 50kA 30A UCB50L 2PT4S0000C 00030 8 UCB50L 3PT4S0000C 00030 8 UCB50L 4PT4S0000C 00030 6 32A UCB50L 2PT4S0000C 00032 8 UCB50L 3PT4S0000C 00032 8 UCB50L 4PT4S0000C 00032 6 40A UCB50L 2PT4S0000C 00040 8 UCB50L 3PT4S0000C 00040 8 UCB50L 4PT4S0000C 00040 6 50A UCB50L 2PT4S0000C 00050 8 UCB50L 3PT4S0000C 00050 8 UCB50L 4PT4S0000C 00050 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ 54 Model / Breaking capacity at AC380/415V Rated current 2 pole 3 pole 4 pole Code Unit (EA) Code Unit (EA) 15A UCB50H 2PT5S0000C 00015 8 UCB50H 3PT5S0000C 00015 8 UCB50H 4PT5S0000C 00015 6 16A UCB50H 2PT5S0000C 00016 8 UCB50H 3PT5S0000C 00016 8 UCB50H 4PT5S0000C 00016 6 20A UCB50H 2PT5S0000C 00020 8 UCB50H 3PT5S0000C 00020 8 UCB50H 4PT5S0000C 00020 6 UCB50H 25A UCB50H 2PT5S0000C 00025 8 UCB50H 3PT5S0000C 00025 8 UCB50H 4PT5S0000C 00025 6 42kA 30A UCB50H 2PT5S0000C 00030 8 UCB50H 3PT5S0000C 00030 8 UCB50H 4PT5S0000C 00030 6 32A UCB50H 2PT5S0000C 00032 8 UCB50H 3PT5S0000C 00032 8 UCB50H 4PT5S0000C 00032 6 40A UCB50H 2PT5S0000C 00040 8 UCB50H 3PT5S0000C 00040 8 UCB50H 4PT5S0000C 00040 6 50A UCB50H 2PT5S0000C 00050 8 UCB50H 3PT5S0000C 00050 8 UCB50H 4PT5S0000C 00050 6 15A UCB50L 2PT5S0000C 00015 8 UCB50L 3PT5S0000C 00015 8 UCB50L 4PT5S0000C 00015 6 16A UCB50L 2PT5S0000C 00016 8 UCB50L 3PT5S0000C 00016 8 UCB50L 4PT5S0000C 00016 6 20A UCB50L 2PT5S0000C 00020 8 UCB50L 3PT5S0000C 00020 8 UCB50L 4PT5S0000C 00020 6 UCB50L 25A UCB50L 2PT5S0000C 00025 8 UCB50L 3PT5S0000C 00025 8 UCB50L 4PT5S0000C 00025 6 Code Unit (EA) 50kA 30A UCB50L 2PT5S0000C 00030 8 UCB50L 3PT5S0000C 00030 8 UCB50L 4PT5S0000C 00030 6 32A UCB50L 2PT5S0000C 00032 8 UCB50L 3PT5S0000C 00032 8 UCB50L 4PT5S0000C 00032 6 40A UCB50L 2PT5S0000C 00040 8 UCB50L 3PT5S0000C 00040 8 UCB50L 4PT5S0000C 00040 6 50A UCB50L 2PT5S0000C 00050 8 UCB50L 3PT5S0000C 00050 8 UCB50L 4PT5S0000C 00050 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 MCCB •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current 15A UCB50H 2PT4S0000C 00015F 8 UCB50H 3PT4S0000C 00015F 8 UCB50H 4PT4S0000C 00015F 6 16A UCB50H 2PT4S0000C 00016F 8 UCB50H 3PT4S0000C 00016F 8 UCB50H 4PT4S0000C 00016F 6 20A UCB50H 2PT4S0000C 00020F 8 UCB50H 3PT4S0000C 00020F 8 UCB50H 4PT4S0000C 00020F 6 UCB50H 25A UCB50H 2PT4S0000C 00025F 8 UCB50H 3PT4S0000C 00025F 8 UCB50H 4PT4S0000C 00025F 6 42kA 30A UCB50H 2PT4S0000C 00030F 8 UCB50H 3PT4S0000C 00030F 8 UCB50H 4PT4S0000C 00030F 6 32A UCB50H 2PT4S0000C 00032F 8 UCB50H 3PT4S0000C 00032F 8 UCB50H 4PT4S0000C 00032F 6 40A UCB50H 2PT4S0000C 00040F 8 UCB50H 3PT4S0000C 00040F 8 UCB50H 4PT4S0000C 00040F 6 50A UCB50H 2PT4S0000C 00050F 8 UCB50H 3PT4S0000C 00050F 8 UCB50H 4PT4S0000C 00050F 6 15A UCB50L 2PT4S0000C 00015F 8 UCB50L 3PT4S0000C 00015F 8 UCB50L 4PT4S0000C 00015F 6 16A UCB50L 2PT4S0000C 00016F 8 UCB50L 3PT4S0000C 00016F 8 UCB50L 4PT4S0000C 00016F 6 20A UCB50L 2PT4S0000C 00020F 8 UCB50L 3PT4S0000C 00020F 8 UCB50L 4PT4S0000C 00020F 6 UCB50L 25A UCB50L 2PT4S0000C 00025F 8 UCB50L 3PT4S0000C 00025F 8 UCB50L 4PT4S0000C 00025F 6 2 pole Code 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) 50kA 30A UCB50L 2PT4S0000C 00030F 8 UCB50L 3PT4S0000C 00030F 8 UCB50L 4PT4S0000C 00030F 6 32A UCB50L 2PT4S0000C 00032F 8 UCB50L 3PT4S0000C 00032F 8 UCB50L 4PT4S0000C 00032F 6 40A UCB50L 2PT4S0000C 00040F 8 UCB50L 3PT4S0000C 00040F 8 UCB50L 4PT4S0000C 00040F 6 50A UCB50L 2PT4S0000C 00050F 8 UCB50L 3PT4S0000C 00050F 8 UCB50L 4PT4S0000C 00050F 6 3 pole 4 pole Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V Rated current 15A 16A UCB50H 2PT5S0000C 00016F 8 UCB50H 3PT5S0000C 00016F 8 UCB50H 4PT5S0000C 00016F 6 20A UCB50H 2PT5S0000C 00020F 8 UCB50H 3PT5S0000C 00020F 8 UCB50H 4PT5S0000C 00020F 6 UCB50H 25A UCB50H 2PT5S0000C 00025F 8 UCB50H 3PT5S0000C 00025F 8 UCB50H 4PT5S0000C 00025F 6 42kA 30A UCB50H 2PT5S0000C 00030F 8 UCB50H 3PT5S0000C 00030F 8 UCB50H 4PT5S0000C 00030F 6 32A UCB50H 2PT5S0000C 00032F 8 UCB50H 3PT5S0000C 00032F 8 UCB50H 4PT5S0000C 00032F 6 40A UCB50H 2PT5S0000C 00040F 8 UCB50H 3PT5S0000C 00040F 8 UCB50H 4PT5S0000C 00040F 6 50A UCB50H 2PT5S0000C 00050F 8 UCB50H 3PT5S0000C 00050F 8 UCB50H 4PT5S0000C 00050F 6 15A UCB50L 2PT5S0000C 00015F 8 UCB50L 3PT5S0000C 00015F 8 UCB50L 4PT5S0000C 00015F 6 16A UCB50L 2PT5S0000C 00016F 8 UCB50L 3PT5S0000C 00016F 8 UCB50L 4PT5S0000C 00016F 6 20A UCB50L 2PT5S0000C 00020F 8 UCB50L 3PT5S0000C 00020F 8 UCB50L 4PT5S0000C 00020F 6 UCB50L 25A UCB50L 2PT5S0000C 00025F 8 UCB50L 3PT5S0000C 00025F 8 UCB50L 4PT5S0000C 00025F 6 2 pole Code Unit (EA) UCB50H 2PT5S0000C 00015F 8 Code Unit (EA) UCB50H 3PT5S0000C 00015F 8 Code Unit (EA) UCB50H 4PT5S0000C 00015F 6 50kA 30A UCB50L 2PT5S0000C 00030F 8 UCB50L 3PT5S0000C 00030F 8 UCB50L 4PT5S0000C 00030F 6 32A UCB50L 2PT5S0000C 00032F 8 UCB50L 3PT5S0000C 00032F 8 UCB50L 4PT5S0000C 00032F 6 40A UCB50L 2PT5S0000C 00040F 8 UCB50L 3PT5S0000C 00040F 8 UCB50L 4PT5S0000C 00040F 6 50A UCB50L 2PT5S0000C 00050F 8 UCB50L 3PT5S0000C 00050F 8 UCB50L 4PT5S0000C 00050F 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Molded Case Circuit Breaker_ 55 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 100AF | •UCB100R 30/25kA •UCB100S 42/36kA UCB100R UCB100S Number of poles (P) Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection Rated current (A) 2, 3, 4 overload, inst., short-circuit 15,16,20,25,30,32,40,50,60,63,75,80,100,125 Rated insulation voltage [Ui] (V) Rating AC690 AC660 Rated operational voltage [Ue] (V) DC250 Rated impulse withstand voltage [Uimp] (kV) 6 AC600/660V, 50-60Hz 10 18 Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) AC480/500V, 50-60Hz 14 25 AC440/460V, 50-60Hz 25 35 AC380/415V, 50-60Hz 30/25 42/36 AC220/240V, 50-60Hz 50 65 IEC 60947-2 K 60947-2 DC250V 14 18 DC125V 20 25 Service [Ics] % of [Icu] 75 ○ Fixed thermal, Trip Fixed instantaneous INST 10×In mechanism Thermal magnetic & Protection LTD (0.8-0.9-1)×In Adjustable thermal, characteristics Fixed instantaneous INST 10×In Direct mounting by screw ○ Mounting Plug-in Both line & load side ○1) for Switchboard Line side only ○1) for Distribution board ○1) Terminal connection Screw ○ Durability (times) Mechanical operation 25,000 Electrical operation a 10,000 a d c b Dimensions 2/3/4P b (mm) c Width 60/90/120 Height 155 Depth 60 d 84.5 Weight (kg, breaker only) 0.7/1.0/1.2 2/3/4P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 56 MCCB ■ Accessories •Signal 1C, left-hand-side Auxiliary switch AUX 10B L1 1C, left-hand-side Trip alarm switch Shunt trip ALT 10B L1 1) Under voltage trip 2) DC24V DC100-110V SHT 10B A - AC100-120V AC200-230V DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V UVT 10B J UVT 10B L UVT 10B N UVT 10B P UVT 10B Q UVT 10B R SHT 10B F AC380-415V AC440-480V SHT 10B H ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. •Operating Upper Right Left S type TFG 10BS U4 TFG 10BS R4 TFG 10BS L4 L type TFG 10BL U4 - TFG 10BL L4 Power supply direction Operating Surface handle1) Extended S type TFH 10BS L type TFH 10BL Motor operator 2) DC24V AC/DC110V AC/DC220V MOT 10UB DC24 MOT 10UB ADC110 MOT 10UB ADC220 2 pole 3 pole 4 pole - MIF 10UF 3 MIF 10UF 4 PLD 10UF Mechanical interlock Padlock plate 3) ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting For both line & load side For line side only TDM 10BP TDM 10BF Connection 2C contact CBM 10AB 2 - block 2) CBM 10AB 3 - CBM BARR - Structure Mounting base Plug-in 1) 3C contact Conn. block barrier ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. •Terminal 3EA/SET4EA/SET Cage terminal block CTB 10B 3S Terminal cover1) Interpole barrier2) 2EA/SET CTB 10B 4S 2 pole 3 pole 4 pole TCF 10BP 2 TCF 10BP 3 TCF 10BP 4 TQQ 10B 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA Molded Case Circuit Breaker_ 57 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UCB100R 30/25kA UCB100S 42/36kA 2 pole 3 pole Rated current Code Unit (EA) Code Unit (EA) 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A UCB100R 2PT4S0000C 00015 UCB100R 2PT4S0000C 00016 UCB100R 2PT4S0000C 00020 UCB100R 2PT4S0000C 00025 UCB100R 2PT4S0000C 00030 UCB100R 2PT4S0000C 00032 UCB100R 2PT4S0000C 00040 UCB100R 2PT4S0000C 00050 UCB100R 2PT4S0000C 00060 UCB100R 2PT4S0000C 00063 UCB100R 2PT4S0000C 00075 UCB100R 2PT4S0000C 00080 UCB100R 2PT4S0000C 00100 UCB100R 2PT4S0000C 00125 UCB100S 2PT4S0000C 00015 UCB100S 2PT4S0000C 00016 UCB100S 2PT4S0000C 00020 UCB100S 2PT4S0000C 00025 UCB100S 2PT4S0000C 00030 UCB100S 2PT4S0000C 00032 UCB100S 2PT4S0000C 00040 UCB100S 2PT4S0000C 00050 UCB100S 2PT4S0000C 00060 UCB100S 2PT4S0000C 00063 UCB100S 2PT4S0000C 00075 UCB100S 2PT4S0000C 00080 UCB100S 2PT4S0000C 00100 UCB100S 2PT4S0000C 00125 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 UCB100R 3PT4S0000C 00015 UCB100R 3PT4S0000C 00016 UCB100R 3PT4S0000C 00020 UCB100R 3PT4S0000C 00025 UCB100R 3PT4S0000C 00030 UCB100R 3PT4S0000C 00032 UCB100R 3PT4S0000C 00040 UCB100R 3PT4S0000C 00050 UCB100R 3PT4S0000C 00060 UCB100R 3PT4S0000C 00063 UCB100R 3PT4S0000C 00075 UCB100R 3PT4S0000C 00080 UCB100R 3PT4S0000C 00100 UCB100R 3PT4S0000C 00125 UCB100S 3PT4S0000C 00015 UCB100S 3PT4S0000C 00016 UCB100S 3PT4S0000C 00020 UCB100S 3PT4S0000C 00025 UCB100S 3PT4S0000C 00030 UCB100S 3PT4S0000C 00032 UCB100S 3PT4S0000C 00040 UCB100S 3PT4S0000C 00050 UCB100S 3PT4S0000C 00060 UCB100S 3PT4S0000C 00063 UCB100S 3PT4S0000C 00075 UCB100S 3PT4S0000C 00080 UCB100S 3PT4S0000C 00100 UCB100S 3PT4S0000C 00125 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Rated current Code Unit (EA) Code Unit (EA) 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A UCB100R 2PT5S0000C 00015 UCB100R 2PT5S0000C 00016 UCB100R 2PT5S0000C 00020 UCB100R 2PT5S0000C 00025 UCB100R 2PT5S0000C 00030 UCB100R 2PT5S0000C 00032 UCB100R 2PT5S0000C 00040 UCB100R 2PT5S0000C 00050 UCB100R 2PT5S0000C 00060 UCB100R 2PT5S0000C 00063 UCB100R 2PT5S0000C 00075 UCB100R 2PT5S0000C 00080 UCB100R 2PT5S0000C 00100 UCB100R 2PT5S0000C 00125 UCB100S 2PT5S0000C 00015 UCB100S 2PT5S0000C 00016 UCB100S 2PT5S0000C 00020 UCB100S 2PT5S0000C 00025 UCB100S 2PT5S0000C 00030 UCB100S 2PT5S0000C 00032 UCB100S 2PT5S0000C 00040 UCB100S 2PT5S0000C 00050 UCB100S 2PT5S0000C 00060 UCB100S 2PT5S0000C 00063 UCB100S 2PT5S0000C 00075 UCB100S 2PT5S0000C 00080 UCB100S 2PT5S0000C 00100 UCB100S 2PT5S0000C 00125 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 UCB100R 3PT5S0000C 00015 UCB100R 3PT5S0000C 00016 UCB100R 3PT5S0000C 00020 UCB100R 3PT5S0000C 00025 UCB100R 3PT5S0000C 00030 UCB100R 3PT5S0000C 00032 UCB100R 3PT5S0000C 00040 UCB100R 3PT5S0000C 00050 UCB100R 3PT5S0000C 00060 UCB100R 3PT5S0000C 00063 UCB100R 3PT5S0000C 00075 UCB100R 3PT5S0000C 00080 UCB100R 3PT5S0000C 00100 UCB100R 3PT5S0000C 00125 UCB100S 3PT5S0000C 00015 UCB100S 3PT5S0000C 00016 UCB100S 3PT5S0000C 00020 UCB100S 3PT5S0000C 00025 UCB100S 3PT5S0000C 00030 UCB100S 3PT5S0000C 00032 UCB100S 3PT5S0000C 00040 UCB100S 3PT5S0000C 00050 UCB100S 3PT5S0000C 00060 UCB100S 3PT5S0000C 00063 UCB100S 3PT5S0000C 00075 UCB100S 3PT5S0000C 00080 UCB100S 3PT5S0000C 00100 UCB100S 3PT5S0000C 00125 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 4 pole Code UCB100R 4PT4S0000C 00015 UCB100R 4PT4S0000C 00016 UCB100R 4PT4S0000C 00020 UCB100R 4PT4S0000C 00025 UCB100R 4PT4S0000C 00030 UCB100R 4PT4S0000C 00032 UCB100R 4PT4S0000C 00040 UCB100R 4PT4S0000C 00050 UCB100R 4PT4S0000C 00060 UCB100R 4PT4S0000C 00063 UCB100R 4PT4S0000C 00075 UCB100R 4PT4S0000C 00080 UCB100R 4PT4S0000C 00100 UCB100R 4PT4S0000C 00125 UCB100S 4PT4S0000C 00015 UCB100S 4PT4S0000C 00016 UCB100S 4PT4S0000C 00020 UCB100S 4PT4S0000C 00025 UCB100S 4PT4S0000C 00030 UCB100S 4PT4S0000C 00032 UCB100S 4PT4S0000C 00040 UCB100S 4PT4S0000C 00050 UCB100S 4PT4S0000C 00060 UCB100S 4PT4S0000C 00063 UCB100S 4PT4S0000C 00075 UCB100S 4PT4S0000C 00080 UCB100S 4PT4S0000C 00100 UCB100S 4PT4S0000C 00125 Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UCB100R 30/25kA UCB100S 42/36kA 58 2 pole 3 pole 4 pole Code UCB100R 4PT5S0000C 00015 UCB100R 4PT5S0000C 00016 UCB100R 4PT5S0000C 00020 UCB100R 4PT5S0000C 00025 UCB100R 4PT5S0000C 00030 UCB100R 4PT5S0000C 00032 UCB100R 4PT5S0000C 00040 UCB100R 4PT5S0000C 00050 UCB100R 4PT5S0000C 00060 UCB100R 4PT5S0000C 00063 UCB100R 4PT5S0000C 00075 UCB100R 4PT5S0000C 00080 UCB100R 4PT5S0000C 00100 UCB100R 4PT5S0000C 00125 UCB100S 4PT5S0000C 00015 UCB100S 4PT5S0000C 00016 UCB100S 4PT5S0000C 00020 UCB100S 4PT5S0000C 00025 UCB100S 4PT5S0000C 00030 UCB100S 4PT5S0000C 00032 UCB100S 4PT5S0000C 00040 UCB100S 4PT5S0000C 00050 UCB100S 4PT5S0000C 00060 UCB100S 4PT5S0000C 00063 UCB100S 4PT5S0000C 00075 UCB100S 4PT5S0000C 00080 UCB100S 4PT5S0000C 00100 UCB100S 4PT5S0000C 00125 Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 MCCB •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UCB100R 30/25kA UCB100S 42/36kA 2 pole 3 pole 4 pole Rated current Code Unit (EA) Code Unit (EA) Code Unit (EA) 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A UCB100R 2PT4S0000C 00015F UCB100R 2PT4S0000C 00016F UCB100R 2PT4S0000C 00020F UCB100R 2PT4S0000C 00025F UCB100R 2PT4S0000C 00030F UCB100R 2PT4S0000C 00032F UCB100R 2PT4S0000C 00040F UCB100R 2PT4S0000C 00050F UCB100R 2PT4S0000C 00060F UCB100R 2PT4S0000C 00063F UCB100R 2PT4S0000C 00075F UCB100R 2PT4S0000C 00080F UCB100R 2PT4S0000C 00100F UCB100R 2PT4S0000C 00125F UCB100S 2PT4S0000C 00015F UCB100S 2PT4S0000C 00016F UCB100S 2PT4S0000C 00020F UCB100S 2PT4S0000C 00025F UCB100S 2PT4S0000C 00030F UCB100S 2PT4S0000C 00032F UCB100S 2PT4S0000C 00040F UCB100S 2PT4S0000C 00050F UCB100S 2PT4S0000C 00060F UCB100S 2PT4S0000C 00063F UCB100S 2PT4S0000C 00075F UCB100S 2PT4S0000C 00080F UCB100S 2PT4S0000C 00100F UCB100S 2PT4S0000C 00125F 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 UCB100R 3PT4S0000C 00015F UCB100R 3PT4S0000C 00016F UCB100R 3PT4S0000C 00020F UCB100R 3PT4S0000C 00025F UCB100R 3PT4S0000C 00030F UCB100R 3PT4S0000C 00032F UCB100R 3PT4S0000C 00040F UCB100R 3PT4S0000C 00050F UCB100R 3PT4S0000C 00060F UCB100R 3PT4S0000C 00063F UCB100R 3PT4S0000C 00075F UCB100R 3PT4S0000C 00080F UCB100R 3PT4S0000C 00100F UCB100R 3PT4S0000C 00125F UCB100S 3PT4S0000C 00015F UCB100S 3PT4S0000C 00016F UCB100S 3PT4S0000C 00020F UCB100S 3PT4S0000C 00025F UCB100S 3PT4S0000C 00030F UCB100S 3PT4S0000C 00032F UCB100S 3PT4S0000C 00040F UCB100S 3PT4S0000C 00050F UCB100S 3PT4S0000C 00060F UCB100S 3PT4S0000C 00063F UCB100S 3PT4S0000C 00075F UCB100S 3PT4S0000C 00080F UCB100S 3PT4S0000C 00100F UCB100S 3PT4S0000C 00125F 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 UCB100R 4PT4S0000C 00015F UCB100R 4PT4S0000C 00016F UCB100R 4PT4S0000C 00020F UCB100R 4PT4S0000C 00025F UCB100R 4PT4S0000C 00030F UCB100R 4PT4S0000C 00032F UCB100R 4PT4S0000C 00040F UCB100R 4PT4S0000C 00050F UCB100R 4PT4S0000C 00060F UCB100R 4PT4S0000C 00063F UCB100R 4PT4S0000C 00075F UCB100R 4PT4S0000C 00080F UCB100R 4PT4S0000C 00100F UCB100R 4PT4S0000C 00125F UCB100S 4PT4S0000C 00015F UCB100S 4PT4S0000C 00016F UCB100S 4PT4S0000C 00020F UCB100S 4PT4S0000C 00025F UCB100S 4PT4S0000C 00030F UCB100S 4PT4S0000C 00032F UCB100S 4PT4S0000C 00040F UCB100S 4PT4S0000C 00050F UCB100S 4PT4S0000C 00060F UCB100S 4PT4S0000C 00063F UCB100S 4PT4S0000C 00075F UCB100S 4PT4S0000C 00080F UCB100S 4PT4S0000C 00100F UCB100S 4PT4S0000C 00125F 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Rated current Code Unit (EA) Code Unit (EA) Code Unit (EA) 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A UCB100R 2PT5S0000C 00015F UCB100R 2PT5S0000C 00016F UCB100R 2PT5S0000C 00020F UCB100R 2PT5S0000C 00025F UCB100R 2PT5S0000C 00030F UCB100R 2PT5S0000C 00032F UCB100R 2PT5S0000C 00040F UCB100R 2PT5S0000C 00050F UCB100R 2PT5S0000C 00060F UCB100R 2PT5S0000C 00063F UCB100R 2PT5S0000C 00075F UCB100R 2PT5S0000C 00080F UCB100R 2PT5S0000C 00100F UCB100R 2PT5S0000C 00125F UCB100S 2PT5S0000C 00015F UCB100S 2PT5S0000C 00016F UCB100S 2PT5S0000C 00020F UCB100S 2PT5S0000C 00025F UCB100S 2PT5S0000C 00030F UCB100S 2PT5S0000C 00032F UCB100S 2PT5S0000C 00040F UCB100S 2PT5S0000C 00050F UCB100S 2PT5S0000C 00060F UCB100S 2PT5S0000C 00063F UCB100S 2PT5S0000C 00075F UCB100S 2PT5S0000C 00080F UCB100S 2PT5S0000C 00100F UCB100S 2PT5S0000C 00125F 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 UCB100R 3PT5S0000C 00015F UCB100R 3PT5S0000C 00016F UCB100R 3PT5S0000C 00020F UCB100R 3PT5S0000C 00025F UCB100R 3PT5S0000C 00030F UCB100R 3PT5S0000C 00032F UCB100R 3PT5S0000C 00040F UCB100R 3PT5S0000C 00050F UCB100R 3PT5S0000C 00060F UCB100R 3PT5S0000C 00063F UCB100R 3PT5S0000C 00075F UCB100R 3PT5S0000C 00080F UCB100R 3PT5S0000C 00100F UCB100R 3PT5S0000C 00125F UCB100S 3PT5S0000C 00015F UCB100S 3PT5S0000C 00016F UCB100S 3PT5S0000C 00020F UCB100S 3PT5S0000C 00025F UCB100S 3PT5S0000C 00030F UCB100S 3PT5S0000C 00032F UCB100S 3PT5S0000C 00040F UCB100S 3PT5S0000C 00050F UCB100S 3PT5S0000C 00060F UCB100S 3PT5S0000C 00063F UCB100S 3PT5S0000C 00075F UCB100S 3PT5S0000C 00080F UCB100S 3PT5S0000C 00100F UCB100S 3PT5S0000C 00125F 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 UCB100R 4PT5S0000C 00015F UCB100R 4PT5S0000C 00016F UCB100R 4PT5S0000C 00020F UCB100R 4PT5S0000C 00025F UCB100R 4PT5S0000C 00030F UCB100R 4PT5S0000C 00032F UCB100R 4PT5S0000C 00040F UCB100R 4PT5S0000C 00050F UCB100R 4PT5S0000C 00060F UCB100R 4PT5S0000C 00063F UCB100R 4PT5S0000C 00075F UCB100R 4PT5S0000C 00080F UCB100R 4PT5S0000C 00100F UCB100R 4PT5S0000C 00125F UCB100S 4PT5S0000C 00015F UCB100S 4PT5S0000C 00016F UCB100S 4PT5S0000C 00020F UCB100S 4PT5S0000C 00025F UCB100S 4PT5S0000C 00030F UCB100S 4PT5S0000C 00032F UCB100S 4PT5S0000C 00040F UCB100S 4PT5S0000C 00050F UCB100S 4PT5S0000C 00060F UCB100S 4PT5S0000C 00063F UCB100S 4PT5S0000C 00075F UCB100S 4PT5S0000C 00080F UCB100S 4PT5S0000C 00100F UCB100S 4PT5S0000C 00125F 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UCB100R 30/25kA UCB100S 42/36kA 2 pole 3 pole 4 pole Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Molded Case Circuit Breaker_ 59 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 125AF | •UCB100H 42kA •UCB100L 50kA UCB100H UCB100L Number of poles (P) ✽2, 3, 4 Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection overload, inst., short-circuit Rated current (A) 15,16,20,25,30,32,40,50,60,63,75,80,100,125 Rated insulation voltage [Ui] (V) AC690 Rating AC660 Rated operational voltage [Ue] (V) DC250 Rated impulse withstand voltage [Uimp] (kV) 6 AC600/660V, 50-60Hz 20 25 Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) IEC 60947-2 K 60947-2 AC480/500V, 50-60Hz 30 35 AC440/460V, 50-60Hz 42 50 AC380/415V, 50-60Hz 42 50 AC220/240V, 50-60Hz 85 100 DC250V 25 40 DC125V 40 60 Service [Ics] % of [Icu] 75 ○ Fixed thermal, Trip Fixed instantaneous INST 15-32A: 15×In, 40-125A: 10×In Thermal mechanism & Protection magnetic LTD (0.8-0.9-1)×In Adjustable thermal, characteristics Fixed instantaneous INST 15-32A: 15×In, 40-125A: 10×In Direct mounting by screw ○ Mounting Plug-in Both line & load side ○1) for Switchboard Line side only ○1) for Distribution board ○1) Terminal connection Screw ○ Durability (times) Mechanical operation 25,000 Electrical operation a 10,000 a d c b Dimensions 2/3/4P b (mm) c Width 902)/90/120 Height 155 Depth 60 d 84.5 Weight (kg, breaker only) 0.9/1.0/1.3 2/3/4P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. 60 MCCB ■ Accessories •Signal 1C, left-hand-side Auxiliary switch Trip alarm switch Shunt trip 1) Under voltage trip2) 2C, left-hand-side AUX 12FG L1 AUX 12FG L2 1C, right-hand-side 1C, left-hand-side ALT 12FG R1 ALT 12FG L1 DC24V DC100-110V AC100-120V AC200-230V AC380-415V SHT 12FG A SHT 12FG C SHT 12FG F SHT 12FG H SHT 12FG B SHT 12FG D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V UVT 12FG J UVT 12FG L UVT 12FG N UVT 12FG P UVT 12FG Q UVT 12FG R AC440-480V ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. •Operating Upper Right Left S type TFG 10UFS U4 TFG 10UFS R4 TFG 10UFS L4 L type TFG 10UFL U4 - TFG 10UFL L4 Power supply direction Operating Surface handle1) Extended S type L type Motor operator 2) TFH 10UFS TFH 10UFL DC24V AC/DC110V AC/DC220V MOT 10F DC24 MOT 10F ADC110 MOT 10F ADC220 Mechanical interlock 2 pole 3 pole 4 pole MIF 10UF 3 MIF 10UF 3 MIF 10UF 4 Padlock plate3) PLD 10UF ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting For both line & load side For line side only TDM 10BP TDM 10BF Plug-in1) Connection 2C contact CBM 10AB 2 - 3C contact CBM 10AB 3 - CBM BARR - Structure Mounting base block 2) Conn. block barrier ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. •Terminal 3EA/SET4EA/SET Cage terminal block CTB 10B 3S Terminal cover1) Interpole barrier2) 2EA/SET CTB 10B 4S 2 pole 3 pole 4 pole TCF 10FP 3 TCF 10FP 3 TCF 10FP 4 TQQ 12FG 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA Molded Case Circuit Breaker_ 61 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UCB100H 42kA UCB100L 50kA Rated current 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 2 pole Code UCB100H 2PT4S0000C 00015 UCB100H 2PT4S0000C 00016 UCB100H 2PT4S0000C 00020 UCB100H 2PT4S0000C 00025 UCB100H 2PT4S0000C 00030 UCB100H 2PT4S0000C 00032 UCB100H 2PT4S0000C 00040 UCB100H 2PT4S0000C 00050 UCB100H 2PT4S0000C 00060 UCB100H 2PT4S0000C 00063 UCB100H 2PT4S0000C 00075 UCB100H 2PT4S0000C 00080 UCB100H 2PT4S0000C 00100 UCB100H 2PT4S0000C 00125 UCB100L 2PT4S0000C 00015 UCB100L 2PT4S0000C 00016 UCB100L 2PT4S0000C 00020 UCB100L 2PT4S0000C 00025 UCB100L 2PT4S0000C 00030 UCB100L 2PT4S0000C 00032 UCB100L 2PT4S0000C 00040 UCB100L 2PT4S0000C 00050 UCB100L 2PT4S0000C 00060 UCB100L 2PT4S0000C 00063 UCB100L 2PT4S0000C 00075 UCB100L 2PT4S0000C 00080 UCB100L 2PT4S0000C 00100 UCB100L 2PT4S0000C 00125 Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 3 pole Code UCB100H 3PT4S0000C 00015 UCB100H 3PT4S0000C 00016 UCB100H 3PT4S0000C 00020 UCB100H 3PT4S0000C 00025 UCB100H 3PT4S0000C 00030 UCB100H 3PT4S0000C 00032 UCB100H 3PT4S0000C 00040 UCB100H 3PT4S0000C 00050 UCB100H 3PT4S0000C 00060 UCB100H 3PT4S0000C 00063 UCB100H 3PT4S0000C 00075 UCB100H 3PT4S0000C 00080 UCB100H 3PT4S0000C 00100 UCB100H 3PT4S0000C 00125 UCB100L 3PT4S0000C 00015 UCB100L 3PT4S0000C 00016 UCB100L 3PT4S0000C 00020 UCB100L 3PT4S0000C 00025 UCB100L 3PT4S0000C 00030 UCB100L 3PT4S0000C 00032 UCB100L 3PT4S0000C 00040 UCB100L 3PT4S0000C 00050 UCB100L 3PT4S0000C 00060 UCB100L 3PT4S0000C 00063 UCB100L 3PT4S0000C 00075 UCB100L 3PT4S0000C 00080 UCB100L 3PT4S0000C 00100 UCB100L 3PT4S0000C 00125 Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 4 pole Code UCB100H 4PT4S0000C 00015 UCB100H 4PT4S0000C 00016 UCB100H 4PT4S0000C 00020 UCB100H 4PT4S0000C 00025 UCB100H 4PT4S0000C 00030 UCB100H 4PT4S0000C 00032 UCB100H 4PT4S0000C 00040 UCB100H 4PT4S0000C 00050 UCB100H 4PT4S0000C 00060 UCB100H 4PT4S0000C 00063 UCB100H 4PT4S0000C 00075 UCB100H 4PT4S0000C 00080 UCB100H 4PT4S0000C 00100 UCB100H 4PT4S0000C 00125 UCB100L 4PT4S0000C 00015 UCB100L 4PT4S0000C 00016 UCB100L 4PT4S0000C 00020 UCB100L 4PT4S0000C 00025 UCB100L 4PT4S0000C 00030 UCB100L 4PT4S0000C 00032 UCB100L 4PT4S0000C 00040 UCB100L 4PT4S0000C 00050 UCB100L 4PT4S0000C 00060 UCB100L 4PT4S0000C 00063 UCB100L 4PT4S0000C 00075 UCB100L 4PT4S0000C 00080 UCB100L 4PT4S0000C 00100 UCB100L 4PT4S0000C 00125 Unit (EA) 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UCB100H 42kA UCB100L 50kA 62 Rated current 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 2 pole Code UCB100H 2PT5S0000C 00015 UCB100H 2PT5S0000C 00016 UCB100H 2PT5S0000C 00020 UCB100H 2PT5S0000C 00025 UCB100H 2PT5S0000C 00030 UCB100H 2PT5S0000C 00032 UCB100H 2PT5S0000C 00040 UCB100H 2PT5S0000C 00050 UCB100H 2PT5S0000C 00060 UCB100H 2PT5S0000C 00063 UCB100H 2PT5S0000C 00075 UCB100H 2PT5S0000C 00080 UCB100H 2PT5S0000C 00100 UCB100H 2PT5S0000C 00125 UCB100L 2PT5S0000C 00015 UCB100L 2PT5S0000C 00016 UCB100L 2PT5S0000C 00020 UCB100L 2PT5S0000C 00025 UCB100L 2PT5S0000C 00030 UCB100L 2PT5S0000C 00032 UCB100L 2PT5S0000C 00040 UCB100L 2PT5S0000C 00050 UCB100L 2PT5S0000C 00060 UCB100L 2PT5S0000C 00063 UCB100L 2PT5S0000C 00075 UCB100L 2PT5S0000C 00080 UCB100L 2PT5S0000C 00100 UCB100L 2PT5S0000C 00125 Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 3 pole Code UCB100H 3PT5S0000C 00015 UCB100H 3PT5S0000C 00016 UCB100H 3PT5S0000C 00020 UCB100H 3PT5S0000C 00025 UCB100H 3PT5S0000C 00030 UCB100H 3PT5S0000C 00032 UCB100H 3PT5S0000C 00040 UCB100H 3PT5S0000C 00050 UCB100H 3PT5S0000C 00060 UCB100H 3PT5S0000C 00063 UCB100H 3PT5S0000C 00075 UCB100H 3PT5S0000C 00080 UCB100H 3PT5S0000C 00100 UCB100H 3PT5S0000C 00125 UCB100L 3PT5S0000C 00015 UCB100L 3PT5S0000C 00016 UCB100L 3PT5S0000C 00020 UCB100L 3PT5S0000C 00025 UCB100L 3PT5S0000C 00030 UCB100L 3PT5S0000C 00032 UCB100L 3PT5S0000C 00040 UCB100L 3PT5S0000C 00050 UCB100L 3PT5S0000C 00060 UCB100L 3PT5S0000C 00063 UCB100L 3PT5S0000C 00075 UCB100L 3PT5S0000C 00080 UCB100L 3PT5S0000C 00100 UCB100L 3PT5S0000C 00125 Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 4 pole Code UCB100H 4PT5S0000C 00015 UCB100H 4PT5S0000C 00016 UCB100H 4PT5S0000C 00020 UCB100H 4PT5S0000C 00025 UCB100H 4PT5S0000C 00030 UCB100H 4PT5S0000C 00032 UCB100H 4PT5S0000C 00040 UCB100H 4PT5S0000C 00050 UCB100H 4PT5S0000C 00060 UCB100H 4PT5S0000C 00063 UCB100H 4PT5S0000C 00075 UCB100H 4PT5S0000C 00080 UCB100H 4PT5S0000C 00100 UCB100H 4PT5S0000C 00125 UCB100L 4PT5S0000C 00015 UCB100L 4PT5S0000C 00016 UCB100L 4PT5S0000C 00020 UCB100L 4PT5S0000C 00025 UCB100L 4PT5S0000C 00030 UCB100L 4PT5S0000C 00032 UCB100L 4PT5S0000C 00040 UCB100L 4PT5S0000C 00050 UCB100L 4PT5S0000C 00060 UCB100L 4PT5S0000C 00063 UCB100L 4PT5S0000C 00075 UCB100L 4PT5S0000C 00080 UCB100L 4PT5S0000C 00100 UCB100L 4PT5S0000C 00125 Unit (EA) 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 MCCB •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UCB100H 42kA UCB100L 50kA Rated current 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 2 pole Code UCB100H 2PT4S0000C 00015F UCB100H 2PT4S0000C 00016F UCB100H 2PT4S0000C 00020F UCB100H 2PT4S0000C 00025F UCB100H 2PT4S0000C 00030F UCB100H 2PT4S0000C 00032F UCB100H 2PT4S0000C 00040F UCB100H 2PT4S0000C 00050F UCB100H 2PT4S0000C 00060F UCB100H 2PT4S0000C 00063F UCB100H 2PT4S0000C 00075F UCB100H 2PT4S0000C 00080F UCB100H 2PT4S0000C 00100F UCB100H 2PT4S0000C 00125F UCB100L 2PT4S0000C 00015F UCB100L 2PT4S0000C 00016F UCB100L 2PT4S0000C 00020F UCB100L 2PT4S0000C 00025F UCB100L 2PT4S0000C 00030F UCB100L 2PT4S0000C 00032F UCB100L 2PT4S0000C 00040F UCB100L 2PT4S0000C 00050F UCB100L 2PT4S0000C 00060F UCB100L 2PT4S0000C 00063F UCB100L 2PT4S0000C 00075F UCB100L 2PT4S0000C 00080F UCB100L 2PT4S0000C 00100F UCB100L 2PT4S0000C 00125F Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 3 pole Code UCB100H 3PT4S0000C 00015F UCB100H 3PT4S0000C 00016F UCB100H 3PT4S0000C 00020F UCB100H 3PT4S0000C 00025F UCB100H 3PT4S0000C 00030F UCB100H 3PT4S0000C 00032F UCB100H 3PT4S0000C 00040F UCB100H 3PT4S0000C 00050F UCB100H 3PT4S0000C 00060F UCB100H 3PT4S0000C 00063F UCB100H 3PT4S0000C 00075F UCB100H 3PT4S0000C 00080F UCB100H 3PT4S0000C 00100F UCB100H 3PT4S0000C 00125F UCB100L 3PT4S0000C 00015F UCB100L 3PT4S0000C 00016F UCB100L 3PT4S0000C 00020F UCB100L 3PT4S0000C 00025F UCB100L 3PT4S0000C 00030F UCB100L 3PT4S0000C 00032F UCB100L 3PT4S0000C 00040F UCB100L 3PT4S0000C 00050F UCB100L 3PT4S0000C 00060F UCB100L 3PT4S0000C 00063F UCB100L 3PT4S0000C 00075F UCB100L 3PT4S0000C 00080F UCB100L 3PT4S0000C 00100F UCB100L 3PT4S0000C 00125F Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 4 pole Code UCB100H 4PT4S0000C 00015F UCB100H 4PT4S0000C 00016F UCB100H 4PT4S0000C 00020F UCB100H 4PT4S0000C 00025F UCB100H 4PT4S0000C 00030F UCB100H 4PT4S0000C 00032F UCB100H 4PT4S0000C 00040F UCB100H 4PT4S0000C 00050F UCB100H 4PT4S0000C 00060F UCB100H 4PT4S0000C 00063F UCB100H 4PT4S0000C 00075F UCB100H 4PT4S0000C 00080F UCB100H 4PT4S0000C 00100F UCB100H 4PT4S0000C 00125F UCB100L 4PT4S0000C 00015F UCB100L 4PT4S0000C 00016F UCB100L 4PT4S0000C 00020F UCB100L 4PT4S0000C 00025F UCB100L 4PT4S0000C 00030F UCB100L 4PT4S0000C 00032F UCB100L 4PT4S0000C 00040F UCB100L 4PT4S0000C 00050F UCB100L 4PT4S0000C 00060F UCB100L 4PT4S0000C 00063F UCB100L 4PT4S0000C 00075F UCB100L 4PT4S0000C 00080F UCB100L 4PT4S0000C 00100F UCB100L 4PT4S0000C 00125F Unit (EA) 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UCB100H 42kA UCB100L 50kA Rated current 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 2 pole Code UCB100H 2PT5S0000C 00015F UCB100H 2PT5S0000C 00016F UCB100H 2PT5S0000C 00020F UCB100H 2PT5S0000C 00025F UCB100H 2PT5S0000C 00030F UCB100H 2PT5S0000C 00032F UCB100H 2PT5S0000C 00040F UCB100H 2PT5S0000C 00050F UCB100H 2PT5S0000C 00060F UCB100H 2PT5S0000C 00063F UCB100H 2PT5S0000C 00075F UCB100H 2PT5S0000C 00080F UCB100H 2PT5S0000C 00100F UCB100H 2PT5S0000C 00125F UCB100L 2PT5S0000C 00015F UCB100L 2PT5S0000C 00016F UCB100L 2PT5S0000C 00020F UCB100L 2PT5S0000C 00025F UCB100L 2PT5S0000C 00030F UCB100L 2PT5S0000C 00032F UCB100L 2PT5S0000C 00040F UCB100L 2PT5S0000C 00050F UCB100L 2PT5S0000C 00060F UCB100L 2PT5S0000C 00063F UCB100L 2PT5S0000C 00075F UCB100L 2PT5S0000C 00080F UCB100L 2PT5S0000C 00100F UCB100L 2PT5S0000C 00125F Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 3 pole Code UCB100H 3PT5S0000C 00015F UCB100H 3PT5S0000C 00016F UCB100H 3PT5S0000C 00020F UCB100H 3PT5S0000C 00025F UCB100H 3PT5S0000C 00030F UCB100H 3PT5S0000C 00032F UCB100H 3PT5S0000C 00040F UCB100H 3PT5S0000C 00050F UCB100H 3PT5S0000C 00060F UCB100H 3PT5S0000C 00063F UCB100H 3PT5S0000C 00075F UCB100H 3PT5S0000C 00080F UCB100H 3PT5S0000C 00100F UCB100H 3PT5S0000C 00125F UCB100L 3PT5S0000C 00015F UCB100L 3PT5S0000C 00016F UCB100L 3PT5S0000C 00020F UCB100L 3PT5S0000C 00025F UCB100L 3PT5S0000C 00030F UCB100L 3PT5S0000C 00032F UCB100L 3PT5S0000C 00040F UCB100L 3PT5S0000C 00050F UCB100L 3PT5S0000C 00060F UCB100L 3PT5S0000C 00063F UCB100L 3PT5S0000C 00075F UCB100L 3PT5S0000C 00080F UCB100L 3PT5S0000C 00100F UCB100L 3PT5S0000C 00125F Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 4 pole Code UCB100H 4PT5S0000C 00015F UCB100H 4PT5S0000C 00016F UCB100H 4PT5S0000C 00020F UCB100H 4PT5S0000C 00025F UCB100H 4PT5S0000C 00030F UCB100H 4PT5S0000C 00032F UCB100H 4PT5S0000C 00040F UCB100H 4PT5S0000C 00050F UCB100H 4PT5S0000C 00060F UCB100H 4PT5S0000C 00063F UCB100H 4PT5S0000C 00075F UCB100H 4PT5S0000C 00080F UCB100H 4PT5S0000C 00100F UCB100H 4PT5S0000C 00125F UCB100L 4PT5S0000C 00015F UCB100L 4PT5S0000C 00016F UCB100L 4PT5S0000C 00020F UCB100L 4PT5S0000C 00025F UCB100L 4PT5S0000C 00030F UCB100L 4PT5S0000C 00032F UCB100L 4PT5S0000C 00040F UCB100L 4PT5S0000C 00050F UCB100L 4PT5S0000C 00060F UCB100L 4PT5S0000C 00063F UCB100L 4PT5S0000C 00075F UCB100L 4PT5S0000C 00080F UCB100L 4PT5S0000C 00100F UCB100L 4PT5S0000C 00125F Unit (EA) 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Molded Case Circuit Breaker_ 63 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 160AF | •UCB160H 42kA •UCB160L 50kA UCB160H UCB160L ✽2, 3, 4 Number of poles (P) IP20 Degree of protection (with terminal cover) A Utilization category ○ Suitability of isolation overload, inst., short-circuit Protection 100,125,160 Rated current (A) AC690 Rated insulation voltage [Ui] (V) AC660 Rating Rated operational voltage [Ue] (V) DC250 Rated impulse withstand voltage [Uimp] (kV) 6 20 25 AC600/660V, 50-60Hz Rated AC480/500V, 50-60Hz 30 35 short-circuit Ultimate AC440/460V, 50-60Hz 42 50 breaking [Icu] AC380/415V, 50-60Hz 42 50 capacity (kA r.m.s.) AC220/240V, 50-60Hz 85 100 DC250V 25 40 IEC 60947-2 K 60947-2 DC125V 40 60 Service [Ics] % of [Icu] 50 Fixed thermal, ○ Trip Fixed instantaneous INST Thermal mechanism 10×In & Protection magnetic LTD Adjustable thermal, (0.8-0.9-1)×In characteristics Fixed instantaneous INST 10×In Direct mounting by screw ○ Both line & load side ○1) for Mounting Switchboard Plug-in Line side only ○1) for Distribution board ○1) Screw ○ Terminal connection Bus bar ○ Mechanical operation 25,000 Durability (times) Electrical operation 10,000 a Width 1052)/105/140 d a c b Height 165 Dimensions 2/3/4P b (mm) c Depth 60 d 84.5 1.1/1.3/1.6 Weight (kg, breaker only) 2/3/4P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip1) Under voltage trip2) 64 1C, left-hand-side AUX 12FG L1 1C, right-hand-side ALT 12FG R1 DC24V SHT 12FG A DC24V UVT 12FG J 2C, leftt-hand-side AUX 12FG L2 1C, left-hand-side ALT 12FG L1 DC100-110V SHT 12FG C DC100-110V UVT 12FG L AC100-120V SHT 12FG F AC100-120V UVT 12FG N ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. AC200-230V SHT 12FG H AC200-230V UVT 12FG P AC380-415V SHT 12FG B AC380-415V UVT 12FG Q AC440-480V SHT 12FG D AC440-480V UVT 12FG R MCCB •Operating Right Left TFG 20UGS R4 TFG 20UGS L4 TFG 20UGL L4 TFH 20UGS TFH 20UGL AC/DC110V AC/DC220V Motor operator 2) MOT 20G ADC110 MOT 20G ADC220 3 pole 4 pole Mechanical interlock MIF 20UG 3 MIF 20UG 4 3) Padlock plate PLD 20UG ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. Operating handle1) Power supply direction S type Surface L type S type Extended L type Upper TFG 20UGS U4 TFG 20UGL U4 DC24V MOT 20G DC24 2 pole MIF 20UG 3 •Mounting Plug-in1) Structure Mounting base Connection 2C contact 5C contact block2) For both line & load side TDM 20CF3) CBM 20C 2 CBM 20C 5 For line side only TDM 20CF - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 3) 2EA are required for both line & load side plug-in type 3P breaker. •Terminal Terminal bus bar Cage terminal block Terminal cover 1) Interpole barrier 2) 2EA/SET 2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET) TBB 20C 2 TBB 20C 3 TBB 20C 4 3EA/SET4EA/SET CTB 20C 3S CTB 20C 4S 2 pole 3 pole 4 pole TCF 20GP 3 TCF 20GP 3 TCF 20GP 4 TQQ 12FG 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UCB160H 42kA UCB160L 50kA 2 pole Code Rated current 100A 125A 160A 100A 125A 160A UCB160H 2PT4S0000C 00100 UCB160H 2PT4S0000C 00125 UCB160H 2PT4S0000C 00160 UCB160L 2PT4S0000C 00100 UCB160L 2PT4S0000C 00125 UCB160L 2PT4S0000C 00160 Rated current 100A 125A 160A 100A 125A 160A 2 pole Code UCB160H 2PT5S0000C 00100 UCB160H 2PT5S0000C 00125 UCB160H 2PT5S0000C 00160 UCB160L 2PT5S0000C 00100 UCB160L 2PT5S0000C 00125 UCB160L 2PT5S0000C 00160 Unit (EA) 8 8 8 8 8 8 3 pole Code UCB160H 3PT4S0000C 00100 UCB160H 3PT4S0000C 00125 UCB160H 3PT4S0000C 00160 UCB160L 3PT4S0000C 00100 UCB160L 3PT4S0000C 00125 UCB160L 3PT4S0000C 00160 Unit (EA) 8 8 8 8 8 8 4 pole Code UCB160H 4PT4S0000C 00100 UCB160H 4PT4S0000C 00125 UCB160H 4PT4S0000C 00160 UCB160L 4PT4S0000C 00100 UCB160L 4PT4S0000C 00125 UCB160L 4PT4S0000C 00160 Unit Specification (EA) 6 6 6 6 6 6 Screw type terminal connection, No option, 50/60Hz Category MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UCB160H 42kA UCB160L 50kA Unit (EA) 8 8 8 8 8 8 3 pole Unit Code (EA) UCB160H 3PT5S0000C 00100 8 UCB160H 3PT5S0000C 00125 8 UCB160H 3PT5S0000C 00160 8 UCB160L 3PT5S0000C 00100 8 UCB160L 3PT5S0000C 00125 8 UCB160L 3PT5S0000C 00160 8 4 pole Code UCB160H 4PT5S0000C 00100 UCB160H 4PT5S0000C 00125 UCB160H 4PT5S0000C 00160 UCB160L 4PT5S0000C 00100 UCB160L 4PT5S0000C 00125 UCB160L 4PT5S0000C 00160 Unit Specification (EA) 6 6 6 6 6 6 Screw type terminal connection, No option, 50/60Hz Category MCCB /M2 •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UCB160H 42kA UCB160L 50kA Rated current 100A 125A 160A 100A 125A 160A 2 pole Unit Code (EA) UCB160H 2PT4S0000C 00100F 8 UCB160H 2PT4S0000C 00125F 8 UCB160H 2PT4S0000C 00160F 8 UCB160L 2PT4S0000C 00100F 8 UCB160L 2PT4S0000C 00125F 8 UCB160L 2PT4S0000C 00160F 8 Rated current 100A 125A 160A 100A 125A 160A 2 pole 3 pole 4 pole Unit Unit Unit Specification Category Code Code Code (EA) (EA) (EA) UCB160H 2PT5S0000C 00100F 8 UCB160H 3PT5S0000C 00100F 8 UCB160H 4PT5S0000C 00100F 6 UCB160H 2PT5S0000C 00125F 8 UCB160H 3PT5S0000C 00125F 8 UCB160H 4PT5S0000C 00125F 6 Screw type terminal UCB160H 2PT5S0000C 00160F 8 UCB160H 3PT5S0000C 00160F 8 UCB160H 4PT5S0000C 00160F 6 MCCB connection, UCB160L 2PT5S0000C 00100F 8 UCB160L 3PT5S0000C 00100F 8 UCB160L 4PT5S0000C 00100F 6 /M2 No option, UCB160L 2PT5S0000C 00125F 8 UCB160L 3PT5S0000C 00125F 8 UCB160L 4PT5S0000C 00125F 6 50/60Hz UCB160L 2PT5S0000C 00160F 8 UCB160L 3PT5S0000C 00160F 8 UCB160L 4PT5S0000C 00160F 6 50℃ Model / Breaking capacity at AC380/415V UCB160H 42kA UCB160L 50kA 3 pole Code UCB160H 3PT4S0000C 00100F UCB160H 3PT4S0000C 00125F UCB160H 3PT4S0000C 00160F UCB160L 3PT4S0000C 00100F UCB160L 3PT4S0000C 00125F UCB160L 3PT4S0000C 00160F Unit (EA) 8 8 8 8 8 8 4 pole Code UCB160H 4PT4S0000C 00100F UCB160H 4PT4S0000C 00125F UCB160H 4PT4S0000C 00160F UCB160L 4PT4S0000C 00100F UCB160L 4PT4S0000C 00125F UCB160L 4PT4S0000C 00160F Unit Specification (EA) 6 6 6 6 6 6 Screw type terminal connection, No option, 50/60Hz Category MCCB /M2 Molded Case Circuit Breaker_ 65 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 250AF | •UCB250R 25/18kA •UCB250S 35/25kA •UCB250N 42/36kA UCB250R UCB250S Number of poles (P) ✽2, 3, 4 Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection overload, inst., short-circuit Rated current (A) 125,150,160,175,200,225,250 Rated insulation voltage [Ui] (V) AC690 AC660 DC250 Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) 6 AC600/660V, 50-60Hz 7.5 10 18 Rated Ultimate short-circuit AC480/500V, 50-60Hz 10 14 25 AC440/460V, 50-60Hz 18 25 35 breaking [Icu] capacity (kA r.m.s.) AC380/415V, 50-60Hz 25/18 35/25 42/36 AC220/240V, 50-60Hz 35 50 65 IEC 60947-2 K 60947-2 DC250V 10 14 18 DC125V 15 20 25 Service [Ics] % of [Icu] 50 Fixed thermal, Trip Fixed instantaneous INST mechanism Thermal magnetic & Protection LTD Adjustable thermal, characteristics Fixed instantaneous INST ○ Direct mounting by screw 10×In (0.8-0.9-1)×In 10×In ○ Mounting Plug-in Both line & load side for Switchboard Line side only ○1) for Distribution board ○1) Screw ○ Bus bar ○ Terminal connection Durability (times) ○1) Mechanical operation 25,000 Electrical operation 10,000 a d c a b Dimensions 2/3/4P b (mm) c Width 1052)/105/140 Height 164 Depth 60 d 84 Weight (kg, breaker only) 2/3/4P 1.1/1.2/1.5 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed. 66 UCB250N MCCB ■ Accessories •Signal 1C, left-hand-side Auxiliary switch AUX 20C L1 1C, left-hand-side Trip alarm switch ALT 20C L1 Shunt trip 1) Under voltage trip 2) DC24V DC100-110V SHT 20C A - AC100-120V AC200-230V DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V UVT 20C J UVT 20C L UVT 20C N UVT 20C P UVT 20C Q UVT 20C R SHT 20C F AC380-415V AC440-480V SHT 20C H ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. •Operating Upper Right Left TFG 20CS U4 TFG 20CS R4 TFG 20CS L4 - TFG 20CL L4 Power supply direction Operating Surface handle1) Extended S type TFG 20CL U4 L type S type L type Motor operator 2) TFH 20CS TFH 20CL DC24V AC/DC110V AC/DC220V MOT 20UC DC24 MOT 20UC ADC110 MOT 20UC ADC220 2 pole 3 pole 4 pole MIF 20UG 3 MIF 20UG 3 MIF 20UG 4 Mechanical interlock Padlock plate 3) PLD 20UG ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting For both line & load side For line side only Mounting base TDM 20CF 3) TDM 20CF Connection 2C contact CBM 20C 2 - block CBM 20C 5 - Structure Plug-in1) 2) 5C contact ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 3) 2EA are required for both line & load side plug-in type 3P breaker. •Terminal 2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET) Terminal bus bar TBB 20C 2 Cage terminal block Terminal cover CTB 20C 3S 1) Interpole barrier 2) TBB 20C 3 TBB 20C 4 3EA/SET4EA/SET 2EA/SET CTB 20C 4S 2 pole 3 pole 4 pole TCF 20CP 3 TCF 20CP 3 TCF 20CP 4 TQQ 20C 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA Molded Case Circuit Breaker_ 67 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current UCB250R 25/18kA UCB250S 35/25kA UCB250N 42/36kA 100A 125A 150A 160A 175A 200A 225A 250A 100A 125A 150A 160A 175A 200A 225A 250A 100A 125A 150A 160A 175A 200A 225A 250A 2 pole Code UCB250R 2PT4S0000C 00100 UCB250R 2PT4S0000C 00125 UCB250R 2PT4S0000C 00150 UCB250R 2PT4S0000C 00160 UCB250R 2PT4S0000C 00175 UCB250R 2PT4S0000C 00200 UCB250R 2PT4S0000C 00225 UCB250R 2PT4S0000C 00250 UCB250S 2PT4S0000C 00100 UCB250S 2PT4S0000C 00125 UCB250S 2PT4S0000C 00150 UCB250S 2PT4S0000C 00160 UCB250S 2PT4S0000C 00175 UCB250S 2PT4S0000C 00200 UCB250S 2PT4S0000C 00225 UCB250S 2PT4S0000C 00250 UCB250N 2PT4S0000C 00100 UCB250N 2PT4S0000C 00125 UCB250N 2PT4S0000C 00150 UCB250N 2PT4S0000C 00160 UCB250N 2PT4S0000C 00175 UCB250N 2PT4S0000C 00200 UCB250N 2PT4S0000C 00225 UCB250N 2PT4S0000C 00250 Unit (EA) 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 3 pole Code UCB250R 3PT4S0000C 00100 UCB250R 3PT4S0000C 00125 UCB250R 3PT4S0000C 00150 UCB250R 3PT4S0000C 00160 UCB250R 3PT4S0000C 00175 UCB250R 3PT4S0000C 00200 UCB250R 3PT4S0000C 00225 UCB250R 3PT4S0000C 00250 UCB250S 3PT4S0000C 00100 UCB250S 3PT4S0000C 00125 UCB250S 3PT4S0000C 00150 UCB250S 3PT4S0000C 00160 UCB250S 3PT4S0000C 00175 UCB250S 3PT4S0000C 00200 UCB250S 3PT4S0000C 00225 UCB250S 3PT4S0000C 00250 UCB250N 3PT4S0000C 00100 UCB250N 3PT4S0000C 00125 UCB250N 3PT4S0000C 00150 UCB250N 3PT4S0000C 00160 UCB250N 3PT4S0000C 00175 UCB250N 3PT4S0000C 00200 UCB250N 3PT4S0000C 00225 UCB250N 3PT4S0000C 00250 Unit (EA) 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 4 pole Code UCB250R 4PT4S0000C 00100 UCB250R 4PT4S0000C 00125 UCB250R 4PT4S0000C 00150 UCB250R 4PT4S0000C 00160 UCB250R 4PT4S0000C 00175 UCB250R 4PT4S0000C 00200 UCB250R 4PT4S0000C 00225 UCB250R 4PT4S0000C 00250 UCB250S 4PT4S0000C 00100 UCB250S 4PT4S0000C 00125 UCB250S 4PT4S0000C 00150 UCB250S 4PT4S0000C 00160 UCB250S 4PT4S0000C 00175 UCB250S 4PT4S0000C 00200 UCB250S 4PT4S0000C 00225 UCB250S 4PT4S0000C 00250 UCB250N 4PT4S0000C 00100 UCB250N 4PT4S0000C 00125 UCB250N 4PT4S0000C 00150 UCB250N 4PT4S0000C 00160 UCB250N 4PT4S0000C 00175 UCB250N 4PT4S0000C 00200 UCB250N 4PT4S0000C 00225 UCB250N 4PT4S0000C 00250 Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UCB250R 25/18kA UCB250S 35/25kA UCB250N 42/36kA 68 Rated current 100A 125A 150A 160A 175A 200A 225A 250A 100A 125A 150A 160A 175A 200A 225A 250A 100A 125A 150A 160A 175A 200A 225A 250A 2 pole Code UCB250R 2PT5S0000C 00100 UCB250R 2PT5S0000C 00125 UCB250R 2PT5S0000C 00150 UCB250R 2PT5S0000C 00160 UCB250R 2PT5S0000C 00175 UCB250R 2PT5S0000C 00200 UCB250R 2PT5S0000C 00225 UCB250R 2PT5S0000C 00250 UCB250S 2PT5S0000C 00100 UCB250S 2PT5S0000C 00125 UCB250S 2PT5S0000C 00150 UCB250S 2PT5S0000C 00160 UCB250S 2PT5S0000C 00175 UCB250S 2PT5S0000C 00200 UCB250S 2PT5S0000C 00225 UCB250S 2PT5S0000C 00250 UCB250N 2PT5S0000C 00100 UCB250N 2PT5S0000C 00125 UCB250N 2PT5S0000C 00150 UCB250N 2PT5S0000C 00160 UCB250N 2PT5S0000C 00175 UCB250N 2PT5S0000C 00200 UCB250N 2PT5S0000C 00225 UCB250N 2PT5S0000C 00250 Unit (EA) 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 3 pole Code UCB250R 3PT5S0000C 00100 UCB250R 3PT5S0000C 00125 UCB250R 3PT5S0000C 00150 UCB250R 3PT5S0000C 00160 UCB250R 3PT5S0000C 00175 UCB250R 3PT5S0000C 00200 UCB250R 3PT5S0000C 00225 UCB250R 3PT5S0000C 00250 UCB250S 3PT5S0000C 00100 UCB250S 3PT5S0000C 00125 UCB250S 3PT5S0000C 00150 UCB250S 3PT5S0000C 00160 UCB250S 3PT5S0000C 00175 UCB250S 3PT5S0000C 00200 UCB250S 3PT5S0000C 00225 UCB250S 3PT5S0000C 00250 UCB250N 3PT5S0000C 00100 UCB250N 3PT5S0000C 00125 UCB250N 3PT5S0000C 00150 UCB250N 3PT5S0000C 00160 UCB250N 3PT5S0000C 00175 UCB250N 3PT5S0000C 00200 UCB250N 3PT5S0000C 00225 UCB250N 3PT5S0000C 00250 Unit (EA) 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 4 pole Code UCB250R 4PT5S0000C 00100 UCB250R 4PT5S0000C 00125 UCB250R 4PT5S0000C 00150 UCB250R 4PT5S0000C 00160 UCB250R 4PT5S0000C 00175 UCB250R 4PT5S0000C 00200 UCB250R 4PT5S0000C 00225 UCB250R 4PT5S0000C 00250 UCB250S 4PT5S0000C 00100 UCB250S 4PT5S0000C 00125 UCB250S 4PT5S0000C 00150 UCB250S 4PT5S0000C 00160 UCB250S 4PT5S0000C 00175 UCB250S 4PT5S0000C 00200 UCB250S 4PT5S0000C 00225 UCB250S 4PT5S0000C 00250 UCB250N 4PT5S0000C 00100 UCB250N 4PT5S0000C 00125 UCB250N 4PT5S0000C 00150 UCB250N 4PT5S0000C 00160 UCB250N 4PT5S0000C 00175 UCB250N 4PT5S0000C 00200 UCB250N 4PT5S0000C 00225 UCB250N 4PT5S0000C 00250 Unit (EA) Specification Category 8 8 8 8 8 8 8 8 8 8 8 Screw type terminal 8 connection, 8 No option, 8 50/60Hz 8 8 8 8 8 8 8 8 8 8 MCCB /M2 MCCB •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UCB250R 25/18kA UCB250S 35/25kA UCB250N 42/36kA Rated current 2 pole Code Unit (EA) 3 pole Code Unit (EA) 4 pole Code Unit (EA) 125A UCB250R 2PT4S0000C 00125F 10 UCB250R 3PT4S0000C 00125F 10 UCB250R 4PT4S0000C 00125F 8 150A UCB250R 2PT4S0000C 00150F 10 UCB250R 3PT4S0000C 00150F 10 UCB250R 4PT4S0000C 00150F 8 160A UCB250R 2PT4S0000C 00160F 10 UCB250R 3PT4S0000C 00160F 10 UCB250R 4PT4S0000C 00160F 8 175A UCB250R 2PT4S0000C 00175F 10 UCB250R 3PT4S0000C 00175F 10 UCB250R 4PT4S0000C 00175F 8 200A UCB250R 2PT4S0000C 00200F 10 UCB250R 3PT4S0000C 00200F 10 UCB250R 4PT4S0000C 00200F 8 225A UCB250R 2PT4S0000C 00225F 10 UCB250R 3PT4S0000C 00225F 10 UCB250R 4PT4S0000C 00225F 8 250A UCB250R 2PT4S0000C 00250F 10 UCB250R 3PT4S0000C 00250F 10 UCB250R 4PT4S0000C 00250F 8 125A UCB250S 2PT4S0000C 00125F 8 10 UCB250S 3PT4S0000C 00125F 10 UCB250S 4PT4S0000C 00125F 150A UCB250S 2PT4S0000C 00150F 10 UCB250S 3PT4S0000C 00150F 10 UCB250S 4PT4S0000C 00150F 8 160A UCB250S 2PT4S0000C 00160F 10 UCB250S 3PT4S0000C 00160F 10 UCB250S 4PT4S0000C 00160F 8 175A UCB250S 2PT4S0000C 00175F 10 UCB250S 3PT4S0000C 00175F 10 UCB250S 4PT4S0000C 00175F 8 200A UCB250S 2PT4S0000C 00200F 10 UCB250S 3PT4S0000C 00200F 10 UCB250S 4PT4S0000C 00200F 8 225A UCB250S 2PT4S0000C 00225F 10 UCB250S 3PT4S0000C 00225F 10 UCB250S 4PT4S0000C 00225F 8 250A UCB250S 2PT4S0000C 00250F 10 UCB250S 3PT4S0000C 00250F 10 UCB250S 4PT4S0000C 00250F 8 125A UCB250N 2PT4S0000C 00125F 10 UCB250N 3PT4S0000C 00125F 10 UCB250N 4PT4S0000C 00125F 8 150A UCB250N 2PT4S0000C 00150F 10 UCB250N 3PT4S0000C 00150F 10 UCB250N 4PT4S0000C 00150F 8 160A UCB250N 2PT4S0000C 00160F 10 UCB250N 3PT4S0000C 00160F 10 UCB250N 4PT4S0000C 00160F 8 175A UCB250N 2PT4S0000C 00175F 10 UCB250N 3PT4S0000C 00175F 10 UCB250N 4PT4S0000C 00175F 8 200A UCB250N 2PT4S0000C 00200F 10 UCB250N 3PT4S0000C 00200F 10 UCB250N 4PT4S0000C 00200F 8 225A UCB250N 2PT4S0000C 00225F 10 UCB250N 3PT4S0000C 00225F 10 UCB250N 4PT4S0000C 00225F 8 250A UCB250N 2PT4S0000C 00250F 10 UCB250N 3PT4S0000C 00250F 10 UCB250N 4PT4S0000C 00250F 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UCB250R 25/18kA UCB250S 35/25kA UCB250N 42/36kA Rated current 2 pole Code Unit (EA) 3 pole Code Unit (EA) 4 pole Code Unit (EA) 125A UCB250R 2PT5S0000C 00125F 10 UCB250R 3PT5S0000C 00125F 10 UCB250R 4PT5S0000C 00125F 8 150A UCB250R 2PT5S0000C 00150F 10 UCB250R 3PT5S0000C 00150F 10 UCB250R 4PT5S0000C 00150F 8 160A UCB250R 2PT5S0000C 00160F 10 UCB250R 3PT5S0000C 00160F 10 UCB250R 4PT5S0000C 00160F 8 175A UCB250R 2PT5S0000C 00175F 10 UCB250R 3PT5S0000C 00175F 10 UCB250R 4PT5S0000C 00175F 8 200A UCB250R 2PT5S0000C 00200F 10 UCB250R 3PT5S0000C 00200F 10 UCB250R 4PT5S0000C 00200F 8 225A UCB250R 2PT5S0000C 00225F 10 UCB250R 3PT5S0000C 00225F 10 UCB250R 4PT5S0000C 00225F 8 250A UCB250R 2PT5S0000C 00250F 10 UCB250R 3PT5S0000C 00250F 10 UCB250R 4PT5S0000C 00250F 8 125A UCB250S 2PT5S0000C 00125F 10 UCB250S 3PT5S0000C 00125F 10 UCB250S 4PT5S0000C 00125F 8 150A UCB250S 2PT5S0000C 00150F 10 UCB250S 3PT5S0000C 00150F 10 UCB250S 4PT5S0000C 00150F 8 160A UCB250S 2PT5S0000C 00160F 10 UCB250S 3PT5S0000C 00160F 10 UCB250S 4PT5S0000C 00160F 8 175A UCB250S 2PT5S0000C 00175F 10 UCB250S 3PT5S0000C 00175F 10 UCB250S 4PT5S0000C 00175F 8 200A UCB250S 2PT5S0000C 00200F 10 UCB250S 3PT5S0000C 00200F 10 UCB250S 4PT5S0000C 00200F 8 225A UCB250S 2PT5S0000C 00225F 10 UCB250S 3PT5S0000C 00225F 10 UCB250S 4PT5S0000C 00225F 8 250A UCB250S 2PT5S0000C 00250F 10 UCB250S 3PT5S0000C 00250F 10 UCB250S 4PT5S0000C 00250F 8 125A UCB250N 2PT5S0000C 00125F 10 UCB250N 3PT5S0000C 00125F 10 UCB250N 4PT5S0000C 00125F 8 150A UCB250N 2PT5S0000C 00150F 10 UCB250N 3PT5S0000C 00150F 10 UCB250N 4PT5S0000C 00150F 8 160A UCB250N 2PT5S0000C 00160F 10 UCB250N 3PT5S0000C 00160F 10 UCB250N 4PT5S0000C 00160F 8 175A UCB250N 2PT5S0000C 00175F 10 UCB250N 3PT5S0000C 00175F 10 UCB250N 4PT5S0000C 00175F 8 200A UCB250N 2PT5S0000C 00200F 10 UCB250N 3PT5S0000C 00200F 10 UCB250N 4PT5S0000C 00200F 8 225A UCB250N 2PT5S0000C 00225F 10 UCB250N 3PT5S0000C 00225F 10 UCB250N 4PT5S0000C 00225F 8 250A UCB250N 2PT5S0000C 00250F 10 UCB250N 3PT5S0000C 00250F 10 UCB250N 4PT5S0000C 00250F 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Molded Case Circuit Breaker_ 69 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 250AF | •UCB250H 42kA •UCB250L 50kA UCB250H UCB250L Number of poles (P) ✽2, 3, 4 Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection overload, inst., short-circuit Rated current (A) 125,150,160,175,200,225,250 Rated insulation voltage [Ui] (V) AC690 AC660 Rating Rated operational voltage [Ue] (V) DC250 Rated impulse withstand voltage [Uimp] (kV) 6 AC600/660V, 50-60Hz 20 25 Rated Ultimate short-circuit breaking [Icu] capacity (kA r.m.s.) AC480/500V, 50-60Hz 30 35 AC440/460V, 50-60Hz 42 50 AC380/415V, 50-60Hz 42 50 AC220/240V, 50-60Hz 85 100 IEC 60947-2 K 60947-2 DC250V 25 40 DC125V 40 60 Service [Ics] % of [Icu] 50 ○ Fixed thermal, Trip Fixed instantaneous INST mechanism 10×In Thermal & Protection magnetic LTD Adjustable thermal, (0.8-0.9-1)×In characteristics Fixed instantaneous INST 10×In Direct mounting by screw ○ Mounting Plug-in Both line & load side ○1) for Switchboard Line side only ○1) for Distribution board ○1) Screw ○ Bus bar ○ Terminal connection Durability (times) Mechanical operation 25,000 Electrical operation a d c a b Dimensions 2/3/4P b (mm) c 10,000 Width 1052)/105/140 Height 165 Depth 60 d 84.5 Weight (kg, breaker only) 1.1/1.3/1.6 2/3/4P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. 70 MCCB ■ Accessories •Signal Auxiliary switch 1C, left-hand-side 2C, left-hand-side AUX 12FG L1 AUX 12FG L2 1C, right-hand-side 1C, left-hand-side Trip alarm switch Shunt trip 1) Under voltage trip 2) ALT 12FG R1 ALT 12FG L1 DC24V DC100-110V AC100-120V AC200-230V AC380-415V SHT 12FG A SHT 12FG C SHT 12FG F SHT 12FG H SHT 12FG B SHT 12FG D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V UVT 12FG J UVT 12FG L UVT 12FG N UVT 12FG P UVT 12FG Q UVT 12FG R AC440-480V ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. •Operating Upper Right Left TFG 20UGS U4 TFG 20UGS R4 TFG 20UGS L4 - TFG 20UGL L4 Power supply direction Operating Surface handle1) Extended S type TFG 20UGL U4 L type S type L type Motor operator 2) TFH 20UGS TFH 20UGL DC24V AC/DC110V AC/DC220V MOT 20G DC24 MOT 20G ADC110 MOT 20G ADC220 2 pole 3 pole 4 pole MIF 20UG 3 MIF 20UG 3 MIF 20UG 4 Mechanical interlock Padlock plate3) PLD 20UG ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting For both line & load side For line side only Mounting base TDM 20CF 3) TDM 20CF Connection 2C contact CBM 20C 2 - block 2) CBM 20C 5 - Structure Plug-in1) 5C contact ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 3) 2EA are required for both line & load side plug-in type 3P breaker. •Terminal 2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET) Terminal bus bar TBB 20C 2 TBB 20C 4 3EA/SET4EA/SET Cage terminal block CTB 20C 3S Terminal cover 1) Interpole barrier 2) TBB 20C 3 2EA/SET CTB 20C 4S 2 pole 3 pole 4 pole TCF 20GP 3 TCF 20GP 3 TCF 20GP 4 TQQ 12FG 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA Molded Case Circuit Breaker_ 71 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UCB250H 42kA UCB250L 50kA Rated current 2 pole Code 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) 125A UCB250H 2PT4S0000C 00125 8 UCB250H 3PT4S0000C 00125 8 UCB250H 4PT4S0000C 00125 6 150A UCB250H 2PT4S0000C 00150 8 UCB250H 3PT4S0000C 00150 8 UCB250H 4PT4S0000C 00150 6 160A UCB250H 2PT4S0000C 00160 8 UCB250H 3PT4S0000C 00160 8 UCB250H 4PT4S0000C 00160 6 175A UCB250H 2PT4S0000C 00175 8 UCB250H 3PT4S0000C 00175 8 UCB250H 4PT4S0000C 00175 6 200A UCB250H 2PT4S0000C 00200 8 UCB250H 3PT4S0000C 00200 8 UCB250H 4PT4S0000C 00200 6 225A UCB250H 2PT4S0000C 00225 8 UCB250H 3PT4S0000C 00225 8 UCB250H 4PT4S0000C 00225 6 250A UCB250H 2PT4S0000C 00250 8 UCB250H 3PT4S0000C 00250 8 UCB250H 4PT4S0000C 00250 6 125A UCB250L 2PT4S0000C 00125 8 UCB250L 3PT4S0000C 00125 8 UCB250L 4PT4S0000C 00125 6 150A UCB250L 2PT4S0000C 00150 8 UCB250L 3PT4S0000C 00150 8 UCB250L 4PT4S0000C 00150 6 160A UCB250L 2PT4S0000C 00160 8 UCB250L 3PT4S0000C 00160 8 UCB250L 4PT4S0000C 00160 6 175A UCB250L 2PT4S0000C 00175 8 UCB250L 3PT4S0000C 00175 8 UCB250L 4PT4S0000C 00175 6 200A UCB250L 2PT4S0000C 00200 8 UCB250L 3PT4S0000C 00200 8 UCB250L 4PT4S0000C 00200 6 225A UCB250L 2PT4S0000C 00225 8 UCB250L 3PT4S0000C 00225 8 UCB250L 4PT4S0000C 00225 6 250A UCB250L 2PT4S0000C 00250 8 UCB250L 3PT4S0000C 00250 8 UCB250L 4PT4S0000C 00250 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V Rated current 125A UCB250H 42kA UCB250L 50kA 72 2 pole 3 pole 4 pole Code Unit (EA) Code Unit (EA) UCB250H 2PT5S0000C 00125 8 UCB250H 3PT5S0000C 00125 8 Code Unit (EA) Specification Category UCB250H 4PT5S0000C 00125 6 150A UCB250H 2PT5S0000C 00150 8 UCB250H 3PT5S0000C 00150 8 UCB250H 4PT5S0000C 00150 6 160A UCB250H 2PT5S0000C 00160 8 UCB250H 3PT5S0000C 00160 8 UCB250H 4PT5S0000C 00160 6 175A UCB250H 2PT5S0000C 00175 8 UCB250H 3PT5S0000C 00175 8 UCB250H 4PT5S0000C 00175 6 200A UCB250H 2PT5S0000C 00200 8 UCB250H 3PT5S0000C 00200 8 UCB250H 4PT5S0000C 00200 6 225A UCB250H 2PT5S0000C 00225 8 UCB250H 3PT5S0000C 00225 8 UCB250H 4PT5S0000C 00225 6 250A UCB250H 2PT5S0000C 00250 8 UCB250H 3PT5S0000C 00250 8 UCB250H 4PT5S0000C 00250 6 125A UCB250L 2PT5S0000C 00125 8 UCB250L 3PT5S0000C 00125 8 UCB250L 4PT5S0000C 00125 6 150A UCB250L 2PT5S0000C 00150 8 UCB250L 3PT5S0000C 00150 8 UCB250L 4PT5S0000C 00150 6 160A UCB250L 2PT5S0000C 00160 8 UCB250L 3PT5S0000C 00160 8 UCB250L 4PT5S0000C 00160 6 175A UCB250L 2PT5S0000C 00175 8 UCB250L 3PT5S0000C 00175 8 UCB250L 4PT5S0000C 00175 6 200A UCB250L 2PT5S0000C 00200 8 UCB250L 3PT5S0000C 00200 8 UCB250L 4PT5S0000C 00200 6 225A UCB250L 2PT5S0000C 00225 8 UCB250L 3PT5S0000C 00225 8 UCB250L 4PT5S0000C 00225 6 250A UCB250L 2PT5S0000C 00250 8 UCB250L 3PT5S0000C 00250 8 UCB250L 4PT5S0000C 00250 6 Screw type terminal connection, No option, 50/60Hz MCCB /M2 MCCB •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UCB250H 42kA UCB250L 50kA Rated current 2 pole 3 pole 4 pole Code Unit (EA) 125A UCB250H 2PT4S0000C 00125F 8 UCB250H 3PT4S0000C 00125F 8 UCB250H 4PT4S0000C 00125F 6 150A UCB250H 2PT4S0000C 00150F 8 UCB250H 3PT4S0000C 00150F 8 UCB250H 4PT4S0000C 00150F 6 160A UCB250H 2PT4S0000C 00160F 8 UCB250H 3PT4S0000C 00160F 8 UCB250H 4PT4S0000C 00160F 6 175A UCB250H 2PT4S0000C 00175F 8 UCB250H 3PT4S0000C 00175F 8 UCB250H 4PT4S0000C 00175F 6 200A UCB250H 2PT4S0000C 00200F 8 UCB250H 3PT4S0000C 00200F 8 UCB250H 4PT4S0000C 00200F 6 225A UCB250H 2PT4S0000C 00225F 8 UCB250H 3PT4S0000C 00225F 8 UCB250H 4PT4S0000C 00225F 6 250A UCB250H 2PT4S0000C 00250F 8 UCB250H 3PT4S0000C 00250F 8 UCB250H 4PT4S0000C 00250F 6 125A UCB250L 2PT4S0000C 00125F 8 UCB250L 3PT4S0000C 00125F 8 UCB250L 4PT4S0000C 00125F 6 150A UCB250L 2PT4S0000C 00150F 8 UCB250L 3PT4S0000C 00150F 8 UCB250L 4PT4S0000C 00150F 6 160A UCB250L 2PT4S0000C 00160F 8 UCB250L 3PT4S0000C 00160F 8 UCB250L 4PT4S0000C 00160F 6 175A UCB250L 2PT4S0000C 00175F 8 UCB250L 3PT4S0000C 00175F 8 UCB250L 4PT4S0000C 00175F 6 200A UCB250L 2PT4S0000C 00200F 8 UCB250L 3PT4S0000C 00200F 8 UCB250L 4PT4S0000C 00200F 6 225A UCB250L 2PT4S0000C 00225F 8 UCB250L 3PT4S0000C 00225F 8 UCB250L 4PT4S0000C 00225F 6 250A UCB250L 2PT4S0000C 00250F 8 UCB250L 3PT4S0000C 00250F 8 UCB250L 4PT4S0000C 00250F 6 Code Unit (EA) Code Unit (EA) Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UCB250H 42kA UCB250L 50kA Rated current 2 pole 3 pole 4 pole Code Unit (EA) Code Unit (EA) 125A UCB250H 2PT5S0000C 00125F 8 UCB250H 3PT5S0000C 00125F 8 UCB250H 4PT5S0000C 00125F 6 150A UCB250H 2PT5S0000C 00150F 8 UCB250H 3PT5S0000C 00150F 8 UCB250H 4PT5S0000C 00150F 6 160A UCB250H 2PT5S0000C 00160F 8 UCB250H 3PT5S0000C 00160F 8 UCB250H 4PT5S0000C 00160F 6 175A UCB250H 2PT5S0000C 00175F 8 UCB250H 3PT5S0000C 00175F 8 UCB250H 4PT5S0000C 00175F 6 200A UCB250H 2PT5S0000C 00200F 8 UCB250H 3PT5S0000C 00200F 8 UCB250H 4PT5S0000C 00200F 6 225A UCB250H 2PT5S0000C 00225F 8 UCB250H 3PT5S0000C 00225F 8 UCB250H 4PT5S0000C 00225F 6 250A UCB250H 2PT5S0000C 00250F 8 UCB250H 3PT5S0000C 00250F 8 UCB250H 4PT5S0000C 00250F 6 125A UCB250L 2PT5S0000C 00125F 8 UCB250L 3PT5S0000C 00125F 8 UCB250L 4PT5S0000C 00125F 6 150A UCB250L 2PT5S0000C 00150F 8 UCB250L 3PT5S0000C 00150F 8 UCB250L 4PT5S0000C 00150F 6 160A UCB250L 2PT5S0000C 00160F 8 UCB250L 3PT5S0000C 00160F 8 UCB250L 4PT5S0000C 00160F 6 175A UCB250L 2PT5S0000C 00175F 8 UCB250L 3PT5S0000C 00175F 8 UCB250L 4PT5S0000C 00175F 6 200A UCB250L 2PT5S0000C 00200F 8 UCB250L 3PT5S0000C 00200F 8 UCB250L 4PT5S0000C 00200F 6 225A UCB250L 2PT5S0000C 00225F 8 UCB250L 3PT5S0000C 00225F 8 UCB250L 4PT5S0000C 00225F 6 250A UCB250L 2PT5S0000C 00250F 8 UCB250L 3PT5S0000C 00250F 8 UCB250L 4PT5S0000C 00250F 6 Code Unit (EA) Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Molded Case Circuit Breaker_ 73 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 400AF | •UCB400R 30kA •UCB400S 42kA •UCB400H 65kA •UCB400L 100kA UCB400R UCB400S UCB400H Number of poles (P) ✽2, 3, 4 Degree of protection (without terminal bus bar) IP20 Utilization category A Suitability of isolation ○ Protection UCB400L overload, inst., short-circuit Rated current (A) 250,300,320,350,400 Rated insulation voltage [Ui] (V) AC690 AC660 Rating Rated operational voltage [Ue] (V) DC250 Rated impulse withstand voltage [Uimp] (kV) 6 AC600/660V, 50-60Hz 18 22 25 30 AC480/500V, 50-60Hz Rated AC440/460V, 50-60Hz short-circuit Ultimate breaking AC380/415V, 50-60Hz [Icu] capacity (kA r.m.s.) AC220/240V, 50-60Hz 18 25 35 65 25 35 50 85 30 42 65 100 35 50 85 125 14 25 40 40 20 30 50 60 IEC 60947-2 DC250V K 60947-2 DC125V Service [Ics] % of [Icu] 50 ○ Fixed thermal, Trip Fixed instantaneous INST 10×In mechanism Thermal & Protection magnetic LTD (0.8-0.9-1)×In Adjustable thermal, characteristics Fixed instantaneous INST 10×In Direct mounting by screw ○ Both line & load side for Plug-in Switchboard Line side only ○1) Screw Terminal connection Bus bar ○ Mounting Durability (times) ○1) ○ Mechanical operation 20,000 Electrical operation a a d c Dimensions b 2/3/4P (mm) 6,000 Width 1402)/140/185 b Height 257 c Depth 110 d 145 Weight (kg, breaker only) 2/3/4P 4/4.5/5.4 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. 74 MCCB ■ Accessories •Signal 1C, right-hand-side Auxiliary switch AUX 46D R1 1C, left-hand-side Trip alarm switch Shunt trip ALT 46D L1 1) Under voltage trip 2) DC24V DC100-110V AC100-120V AC200-230V AC380-415V SHT 46D A SHT 46D C SHT 46D F SHT 46D H SHT 46D B AC440-480V SHT 46D D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V ✽UVT 46D J ✽UVT 46D L ✽UVT 46D N ✽UVT 46D P ✽UVT 46D Q ✽UVT 46D R ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. •Operating Power supply direction Operating Surface S type handle 1) Extended S type Upper Right Left TFG 46DS U4 TFG 46DS R4 TFG 46DS L4 Motor operator 2) AC/DC110V AC/DC220V MOT 40D DC24 MOT 40D ADC110 MOT 40D ADC220 2 pole 3 pole 4 pole MIF 40D 3 MIF 40D 3 MIF 40D 4 Mechanical interlock Padlock plate 3) Extension handle 4) TFH 46DS DC24V PLD 40D THA 46D ※ 1) For detail type information, please refer to page no. 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. 4) Supplied as standard component •Mounting Structure Plug-in 1) Mounting base Connection 2C contact block 2) 5C contact For both line & load side For line side only TDM 4BA 3) TDM 4BA TYA 5/2 4) - TYA 5/5 - 4) ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 3) 2EA are required for both line & load side plug-in type 3P breaker. 4) TYA type connection blocks are to be installed with separate mounting angle. Separate mounting angle is not supplied. •Terminal 2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET) Terminal bus bar TBB 4S 2 Cage terminal block Terminal cover 1) Interpole barrier 2) 2EA/SET TBB 4S 3 TBB 4S 4 3EA/SET 4EA/SET CTB 40D 3S CTB 40D 4S 2 pole 3 pole 4 pole TCF 40D 3 TCF 40D 3 TCF 40D 4 TQQ 4BA 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA Molded Case Circuit Breaker_ 75 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current 2 pole Code Unit (EA) 3 pole Code Unit (EA) 4 pole Code Unit (EA) 250A UCB400R 2PT4S0000C 00250 3 UCB400R 3PT4S0000C 00250 3 UCB400R 4PT4S0000C 00250 2 UCB400R 300A UCB400R 2PT4S0000C 00300 3 UCB400R 3PT4S0000C 00300 3 UCB400R 4PT4S0000C 00300 2 30kA 320A UCB400R 2PT4S0000C 00320 3 UCB400R 3PT4S0000C 00320 3 UCB400R 4PT4S0000C 00320 2 350A UCB400R 2PT4S0000C 00350 3 UCB400R 3PT4S0000C 00350 3 UCB400R 4PT4S0000C 00350 2 400A UCB400R 2PT4S0000C 00400 3 UCB400R 3PT4S0000C 00400 3 UCB400R 4PT4S0000C 00400 2 250A UCB400S 2PT4S0000C 00250 3 UCB400S 3PT4S0000C 00250 3 UCB400S 4PT4S0000C 00250 2 UCB400S 300A UCB400S 2PT4S0000C 00300 3 UCB400S 3PT4S0000C 00300 3 UCB400S 4PT4S0000C 00300 2 320A UCB400S 2PT4S0000C 00320 3 UCB400S 3PT4S0000C 00320 3 UCB400S 4PT4S0000C 00320 2 42kA 350A UCB400S 2PT4S0000C 00350 3 UCB400S 3PT4S0000C 00350 3 UCB400S 4PT4S0000C 00350 2 400A UCB400S 2PT4S0000C 00400 3 UCB400S 3PT4S0000C 00400 3 UCB400S 4PT4S0000C 00400 2 250A UCB400H 2PT4S0000C 00250 3 UCB400H 3PT4S0000C 00250 3 UCB400H 4PT4S0000C 00250 2 UCB400H 300A UCB400H 2PT4S0000C 00300 3 UCB400H 3PT4S0000C 00300 3 UCB400H 4PT4S0000C 00300 2 320A UCB400H 2PT4S0000C 00320 3 UCB400H 3PT4S0000C 00320 3 UCB400H 4PT4S0000C 00320 2 65kA 350A UCB400H 2PT4S0000C 00350 3 UCB400H 3PT4S0000C 00350 3 UCB400H 4PT4S0000C 00350 2 400A UCB400H 2PT4S0000C 00400 3 UCB400H 3PT4S0000C 00400 3 UCB400H 4PT4S0000C 00400 2 250A UCB400L 2PT4S0000C 00250 3 UCB400L 3PT4S0000C 00250 3 UCB400L 4PT4S0000C 00250 2 UCB400L 300A UCB400L 2PT4S0000C 00300 3 UCB400L 3PT4S0000C 00300 3 UCB400L 4PT4S0000C 00300 2 100kA 320A UCB400L 2PT4S0000C 00320 3 UCB400L 3PT4S0000C 00320 3 UCB400L 4PT4S0000C 00320 2 350A UCB400L 2PT4S0000C 00350 3 UCB400L 3PT4S0000C 00350 3 UCB400L 4PT4S0000C 00350 2 400A UCB400L 2PT4S0000C 00400 3 UCB400L 3PT4S0000C 00400 3 UCB400L 4PT4S0000C 00400 2 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V 2 pole Code Unit (EA) 3 pole Code Unit (EA) 4 pole Code Unit (EA) 250A UCB400R 2PT5S0000C 00250 3 UCB400R 3PT5S0000C 00250 3 UCB400R 4PT5S0000C 00250 2 UCB400R 300A UCB400R 2PT5S0000C 00300 3 UCB400R 3PT5S0000C 00300 3 UCB400R 4PT5S0000C 00300 2 320A UCB400R 2PT5S0000C 00320 3 UCB400R 3PT5S0000C 00320 3 UCB400R 4PT5S0000C 00320 2 350A UCB400R 2PT5S0000C 00350 3 UCB400R 3PT5S0000C 00350 3 UCB400R 4PT5S0000C 00350 2 400A UCB400R 2PT5S0000C 00400 3 UCB400R 3PT5S0000C 00400 3 UCB400R 4PT5S0000C 00400 2 250A UCB400S 2PT5S0000C 00250 3 UCB400S 3PT5S0000C 00250 3 UCB400S 4PT5S0000C 00250 2 UCB400S 300A UCB400S 2PT5S0000C 00300 3 UCB400S 3PT5S0000C 00300 3 UCB400S 4PT5S0000C 00300 2 320A UCB400S 2PT5S0000C 00320 3 UCB400S 3PT5S0000C 00320 3 UCB400S 4PT5S0000C 00320 2 350A UCB400S 2PT5S0000C 00350 3 UCB400S 3PT5S0000C 00350 3 UCB400S 4PT5S0000C 00350 2 400A UCB400S 2PT5S0000C 00400 3 UCB400S 3PT5S0000C 00400 3 UCB400S 4PT5S0000C 00400 2 250A UCB400H 2PT5S0000C 00250 3 UCB400H 3PT5S0000C 00250 3 UCB400H 4PT5S0000C 00250 2 UCB400H 300A UCB400H 2PT5S0000C 00300 3 UCB400H 3PT5S0000C 00300 3 UCB400H 4PT5S0000C 00300 2 320A UCB400H 2PT5S0000C 00320 3 UCB400H 3PT5S0000C 00320 3 UCB400H 4PT5S0000C 00320 2 350A UCB400H 2PT5S0000C 00350 3 UCB400H 3PT5S0000C 00350 3 UCB400H 4PT5S0000C 00350 2 400A UCB400H 2PT5S0000C 00400 3 UCB400H 3PT5S0000C 00400 3 UCB400H 4PT5S0000C 00400 2 250A UCB400L 2PT5S0000C 00250 3 UCB400L 3PT5S0000C 00250 3 UCB400L 4PT5S0000C 00250 2 UCB400L 300A UCB400L 2PT5S0000C 00300 3 UCB400L 3PT5S0000C 00300 3 UCB400L 4PT5S0000C 00300 2 320A UCB400L 2PT5S0000C 00320 3 UCB400L 3PT5S0000C 00320 3 UCB400L 4PT5S0000C 00320 2 350A UCB400L 2PT5S0000C 00350 3 UCB400L 3PT5S0000C 00350 3 UCB400L 4PT5S0000C 00350 2 400A UCB400L 2PT5S0000C 00400 3 UCB400L 3PT5S0000C 00400 3 UCB400L 4PT5S0000C 00400 2 30kA 42kA 65kA 100kA 76 Rated current Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 MCCB •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current 2 pole Code Unit (EA) 3 pole Code Unit (EA) 4 pole Code Unit (EA) 250A UCB400R 2PT4S0000C 00250F 3 UCB400R 3PT4S0000C 00250F 3 UCB400R 4PT4S0000C 00250F 2 UCB400R 300A UCB400R 2PT4S0000C 00300F 3 UCB400R 3PT4S0000C 00300F 3 UCB400R 4PT4S0000C 00300F 2 30kA 320A UCB400R 2PT4S0000C 00320F 3 UCB400R 3PT4S0000C 00320F 3 UCB400R 4PT4S0000C 00320F 2 350A UCB400R 2PT4S0000C 00350F 3 UCB400R 3PT4S0000C 00350F 3 UCB400R 4PT4S0000C 00350F 2 400A UCB400R 2PT4S0000C 00400F 3 UCB400R 3PT4S0000C 00400F 3 UCB400R 4PT4S0000C 00400F 2 250A UCB400S 2PT4S0000C 00250F 3 UCB400S 3PT4S0000C 00250F 3 UCB400S 4PT4S0000C 00250F 2 UCB400S 300A UCB400S 2PT4S0000C 00300F 3 UCB400S 3PT4S0000C 00300F 3 UCB400S 4PT4S0000C 00300F 2 320A UCB400S 2PT4S0000C 00320F 3 UCB400S 3PT4S0000C 00320F 3 UCB400S 4PT4S0000C 00320F 2 42kA 350A UCB400S 2PT4S0000C 00350F 3 UCB400S 3PT4S0000C 00350F 3 UCB400S 4PT4S0000C 00350F 2 400A UCB400S 2PT4S0000C 00400F 3 UCB400S 3PT4S0000C 00400F 3 UCB400S 4PT4S0000C 00400F 2 250A UCB400H 2PT4S0000C 00250F 3 UCB400H 3PT4S0000C 00250F 3 UCB400H 4PT4S0000C 00250F 2 UCB400H 300A UCB400H 2PT4S0000C 00300F 3 UCB400H 3PT4S0000C 00300F 3 UCB400H 4PT4S0000C 00300F 2 320A UCB400H 2PT4S0000C 00320F 3 UCB400H 3PT4S0000C 00320F 3 UCB400H 4PT4S0000C 00320F 2 65kA 350A UCB400H 2PT4S0000C 00350F 3 UCB400H 3PT4S0000C 00350F 3 UCB400H 4PT4S0000C 00350F 2 400A UCB400H 2PT4S0000C 00400F 3 UCB400H 3PT4S0000C 00400F 3 UCB400H 4PT4S0000C 00400F 2 250A UCB400L 2PT4S0000C 00250F 3 UCB400L 3PT4S0000C 00250F 3 UCB400L 4PT4S0000C 00250F 2 UCB400L 300A UCB400L 2PT4S0000C 00300F 3 UCB400L 3PT4S0000C 00300F 3 UCB400L 4PT4S0000C 00300F 2 100kA 320A UCB400L 2PT4S0000C 00320F 3 UCB400L 3PT4S0000C 00320F 3 UCB400L 4PT4S0000C 00320F 2 350A UCB400L 2PT4S0000C 00350F 3 UCB400L 3PT4S0000C 00350F 3 UCB400L 4PT4S0000C 00350F 2 400A UCB400L 2PT4S0000C 00400F 3 UCB400L 3PT4S0000C 00400F 3 UCB400L 4PT4S0000C 00400F 2 3 pole Code 4 pole Code Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V Rated current 2 pole Code Unit (EA) Unit (EA) Unit (EA) 250A UCB400R 2PT5S0000C 00250F 3 UCB400R 3PT5S0000C 00250F 3 UCB400R 4PT5S0000C 00250F 2 UCB400R 300A UCB400R 2PT5S0000C 00300F 3 UCB400R 3PT5S0000C 00300F 3 UCB400R 4PT5S0000C 00300F 2 30kA 320A UCB400R 2PT5S0000C 00320F 3 UCB400R 3PT5S0000C 00320F 3 UCB400R 4PT5S0000C 00320F 2 350A UCB400R 2PT5S0000C 00350F 3 UCB400R 3PT5S0000C 00350F 3 UCB400R 4PT5S0000C 00350F 2 400A UCB400R 2PT5S0000C 00400F 3 UCB400R 3PT5S0000C 00400F 3 UCB400R 4PT5S0000C 00400F 2 250A UCB400S 2PT5S0000C 00250F 3 UCB400S 3PT5S0000C 00250F 3 UCB400S 4PT5S0000C 00250F 2 UCB400S 300A UCB400S 2PT5S0000C 00300F 3 UCB400S 3PT5S0000C 00300F 3 UCB400S 4PT5S0000C 00300F 2 42kA 320A UCB400S 2PT5S0000C 00320F 3 UCB400S 3PT5S0000C 00320F 3 UCB400S 4PT5S0000C 00320F 350A UCB400S 2PT5S0000C 00350F 3 UCB400S 3PT5S0000C 00350F 3 Screw type terminal UCB400S 4PT5S0000C 00400F 2 connection, UCB400H 4PT5S0000C 00250F 2 No option, UCB400H 4PT5S0000C 00300F 2 50/60Hz UCB400H 4PT5S0000C 00320F 2 400A UCB400S 2PT5S0000C 00400F 3 UCB400S 3PT5S0000C 00400F 3 250A UCB400H 2PT5S0000C 00250F 3 UCB400H 3PT5S0000C 00250F 3 UCB400H 300A UCB400H 2PT5S0000C 00300F 3 UCB400H 3PT5S0000C 00300F 3 320A UCB400H 2PT5S0000C 00320F 3 UCB400H 3PT5S0000C 00320F 3 65kA UCB400S 4PT5S0000C 00350F 2 2 350A UCB400H 2PT5S0000C 00350F 3 UCB400H 3PT5S0000C 00350F 3 UCB400H 4PT5S0000C 00350F 2 400A UCB400H 2PT5S0000C 00400F 3 UCB400H 3PT5S0000C 00400F 3 UCB400H 4PT5S0000C 00400F 2 250A UCB400L 2PT5S0000C 00250F 3 UCB400L 3PT5S0000C 00250F 3 UCB400L 4PT5S0000C 00250F 2 UCB400L 300A UCB400L 2PT5S0000C 00300F 3 UCB400L 3PT5S0000C 00300F 3 UCB400L 4PT5S0000C 00300F 2 100kA Specification Category 320A UCB400L 2PT5S0000C 00320F 3 UCB400L 3PT5S0000C 00320F 3 UCB400L 4PT5S0000C 00320F 2 350A UCB400L 2PT5S0000C 00350F 3 UCB400L 3PT5S0000C 00350F 3 UCB400L 4PT5S0000C 00350F 2 400A UCB400L 2PT5S0000C 00400F 3 UCB400L 3PT5S0000C 00400F 3 UCB400L 4PT5S0000C 00400F 2 MCCB /M2 Molded Case Circuit Breaker_ 77 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 630AF | •UCB630R 45kA •UCB630S 65kA •UCB630H 85kA •UCB630L 100kA UCB630R UCB630S UCB630H Number of poles (P) ✽2, 3, 4 Degree of protection (without terminal bus bar) IP20 Utilization category A Suitability of isolation ○ Protection overload, inst., short-circuit Rated current (A) Rated insulation voltage [Ui] (V) UCB630L 500, 630 AC690 AC660 Rating Rated operational voltage [Ue] (V) DC250 Rated impulse withstand voltage [Uimp] (kV) 6 AC600/660V, 50-60Hz AC480/500V, 50-60Hz Rated AC440/460V, 50-60Hz short-circuit Ultimate breaking AC380/415V, 50-60Hz [Icu] capacity (kA r.m.s.) AC220/240V, 50-60Hz IEC 60947-2 DC250V K 60947-2 DC125V Service [Ics] % of [Icu] 22 25 35 35 25 45 50 65 35 50 65 85 45 65 85 100 50 100 100 125 20 40 40 40 30 50 50 60 50 ○ Fixed thermal, Trip Fixed instantaneous INST 10×In mechanism Thermal & Protection magnetic LTD (0.8-0.9-1)×In Adjustable thermal, characteristics Fixed instantaneous INST 10×In Direct mounting by screw ○ Both line & load side for Plug-in Switchboard Line side only ○1) Screw Terminal connection Bus bar ○ Mounting Durability (times) ○1) ○ Mechanical operation 20,000 Electrical operation a a d c Dimensions b 2/3/4P (mm) 6,000 Width 2102)/210/280 b Height 280 c Depth 110 d 145 Weight (kg, breaker only) 2/3/4P 8.7/9.5/12.5 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2)✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. 78 MCCB ■ Accessories •Signal 1C, right-hand-side Auxiliary switch AUX 46D R1 1C, left-hand-side Trip alarm switch ALT 46D L1 Shunt trip 1) Under voltage trip 2) DC24V DC100-110V AC100-120V AC200-230V AC380-415V SHT 46D A SHT 46D C SHT 46D F SHT 46D H SHT 46D B AC440-480V SHT 46D D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V ✽UVT 46D J ✽UVT 46D L ✽UVT 46D N ✽UVT 46D P ✽UVT 46D Q ✽UVT 46D R ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. •Operating Power supply direction Operating Surface S type handle 1) Extended S type Motor operator 2) Mechanical interlock Padlock plate3) Extension handle 4) Upper TFG 46DS U4 DC24V MOT 68E DC24 2 pole MIF 80E 3 Right Left TFG 46DS R4 TFG 46DS L4 TFH 46DS AC/DC110V AC/DC220V MOT 68E ADC110 MOT 68E ADC220 3 pole 4 pole MIF 80E 3 MIF 80E 4 PLD 40D THA 46D ` ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. 4) Supplied as standard component •Mounting Plug-in 1) Structure Mounting base Connection 2C contact block 2) 5C contact For both line & load side TDM 5BA 3) TYA 5/2 4) TYA 5/5 4) For line side only TDM 5BA - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 3) 2EA are required for both line & load side plug-in type 3P breaker. 4) TYA type connection blocks are to be installed with separate mounting angle. Separate mounting angle is not supplied. •Terminal 2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET) Terminal bus bar TBB 6S 2 Cage terminal block Terminal cover 1) Interpole barrier 2) 2EA/SET TBB 6S 3 TBB 6S 4 3EA/SET 4EA/SET CTB 80E 3S CTB 80E 4S 2 pole 3 pole 4 pole TCF 80E 3 TCF 80E 3 TCF 80E 4 TQQ 5BA 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit ※ Please refer to page 82. Molded Case Circuit Breaker_ 79 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 800AF | •UCB800R 45kA •UCB800S 65kA •UCB800H 85kA •UCB800L 100kA UCB800R UCB800S UCB800H Number of poles (P) ✽2, 3, 4 Degree of protection (without terminal bus bar) IP20 Utilization category A Suitability of isolation ○ Protection overload, inst., short-circuit Rated current (A) Rated insulation voltage [Ui] (V) UCB800L 700, 800 AC690 AC660 Rating Rated operational voltage [Ue] (V) DC250 Rated impulse withstand voltage [Uimp] (kV) 6 AC600/660V, 50-60Hz 25 25 35 35 AC480/500V, 50-60Hz Rated short-circuit AC440/460V, 50-60Hz Ultimate breaking [Icu] AC380/415V, 50-60Hz capacity (kA r.m.s.) AC220/240V, 50-60Hz 35 45 50 65 35 50 65 85 45 65 85 100 50 100 100 125 20 40 40 40 30 50 50 60 IEC 60947-2 DC250V K 60947-2 DC125V Service [Ics] % of [Icu] 50 ○ Fixed thermal, Trip Fixed instantaneous INST 10×In mechanism Thermal & Protection magnetic LTD (0.8-0.9-1)×In Adjustable thermal, characteristics Fixed instantaneous INST 10×In Direct mounting by screw ○ Both line & load side for Plug-in Switchboard Line side only ○1) Screw Terminal connection Bus bar ○ Mounting Durability (times) ○1) ○ Mechanical operation 10,000 Electrical operation 3,000 a Width 210 2)/210/280 Dimensions b 2/3/4P (mm) b Height 280 c Depth 110 a d c d 145 Weight (kg, breaker only) 2/3/4P 8.7/9.5/12.5 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) Available for 3P breaker 2)✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. 80 MCCB ■ Accessories •Signal 1C, right-hand-side Auxiliary switch AUX 46D R1 1C, left-hand-side Trip alarm switch Shunt trip ALT 46D L1 1) Under voltage trip 2) DC24V DC100-110V AC100-120V AC200-230V AC380-415V SHT 46D A SHT 46D C SHT 46D F SHT 46D H SHT 46D B AC440-480V SHT 46D D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V ✽UVT 46D J ✽UVT 46D L ✽UVT 46D N ✽UVT 46D P ✽UVT 46D Q ✽UVT 46D R ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. •Operating Power supply direction Operating Surface S type handle1) Extended S type Motor operator 2) Mechanical interlock Padlock plate3) Extension handle 4) Upper TFG 46DS U4 DC24V MOT 68E DC24 2 pole MIF 80E 3 Right TFG 46DS R4 TFH 46DS AC/DC110V MOT 68E ADC110 3 pole MIF 80E 3 PLD 40D THA 46D Left TFG 46DS L4 AC/DC220V MOT 68E ADC220 4 pole MIF 80E 4 ※ 1) For detail type information, please refer to page no. 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. 4) Supplied as standard component •Mounting Plug-in 1) Structure Mounting base Connection 2C contact block 2) 5C contact For both line & load side TDM 5BA 3) TYA 5/2 4) TYA 5/5 4) For line side only TDM 5BA - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 3) 2EA are required for both line & load side plug-in type 3p breaker. 4) TYA type connection blocks are to be installed with separate mounting angle. Separate mounting angle is not supplied. •Terminal 2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET) Terminal bus bar TBB 8S 2 Cage terminal block Terminal cover 1) Interpole barrier 2) 2EA/SET TBB 8S 3 TBB 8S 4 3EA/SET 4EA/SET CTB 80E 3S CTB 80E 4S 2 pole 3 pole 4 pole TCF 80E 3 TCF 80E 3 TCF 80E 4 TQQ 5BA 3PLINE ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit ※ Please refer to page 83. Molded Case Circuit Breaker_ 81 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit / UCB type 630AF •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current 2 pole Code 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) 500A UCB630R 2PT4S0000C 00500 2 UCB630R 3PT4S0000C 00500 2 UCB630R 4PT4S0000C 00500 1 630A UCB630R 2PT4S0000C 00630 2 UCB630R 3PT4S0000C 00630 2 UCB630R 4PT4S0000C 00630 1 UCB630S 65kA 500A UCB630S 2PT4S0000C 00500 2 UCB630S 3PT4S0000C 00500 2 UCB630S 4PT4S0000C 00500 1 630A UCB630S 2PT4S0000C 00630 2 UCB630S 3PT4S0000C 00630 2 UCB630S 4PT4S0000C 00630 1 UCB630H 85kA 500A UCB630H 2PT4S0000C 00500 2 UCB630H 3PT4S0000C 00500 2 UCB630H 4PT4S0000C 00500 1 630A UCB630H 2PT4S0000C 00630 2 UCB630H 3PT4S0000C 00630 2 UCB630H 4PT4S0000C 00630 1 UCB630L 100kA 500A UCB630L 2PT4S0000C 00500 2 UCB630L 3PT4S0000C 00500 2 UCB630L 4PT4S0000C 00500 1 630A UCB630L 2PT4S0000C 00630 2 UCB630L 3PT4S0000C 00630 2 UCB630L 4PT4S0000C 00630 1 2 pole 3 pole UCB630R 45kA Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V Rated current Code Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) 500A UCB630R 2PT5S0000C 00500 2 UCB630R 3PT5S0000C 00500 2 UCB630R 4PT5S0000C 00500 1 630A UCB630R 2PT5S0000C 00630 2 UCB630R 3PT5S0000C 00630 2 UCB630R 4PT5S0000C 00630 1 UCB630S 65kA 500A UCB630S 2PT5S0000C 00500 2 UCB630S 3PT5S0000C 00500 2 UCB630S 4PT5S0000C 00500 1 630A UCB630S 2PT5S0000C 00630 2 UCB630S 3PT5S0000C 00630 2 UCB630S 4PT5S0000C 00630 1 UCB630H 85kA 500A UCB630H 2PT5S0000C 00500 2 UCB630H 3PT5S0000C 00500 2 UCB630H 4PT5S0000C 00500 1 630A UCB630H 2PT5S0000C 00630 2 UCB630H 3PT5S0000C 00630 2 UCB630H 4PT5S0000C 00630 1 UCB630L 100kA 500A UCB630L 2PT5S0000C 00500 2 UCB630L 3PT5S0000C 00500 2 UCB630L 4PT5S0000C 00500 1 630A UCB630L 2PT5S0000C 00630 2 UCB630L 3PT5S0000C 00630 2 UCB630L 4PT5S0000C 00630 1 UCB630R 45kA Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UCB630R 45kA Rated current 2 pole Code 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) 500A UCB630R 2PT4S0000C 00500F 2 UCB630R 3PT4S0000C 00500F 2 UCB630R 4PT4S0000C 00500F 1 630A UCB630R 2PT4S0000C 00630F 2 UCB630R 3PT4S0000C 00630F 2 UCB630R 4PT4S0000C 00630F 1 UCB630S 65kA 500A UCB630S 2PT4S0000C 00500F 2 UCB630S 3PT4S0000C 00500F 2 UCB630S 4PT4S0000C 00500F 1 630A UCB630S 2PT4S0000C 00630F 2 UCB630S 3PT4S0000C 00630F 2 UCB630S 4PT4S0000C 00630F 1 UCB630H 85kA 500A UCB630H 2PT4S0000C 00500F 2 UCB630H 3PT4S0000C 00500F 2 UCB630H 4PT4S0000C 00500F 1 630A UCB630H 2PT4S0000C 00630F 2 UCB630H 3PT4S0000C 00630F 2 UCB630H 4PT4S0000C 00630F 1 UCB630L 100kA 500A UCB630L 2PT4S0000C 00500F 2 UCB630L 3PT4S0000C 00500F 2 UCB630L 4PT4S0000C 00500F 1 630A UCB630L 2PT4S0000C 00630F 2 UCB630L 3PT4S0000C 00630F 2 UCB630L 4PT4S0000C 00630F 1 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V 2 pole Code 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) 500A UCB630R 2PT5S0000C 00500F 2 UCB630R 3PT5S0000C 00500F 2 UCB630R 4PT5S0000C 00500F 1 630A UCB630R 2PT5S0000C 00630F 2 UCB630R 3PT5S0000C 00630F 2 UCB630R 4PT5S0000C 00630F 1 UCB630S 65kA 500A UCB630S 2PT5S0000C 00500F 2 UCB630S 3PT5S0000C 00500F 2 UCB630S 4PT5S0000C 00500F 1 630A UCB630S 2PT5S0000C 00630F 2 UCB630S 3PT5S0000C 00630F 2 UCB630S 4PT5S0000C 00630F 1 UCB630H 85kA 500A UCB630H 2PT5S0000C 00500F 2 UCB630H 3PT5S0000C 00500F 2 UCB630H 4PT5S0000C 00500F 1 630A UCB630H 2PT5S0000C 00630F 2 UCB630H 3PT5S0000C 00630F 2 UCB630H 4PT5S0000C 00630F 1 UCB630L 100kA 500A UCB630L 2PT5S0000C 00500F 2 UCB630L 3PT5S0000C 00500F 2 UCB630L 4PT5S0000C 00500F 1 630A UCB630L 2PT5S0000C 00630F 2 UCB630L 3PT5S0000C 00630F 2 UCB630L 4PT5S0000C 00630F 1 UCB630R 45kA 82 Rated current Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 MCCB ■ Standard order code and unit / UCB type 800AF •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V 2 pole 3 pole Rated current Code Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) 700A UCB800R 2PT4S0000C 00700 2 UCB800R 3PT4S0000C 00700 2 UCB800R 4PT4S0000C 00700 1 800A UCB800R 2PT4S0000C 00800 2 UCB800R 3PT4S0000C 00800 2 UCB800R 4PT4S0000C 00800 1 700A UCB800S 2PT4S0000C 00700 2 UCB800S 3PT4S0000C 00700 2 UCB800S 4PT4S0000C 00700 1 800A UCB800S 2PT4S0000C 00800 2 UCB800S 3PT4S0000C 00800 2 UCB800S 4PT4S0000C 00800 1 UCB800H 85kA 700A UCB800H 2PT4S0000C 00700 2 UCB800H 3PT4S0000C 00700 2 UCB800H 4PT4S0000C 00700 1 800A UCB800H 2PT4S0000C 00800 2 UCB800H 3PT4S0000C 00800 2 UCB800H 4PT4S0000C 00800 1 UCB800L 100kA 700A UCB800L 2PT4S0000C 00700 2 UCB800L 3PT4S0000C 00700 2 UCB800L 4PT4S0000C 00700 1 800A UCB800L 2PT4S0000C 00800 2 UCB800L 3PT4S0000C 00800 2 UCB800L 4PT4S0000C 00800 1 UCB800R 45kA UCB800S 65kA Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UCB800R 45kA UCB800S 65kA UCB800H 85kA UCB800L 100kA 2 pole 3 pole Rated current Code Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) 700A UCB800R 2PT5S0000C 00700 2 UCB800R 3PT5S0000C 00700 2 UCB800R 4PT5S0000C 00700 1 800A UCB800R 2PT5S0000C 00800 2 UCB800R 3PT5S0000C 00800 2 UCB800R 4PT5S0000C 00800 1 700A UCB800S 2PT5S0000C 00700 2 UCB800S 3PT5S0000C 00700 2 UCB800S 4PT5S0000C 00700 1 800A UCB800S 2PT5S0000C 00800 2 UCB800S 3PT5S0000C 00800 2 UCB800S 4PT5S0000C 00800 1 700A UCB800H 2PT5S0000C 00700 2 UCB800H 3PT5S0000C 00700 2 UCB800H 4PT5S0000C 00700 1 800A UCB800H 2PT5S0000C 00800 2 UCB800H 3PT5S0000C 00800 2 UCB800H 4PT5S0000C 00800 1 700A UCB800L 2PT5S0000C 00700 2 UCB800L 3PT5S0000C 00700 2 UCB800L 4PT5S0000C 00700 1 800A UCB800L 2PT5S0000C 00800 2 UCB800L 3PT5S0000C 00800 2 UCB800L 4PT5S0000C 00800 1 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current 2 pole Code 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) UCB800R 45kA 700A UCB800R 2PT4S0000C 00700F 2 UCB800R 3PT4S0000C 00700F 2 UCB800R 4PT4S0000C 00700F 1 800A UCB800R 2PT4S0000C 00800F 2 UCB800R 3PT4S0000C 00800F 2 UCB800R 4PT4S0000C 00800F 1 UCB800S 65kA 700A UCB800S 2PT4S0000C 00700F 2 UCB800S 3PT4S0000C 00700F 2 UCB800S 4PT4S0000C 00700F 1 800A UCB800S 2PT4S0000C 00800F 2 UCB800S 3PT4S0000C 00800F 2 UCB800S 4PT4S0000C 00800F 1 700A UCB800H 2PT4S0000C 00700F 2 UCB800H 3PT4S0000C 00700F 2 UCB800H 4PT4S0000C 00700F 1 UCB800H 85kA UCB800L 100kA 800A UCB800H 2PT4S0000C 00800F 2 UCB800H 3PT4S0000C 00800F 2 UCB800H 4PT4S0000C 00800F 1 700A UCB800L 2PT4S0000C 00700F 2 UCB800L 3PT4S0000C 00700F 2 UCB800L 4PT4S0000C 00700F 1 800A UCB800L 2PT4S0000C 00800F 2 UCB800L 3PT4S0000C 00800F 2 UCB800L 4PT4S0000C 00800F 1 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V UCB800R 45kA UCB800S 65kA UCB800H 85kA UCB800L 100kA Rated current 2 pole Code 3 pole Unit (EA) Code 4 pole Unit (EA) Code Unit (EA) 700A UCB800R 2PT5S0000C 00700F 2 UCB800R 3PT5S0000C 00700F 2 UCB800R 4PT5S0000C 00700F 1 800A UCB800R 2PT5S0000C 00800F 2 UCB800R 3PT5S0000C 00800F 2 UCB800R 4PT5S0000C 00800F 1 700A UCB800S 2PT5S0000C 00700F 2 UCB800S 3PT5S0000C 00700F 2 UCB800S 4PT5S0000C 00700F 1 800A UCB800S 2PT5S0000C 00800F 2 UCB800S 3PT5S0000C 00800F 2 UCB800S 4PT5S0000C 00800F 1 700A UCB800H 2PT5S0000C 00700F 2 UCB800H 3PT5S0000C 00700F 2 UCB800H 4PT5S0000C 00700F 1 800A UCB800H 2PT5S0000C 00800F 2 UCB800H 3PT5S0000C 00800F 2 UCB800H 4PT5S0000C 00800F 1 700A UCB800L 2PT5S0000C 00700F 2 UCB800L 3PT5S0000C 00700F 2 UCB800L 4PT5S0000C 00700F 1 800A UCB800L 2PT5S0000C 00800F 2 UCB800L 3PT5S0000C 00800F 2 UCB800L 4PT5S0000C 00800F 1 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Molded Case Circuit Breaker_ 83 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 1000AF | •UCB1000S 100kA •UCB1000L 130kA UCB1000S UCB1000L Number of poles (P) Degree of protection (without terminal bus bar) IP20 Utilization category A Suitability of isolation ○ Protection Rating 3, 4 overload, inst., short-circuit Rated current (A) 505-1,000 Rated insulation voltage [Ui] (V) AC750 Rated operational voltage [Ue] (V) AC690 Rated impulse withstand voltage [Uimp] (kV) 8 Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) AC600/660V, 50-60Hz 40 60 AC480/500V, 50-60Hz 75 100 AC440/460V, 50-60Hz 75 100 AC380/415V, 50-60Hz 100130 IEC 60947-2 AC220/240V, 50-60Hz K 60947-2 Service [Ics] % of [Icu] 100 150 50 Long time delay LTD (0.5-1) 1)×In (15 setting) Short time delay STD (2-4-6-8-10)×Ir Trip mechanism Electronic & Protection characteristics Instantaneous INST (3-6-8-10-11)×In Ground fault trip GFT (0.2-0.3-0.4)×In Pre-trip alarm PTA 0.9×In I2T lamp ○ ○ ○ ○ Mounting Pick-up LED Direct mounting by screw Terminal connection Durability (times) Bus bar Mechanical operation 10,000 Electrical operation a 3,000 a d c b Dimensions 3/4P b (mm) c d Weight (kg, breaker only) 3/4P Width 210/280 210/280 Height 370 370 Depth 110 200 159 249 13/17 25/33 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1) 84 MCCB ■ Accessories •Signal 1C, right-hand-side 2C, right-hand-side 3C, right-hand-side Auxiliary switch AUX 80NE R1 Trip alarm switch Shunt trip AUX 80NE R2 AUX 80NE R3 1C, right-hand-side ALT 80NE R1 1) Under voltage trip 2) DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V SHT 120NE A SHT 120NE C SHT 120NE F SHT 120NE H SHT 120NE B SHT 120NE D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V UVT 120NE J UVT 120NE L UVT 120NE N UVT 120NE P UVT 120NE Q UVT 120NE R ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. •Operating Motor operator 1) DC24V AC/DC110V AC/DC220V MOT 80NE DC24 MOT 80NE ADC110 MOT 80NE ADC220 Padlock plate 2) PLD 120NE Extension handle 3) THA 120NE ※ 1) Motor operator is not recommended for marine application. 2) Padlock is not supplied. 3) Supplied as standard component •Terminal Interpole barrier 1) 2EA/SET TQQ 80NE 3P ※ 1) Supplied as standard component Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit •Electronic - LTD, STD, INST trip & PTA Model / Breaking capacity at AC380/415V 표준품 주문코드 Rated current UCB1000S 100kA 1000A UCB1000S 3PESB0000X 01000 1 UCB1000S 4PESB0000X 01000 1 3 pole Code 4 pole Unit (EA) Code Unit (EA) UCB1000L 130kA 1000A UCB1000L 3PESB0000X 01000 1 UCB1000L 4PESB0000X 01000 1 UCB1000S 100kA 1000A UCB1000S 3PESB0000Y 01000 1 UCB1000S 4PESB0000Y 01000 1 UCB1000L 130kA 1000A UCB1000L 3PESB0000Y 01000 1 UCB1000S 4PESB0000Y 01000 1 Specification Bus bar type terminal connection, No option, 50Hz Bus bar type terminal connection, No option, 60Hz Category MCCB /M3 •Electronic - LTD, STD, INST, GFT trip & PTA Model / Breaking capacity at AC380/415V 표준품 주문코드 Rated current UCB1000S 100kA 1000A UCB1000S 3PEGB0000X 01000 1 UCB1000S 4PEGB0000X 01000 1 UCB1000L 130kA 1000A UCB1000L 3PEGB0000X 01000 1 UCB1000L 4PEGB0000X 01000 1 UCB1000S 100kA 1000A UCB1000S 3PEGB0000Y 01000 1 UCB1000S 4PEGB0000Y 01000 1 UCB1000L 130kA 1000A UCB1000L 3PEGB0000Y 01000 1 UCB1000L 4PEGB0000Y 01000 1 3 pole Code 4 pole Unit (EA) Code Unit (EA) Specification Bus bar type terminal connection, No option, 50Hz Bus bar type terminal connection, No option, 60Hz Category MCCB /M3 Molded Case Circuit Breaker_ 85 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 1250AF | •UCB1250S 100kA •UCB1250L 130kA UCB1250S UCB1250L Number of poles (P) Degree of protection (without terminal bus bar) IP20 Utilization category A Suitability of isolation ○ Protection overload, inst., short-circuit Rating 3, 4 Rated current (A) 630-1,250 Rated insulation voltage [Ui] (V) AC750 Rated operational voltage [Ue] (V) AC690 Rated impulse withstand voltage [Uimp] (kV) 8 Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) AC600/660V, 50-60Hz 40 60 AC480/500V, 50-60Hz 75 100 AC440/460V, 50-60Hz 75 100 AC380/415V, 50-60Hz 100130 IEC 60947-2 AC220/240V, 50-60Hz K 60947-2 Service [Ics] % of [Icu] 100 150 50 Long time delay LTD (0.5-1) 1)×In (15 setting) Short time delay STD (2-4-6-8-10)×Ir Trip mechanism Electronic & Protection characteristics Instantaneous INST (3-6-8-10-11)×In Ground fault trip GFT (0.2-0.3-0.4)×In Pre-trip alarm PTA 0.9×In I2T lamp ○ Mounting Pick-up LED Direct mounting by screw Terminal connection Durability (times) ○ ○ Bus bar ○ Mechanical operation 10,000 Electrical operation (times) a a d c b Dimensions 3/4P b (mm) c d Weight (kg, breaker only) 3/4P 3,000 Width 210/280 210/280 Height 370 370 Depth 110 200 159 249 13.5/17.5 25.5/33.5 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1) 86 MCCB ■ Accessories •Signal 1C, right-hand-side 2C, right-hand-side 3C, right-hand-side Auxiliary switch AUX 80NE R1 Trip alarm switch Shunt trip 1) Under voltage trip 2) AUX 80NE R2 AUX 80NE R3 1C, right-hand-side ALT 80NE R1 DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V SHT 120NE A SHT 120NE C SHT 120NE F SHT 120NE H SHT 120NE B SHT 120NE D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V UVT 120NE J UVT 120NE L UVT 120NE N UVT 120NE P UVT 120NE Q UVT 120NE R ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. •Operating Motor operator 1) DC24V AC/DC110V AC/DC220V MOT 80NE DC24 MOT 80NE ADC110 MOT 80NE ADC220 Padlock plate 2) PLD 120NE Extension handle 3) THA 120NE ※ 1) Motor operator is not recommended for marine application. 2) Padlock is not supplied. 3) Supplied as standard component •Terminal Interpole barrier 1) 2EA/SET TQQ 80NE 3P ※ 1) Supplied as standard component Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit •Electronic - LTD, STD, INST trip & PTA Model / Breaking capacity at AC380/415V 표준품 주문코드 Rated current UCB1250S 100kA 1250A UCB1250S 3PESB0000X 01250 1 UCB1250S 4PESB0000X 01250 1 3 pole Code 4 pole Unit (EA) Code Unit (EA) UCB1250L 130kA 1250A UCB1250L 3PESB0000X 01250 1 UCB1250L 4PESB0000X 01250 1 UCB1250S 100kA 1250A UCB1250S 3PESB0000Y 01250 1 UCB1250S 4PESB0000Y 01250 1 UCB1250L 130kA 1250A UCB1250L 3PESB0000Y 01250 1 UCB1250L 4PESB0000Y 01250 1 Specification Bus bar type terminal connection, No option, 50Hz Bus bar type terminal connection, No option, 60Hz Category MCCB /M3 •Electronic - LTD, STD, INST, GFT trip & PTA Model / Breaking capacity at AC380/415V 표준품 주문코드 Rated current UCB1250S 100kA 1250A UCB1250S 3PEGB0000X 01250 1 UCB1250S 4PEGB0000X 01250 1 3 pole Code 4 pole Unit (EA) Code Unit (EA) UCB1250L 130kA 1250A UCB1250L 3PEGB0000X 01250 1 UCB1250L 4PEGB0000X 01250 1 UCB1250S 100kA 1250A UCB1250S 3PEGB0000Y 01250 1 UCB1250S 4PEGB0000Y 01250 1 UCB1250L 130kA 1250A UCB1250L 3PEGB0000Y 01250 1 UCB1250L 4PEGB0000Y 01250 1 Specification Bus bar type terminal connection, No option, 50Hz Bus bar type terminal connection, No option, 60Hz Category MCCB /M3 Molded Case Circuit Breaker_ 87 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UCB type / 1600AF | •UCB1600S 65kA UCB1600S Number of poles (P) 3 Degree of protection (without terminal bus bar) IP20 Utilization category A Suitability of isolation ○ Protection Rating overload, inst., short-circuit Rated current (A) 640-1,600 Rated insulation voltage [Ui] (V) AC750 Rated operational voltage [Ue] (V) AC690 Rated impulse withstand voltage [Uimp] (kV) 8 Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) AC600/660V, 50-60Hz 25 AC480/500V, 50-60Hz 35 AC440/460V, 50-60Hz 45 AC380/415V, 50-60Hz 65 IEC 60947-2 AC220/240V, 50-60Hz K 60947-2 Service [Ics] % of [Icu] 100 Trip mechanism Electronic & Protection characteristics Mounting Durability (times) Long time delay LTD (0.4-1) 1)×In (8 setting) Instantaneous INST (2-3-4-5-6-7-8-10)×In Pick-up LED Direct mounting by screw Terminal connection 50 Bus bar ○ ○ ○ Mechanical operation 10,000 Electrical operation a d c Dimensions 3/4P b (mm) 3,000 a Width 210 b Height 371 c Depth 151 d 215 Weight (kg, breaker only) 27 3/4P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) (0.4-1): (0.4-0.5-0.6-0.7-0.8-0.9-0.95-1) 88 MCCB ■ Accessories •Signal 1C, right-hand-side 2C, right-hand-side Auxiliary switch AUX 160NE R1 Shunt trip 1) Under voltage trip 2) AUX 160NE R2 DC24V DC100-110V AC100-120V AC200-230V AC380V SHT 160NE A SHT 160NE C SHT 160NE F SHT 160NE H SHT 160NE B DC24V DC100-110V AC100-120V AC200-230V AC380V AC440V - - - UVT 160NE P UVT 160NE Q UVT 160NE R ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. •Operating Motor operator 1) Extension handle MOT 160NE AC220 AC220V THA 160NE 2) ※ 1) Motor operator is not recommended for marine application. 2) Supplied as standard component •Terminal Terminal cover 1) Interpole barrier 2) TCF 160NE 3 4EA/SET TQQ 160NE 3P ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component ■ Standard order code and unit •Electronic - LTD, INST trip Model / Breaking capacity at AC380/415V Rated current UCB1600S 65kA 1600A 3 pole Code UCB1600S 3PESB0000C 01600 Unit (EA) 1 Specification Category Bus bar type terminal connection, No option, 50/60Hz MCCB/M3 Molded Case Circuit Breaker_ 89 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UPB type / 125AF | •UPB100S 85kA •UPB100H 100kA •UPB100L 130kA •UPB100X 150kA UPB100S UPB100H UPB100L UPB100X Number of poles (P) 3, 4 Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection overload, inst., short-circuit Thermal magnetic type 15,16,20,25,30,32,40,50,60, 63,75, 80,100,125 Rated current (A) Electronic type 50-125 Rated insulation voltage [Ui] (V) AC750 Rating AC690 Rated operational voltage [Ue] (V) DC500 1) Rated impulse withstand voltage [Uimp] (kV) 8 AC660/690V, 50-60Hz 10 1025 25 Rated AC480/500V, 50-60Hz 50 6585 85 short-circuit Ultimate AC440/460V, 50-60Hz 65 85100 150 breaking [Icu] AC380/415V, 50-60Hz 85 100130 150 capacity (kA r.m.s.) AC220/240V, 50-60Hz 100 130150 200 DC250V 501) 65 1)85 1) 1001) IEC 60947-2 DC125V 651) 100 1)100 1) 1001) K 60947-2 Service [Ics] % of [Icu] 100 Fixed thermal, ○ Thermal Fixed instantaneous INST 10×In magnetic Adjustable thermal, LTD (0.8-0.9-1)×In Trip Fixed instantaneous INST 10×In mechanism Long time delay LTD & Protection 50,55,63,70,80,90,100,115,125 characteristics Short time delay STD (NON-2-3-4-5-6-7-8-9-10)×Ir Electronic Instantaneous INST 11×In Pre-trip alarm PTA 0.9×Ir Pick-up LED ○ Direct mounting by screw ○ Mounting Both line & load side ○2) for Plug-in Switchboard Line side only ○2) Screw ○ Terminal connection Bus bar ○ Mechanical operation 25,000 Durability (times) Electrical operation 10,000 d a a Width 105/140 c Dimensions b Height 165 3/4P b (mm) c Depth 86.5 d 112 Weight (kg, breaker only) 3/4P 1.8/2.2 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) DC is not applicable for electronic breaker. 2) Available for 3P breaker ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip 1) Under voltage trip 2) 90 1C, right-hand-side AUX 12UP R1 1C, left-hand-side ALT 12UP L1 DC24V SHT 12UP A DC24V ✽UVT 12UP J DC100-110V SHT 12UP C DC100-110V ✽UVT 12UP L AC100-120V SHT 12UP F AC100-120V ✽UVT 12UP N ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. AC200-230V SHT 12UP H AC200-230V ✽UVT 12UP P AC380-415V SHT 12UP B AC380-415V ✽UVT 12UP Q AC440-480V SHT 12UP D AC440-480V ✽UVT 12UP R MCCB •Operating Upper Right Left Power supply direction TFG 12UPS U4 TFG 12UPS R4 TFG 12UPS L4 S type Operating Surface TFG 12UPL U4 - TFG 12UPL L4 L type handle 1) TFH 12UPS S type Extended TFH 12UPL L type DC24V AC/DC110VAC/DC220V Motor operator 2) MOT 12UP DC24 MOT 12UP ADC110MOT 12UP ADC220 3 pole 4 pole Mechanical interlock MIF 12UP 3 MIF 12UP 4 Padlock plate3) PLD 12UP ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting Plug-in 1) Structure Mounting base Connection 6C contact block 2) 12C contact For both line & load side TDM 12NEP CBM 26NE 6 CBM 26NE 63) For line side only TDM 12NEF - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 3) 2EA shall be ordered for 12C contact. •Terminal Terminal bus bar Cage terminal block Terminal cover 1) Interpole barrier 2) 3 pole (6EA/SET) 4 pole (8EA/SET) 3EA/SET 4EA/SET 3 pole 4 pole 4EA/SET TBB 12NE 3 TBB 12NE 4 CTB 12UP 3S CTB 12UP 4S TCF 12UP 3 TCF 12UP 4 TQQ 12NE 3P ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) S upplied as standard component Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit •Electronic - LTD, STD, INST trip & PTA Model / Breaking capacity at AC380/415V 3 pole Rated current Code UPB100S 85kA 125A UPB100H 100kA 125A UPB100L 130kA UPB100X 150kA 4 pole Unit (EA) Code Unit (EA) UPB100S 3PESS0000X 00125 8 UPB100S 4PESS0000X 00125 6 UPB100H 3PESS0000X 00125 8 UPB100H 4PESS0000X 00125 6 125A UPB100L 3PESS0000X 00125 8 UPB100L 4PESS0000X 00125 6 125A UPB100X 3PESS0000X 00125 8 UPB100X 4PESS0000X 00125 6 UPB100S 85kA 125A UPB100S 3PESS0000Y 00125 8 UPB100S 4PESS0000Y 00125 6 UPB100H 100kA 125A UPB100H 3PESS0000Y 00125 8 UPB100H 4PESS0000Y 00125 6 UPB100L 130kA 125A UPB100L 3PESS0000Y 00125 8 UPB100L 4PESS0000Y 00125 6 UPB100X 150kA 125A UPB100X 3PESS0000Y 00125 8 UPB100X 4PESS0000Y 00125 6 Specification Screw type terminal connection, No option, 50Hz Category MCCB/M3 Screw type terminal connection, No option, 60Hz Molded Case Circuit Breaker_ 91 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UPB100S 85kA UPB100H 100kA UPB100L 130kA UPB100X 150kA 92 Rated current 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 3 pole Code UPB100S 3PT4S0000C 00015 UPB100S 3PT4S0000C 00016 UPB100S 3PT4S0000C 00020 UPB100S 3PT4S0000C 00025 UPB100S 3PT4S0000C 00030 UPB100S 3PT4S0000C 00032 UPB100S 3PT4S0000C 00040 UPB100S 3PT4S0000C 00050 UPB100S 3PT4S0000C 00060 UPB100S 3PT4S0000C 00063 UPB100S 3PT4S0000C 00075 UPB100S 3PT4S0000C 00080 UPB100S 3PT4S0000C 00100 UPB100S 3PT4S0000C 00125 UPB100H 3PT4S0000C 00015 UPB100H 3PT4S0000C 00016 UPB100H 3PT4S0000C 00020 UPB100H 3PT4S0000C 00025 UPB100H 3PT4S0000C 00030 UPB100H 3PT4S0000C 00032 UPB100H 3PT4S0000C 00040 UPB100H 3PT4S0000C 00050 UPB100H 3PT4S0000C 00060 UPB100H 3PT4S0000C 00063 UPB100H 3PT4S0000C 00075 UPB100H 3PT4S0000C 00080 UPB100H 3PT4S0000C 00100 UPB100H 3PT4S0000C 00125 UPB100L 3PT4S0000C 00015 UPB100L 3PT4S0000C 00016 UPB100L 3PT4S0000C 00020 UPB100L 3PT4S0000C 00025 UPB100L 3PT4S0000C 00030 UPB100L 3PT4S0000C 00032 UPB100L 3PT4S0000C 00040 UPB100L 3PT4S0000C 00050 UPB100L 3PT4S0000C 00060 UPB100L 3PT4S0000C 00063 UPB100L 3PT4S0000C 00075 UPB100L 3PT4S0000C 00080 UPB100L 3PT4S0000C 00100 UPB100L 3PT4S0000C 00125 UPB100X 3PT4S0000C 00015 UPB100X 3PT4S0000C 00016 UPB100X 3PT4S0000C 00020 UPB100X 3PT4S0000C 00025 UPB100X 3PT4S0000C 00030 UPB100X 3PT4S0000C 00032 UPB100X 3PT4S0000C 00040 UPB100X 3PT4S0000C 00050 UPB100X 3PT4S0000C 00060 UPB100X 3PT4S0000C 00063 UPB100X 3PT4S0000C 00075 UPB100X 3PT4S0000C 00080 UPB100X 3PT4S0000C 00100 UPB100X 3PT4S0000C 00125 Unit (EA) 4 pole Code Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 UPB100S 4PT4S0000C 00015 UPB100S 4PT4S0000C 00016 UPB100S 4PT4S0000C 00020 UPB100S 4PT4S0000C 00025 UPB100S 4PT4S0000C 00030 UPB100S 4PT4S0000C 00032 UPB100S 4PT4S0000C 00040 UPB100S 4PT4S0000C 00050 UPB100S 4PT4S0000C 00060 UPB100S 4PT4S0000C 00063 UPB100S 4PT4S0000C 00075 UPB100S 4PT4S0000C 00080 UPB100S 4PT4S0000C 00100 UPB100S 4PT4S0000C 00125 UPB100H 4PT4S0000C 00015 UPB100H 4PT4S0000C 00016 UPB100H 4PT4S0000C 00020 UPB100H 4PT4S0000C 00025 UPB100H 4PT4S0000C 00030 UPB100H 4PT4S0000C 00032 UPB100H 4PT4S0000C 00040 UPB100H 4PT4S0000C 00050 UPB100H 4PT4S0000C 00060 UPB100H 4PT4S0000C 00063 UPB100H 4PT4S0000C 00075 UPB100H 4PT4S0000C 00080 UPB100H 4PT4S0000C 00100 UPB100H 4PT4S0000C 00125 UPB100L 4PT4S0000C 00015 UPB100L 4PT4S0000C 00016 UPB100L 4PT4S0000C 00020 UPB100L 4PT4S0000C 00025 UPB100L 4PT4S0000C 00030 UPB100L 4PT4S0000C 00032 UPB100L 4PT4S0000C 00040 UPB100L 4PT4S0000C 00050 UPB100L 4PT4S0000C 00060 UPB100L 4PT4S0000C 00063 UPB100L 4PT4S0000C 00075 UPB100L 4PT4S0000C 00080 UPB100L 4PT4S0000C 00100 UPB100L 4PT4S0000C 00125 UPB100X 4PT4S0000C 00015 UPB100X 4PT4S0000C 00016 UPB100X 4PT4S0000C 00020 UPB100X 4PT4S0000C 00025 UPB100X 4PT4S0000C 00030 UPB100X 4PT4S0000C 00032 UPB100X 4PT4S0000C 00040 UPB100X 4PT4S0000C 00050 UPB100X 4PT4S0000C 00060 UPB100X 4PT4S0000C 00063 UPB100X 4PT4S0000C 00075 UPB100X 4PT4S0000C 00080 UPB100X 4PT4S0000C 00100 UPB100X 4PT4S0000C 00125 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 MCCB 50℃ Model / Breaking capacity at AC380/415V UPB100S 85kA UPB100H 100kA UPB100L 130kA UPB100X 150kA Rated current 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 3 pole Code UPB100S 3PT5S0000C 00015 UPB100S 3PT5S0000C 00016 UPB100S 3PT5S0000C 00020 UPB100S 3PT5S0000C 00025 UPB100S 3PT5S0000C 00030 UPB100S 3PT5S0000C 00032 UPB100S 3PT5S0000C 00040 UPB100S 3PT5S0000C 00050 UPB100S 3PT5S0000C 00060 UPB100S 3PT5S0000C 00063 UPB100S 3PT5S0000C 00075 UPB100S 3PT5S0000C 00080 UPB100S 3PT5S0000C 00100 UPB100S 3PT5S0000C 00125 UPB100H 3PT5S0000C 00015 UPB100H 3PT5S0000C 00016 UPB100H 3PT5S0000C 00020 UPB100H 3PT5S0000C 00025 UPB100H 3PT5S0000C 00030 UPB100H 3PT5S0000C 00032 UPB100H 3PT5S0000C 00040 UPB100H 3PT5S0000C 00050 UPB100H 3PT5S0000C 00060 UPB100H 3PT5S0000C 00063 UPB100H 3PT5S0000C 00075 UPB100H 3PT5S0000C 00080 UPB100H 3PT5S0000C 00100 UPB100H 3PT5S0000C 00125 UPB100L 3PT5S0000C 00015 UPB100L 3PT5S0000C 00016 UPB100L 3PT5S0000C 00020 UPB100L 3PT5S0000C 00025 UPB100L 3PT5S0000C 00030 UPB100L 3PT5S0000C 00032 UPB100L 3PT5S0000C 00040 UPB100L 3PT5S0000C 00050 UPB100L 3PT5S0000C 00060 UPB100L 3PT5S0000C 00063 UPB100L 3PT5S0000C 00075 UPB100L 3PT5S0000C 00080 UPB100L 3PT5S0000C 00100 UPB100L 3PT5S0000C 00125 UPB100X 3PT5S0000C 00015 UPB100X 3PT5S0000C 00016 UPB100X 3PT5S0000C 00020 UPB100X 3PT5S0000C 00025 UPB100X 3PT5S0000C 00030 UPB100X 3PT5S0000C 00032 UPB100X 3PT5S0000C 00040 UPB100X 3PT5S0000C 00050 UPB100X 3PT5S0000C 00060 UPB100X 3PT5S0000C 00063 UPB100X 3PT5S0000C 00075 UPB100X 3PT5S0000C 00080 UPB100X 3PT5S0000C 00100 UPB100X 3PT5S0000C 00125 Unit (EA) 4 pole Code Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 UPB100S 4PT5S0000C 00015 UPB100S 4PT5S0000C 00016 UPB100S 4PT5S0000C 00020 UPB100S 4PT5S0000C 00025 UPB100S 4PT5S0000C 00030 UPB100S 4PT5S0000C 00032 UPB100S 4PT5S0000C 00040 UPB100S 4PT5S0000C 00050 UPB100S 4PT5S0000C 00060 UPB100S 4PT5S0000C 00063 UPB100S 4PT5S0000C 00075 UPB100S 4PT5S0000C 00080 UPB100S 4PT5S0000C 00100 UPB100S 4PT5S0000C 00125 UPB100H 4PT5S0000C 00015 UPB100H 4PT5S0000C 00016 UPB100H 4PT5S0000C 00020 UPB100H 4PT5S0000C 00025 UPB100H 4PT5S0000C 00030 UPB100H 4PT5S0000C 00032 UPB100H 4PT5S0000C 00040 UPB100H 4PT5S0000C 00050 UPB100H 4PT5S0000C 00060 UPB100H 4PT5S0000C 00063 UPB100H 4PT5S0000C 00075 UPB100H 4PT5S0000C 00080 UPB100H 4PT5S0000C 00100 UPB100H 4PT5S0000C 00125 UPB100L 4PT5S0000C 00015 UPB100L 4PT5S0000C 00016 UPB100L 4PT5S0000C 00020 UPB100L 4PT5S0000C 00025 UPB100L 4PT5S0000C 00030 UPB100L 4PT5S0000C 00032 UPB100L 4PT5S0000C 00040 UPB100L 4PT5S0000C 00050 UPB100L 4PT5S0000C 00060 UPB100L 4PT5S0000C 00063 UPB100L 4PT5S0000C 00075 UPB100L 4PT5S0000C 00080 UPB100L 4PT5S0000C 00100 UPB100L 4PT5S0000C 00125 UPB100X 4PT5S0000C 00015 UPB100X 4PT5S0000C 00016 UPB100X 4PT5S0000C 00020 UPB100X 4PT5S0000C 00025 UPB100X 4PT5S0000C 00030 UPB100X 4PT5S0000C 00032 UPB100X 4PT5S0000C 00040 UPB100X 4PT5S0000C 00050 UPB100X 4PT5S0000C 00060 UPB100X 4PT5S0000C 00063 UPB100X 4PT5S0000C 00075 UPB100X 4PT5S0000C 00080 UPB100X 4PT5S0000C 00100 UPB100X 4PT5S0000C 00125 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Molded Case Circuit Breaker_ 93 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UPB100S 85kA UPB100H 100kA UPB100L 130kA UPB100X 150kA 94 Rated current 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 3 pole Code UPB100S 3PT4S0000C 00015F UPB100S 3PT4S0000C 00016F UPB100S 3PT4S0000C 00020F UPB100S 3PT4S0000C 00025F UPB100S 3PT4S0000C 00030F UPB100S 3PT4S0000C 00032F UPB100S 3PT4S0000C 00040F UPB100S 3PT4S0000C 00050F UPB100S 3PT4S0000C 00060F UPB100S 3PT4S0000C 00063F UPB100S 3PT4S0000C 00075F UPB100S 3PT4S0000C 00080F UPB100S 3PT4S0000C 00100F UPB100S 3PT4S0000C 00125F UPB100H 3PT4S0000C 00015F UPB100H 3PT4S0000C 00016F UPB100H 3PT4S0000C 00020F UPB100H 3PT4S0000C 00025F UPB100H 3PT4S0000C 00030F UPB100H 3PT4S0000C 00032F UPB100H 3PT4S0000C 00040F UPB100H 3PT4S0000C 00050F UPB100H 3PT4S0000C 00060F UPB100H 3PT4S0000C 00063F UPB100H 3PT4S0000C 00075F UPB100H 3PT4S0000C 00080F UPB100H 3PT4S0000C 00100F UPB100H 3PT4S0000C 00125F UPB100L 3PT4S0000C 00015F UPB100L 3PT4S0000C 00016F UPB100L 3PT4S0000C 00020F UPB100L 3PT4S0000C 00025F UPB100L 3PT4S0000C 00030F UPB100L 3PT4S0000C 00032F UPB100L 3PT4S0000C 00040F UPB100L 3PT4S0000C 00050F UPB100L 3PT4S0000C 00060F UPB100L 3PT4S0000C 00063F UPB100L 3PT4S0000C 00075F UPB100L 3PT4S0000C 00080F UPB100L 3PT4S0000C 00100F UPB100L 3PT4S0000C 00125F UPB100X 3PT4S0000C 00015F UPB100X 3PT4S0000C 00016F UPB100X 3PT4S0000C 00020F UPB100X 3PT4S0000C 00025F UPB100X 3PT4S0000C 00030F UPB100X 3PT4S0000C 00032F UPB100X 3PT4S0000C 00040F UPB100X 3PT4S0000C 00050F UPB100X 3PT4S0000C 00060F UPB100X 3PT4S0000C 00063F UPB100X 3PT4S0000C 00075F UPB100X 3PT4S0000C 00080F UPB100X 3PT4S0000C 00100F UPB100X 3PT4S0000C 00125F Unit (EA) 4 pole Code Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 UPB100S 4PT4S0000C 00015F UPB100S 4PT4S0000C 00016F UPB100S 4PT4S0000C 00020F UPB100S 4PT4S0000C 00025F UPB100S 4PT4S0000C 00030F UPB100S 4PT4S0000C 00032F UPB100S 4PT4S0000C 00040F UPB100S 4PT4S0000C 00050F UPB100S 4PT4S0000C 00060F UPB100S 4PT4S0000C 00063F UPB100S 4PT4S0000C 00075F UPB100S 4PT4S0000C 00080F UPB100S 4PT4S0000C 00100F UPB100S 4PT4S0000C 00125F UPB100H 4PT4S0000C 00015F UPB100H 4PT4S0000C 00016F UPB100H 4PT4S0000C 00020F UPB100H 4PT4S0000C 00025F UPB100H 4PT4S0000C 00030F UPB100H 4PT4S0000C 00032F UPB100H 4PT4S0000C 00040F UPB100H 4PT4S0000C 00050F UPB100H 4PT4S0000C 00060F UPB100H 4PT4S0000C 00063F UPB100H 4PT4S0000C 00075F UPB100H 4PT4S0000C 00080F UPB100H 4PT4S0000C 00100F UPB100H 4PT4S0000C 00125F UPB100L 4PT4S0000C 00015F UPB100L 4PT4S0000C 00016F UPB100L 4PT4S0000C 00020F UPB100L 4PT4S0000C 00025F UPB100L 4PT4S0000C 00030F UPB100L 4PT4S0000C 00032F UPB100L 4PT4S0000C 00040F UPB100L 4PT4S0000C 00050F UPB100L 4PT4S0000C 00060F UPB100L 4PT4S0000C 00063F UPB100L 4PT4S0000C 00075F UPB100L 4PT4S0000C 00080F UPB100L 4PT4S0000C 00100F UPB100L 4PT4S0000C 00125F UPB100X 4PT4S0000C 00015F UPB100X 4PT4S0000C 00016F UPB100X 4PT4S0000C 00020F UPB100X 4PT4S0000C 00025F UPB100X 4PT4S0000C 00030F UPB100X 4PT4S0000C 00032F UPB100X 4PT4S0000C 00040F UPB100X 4PT4S0000C 00050F UPB100X 4PT4S0000C 00060F UPB100X 4PT4S0000C 00063F UPB100X 4PT4S0000C 00075F UPB100X 4PT4S0000C 00080F UPB100X 4PT4S0000C 00100F UPB100X 4PT4S0000C 00125F 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 MCCB 50℃ Model / Breaking capacity at AC380/415V UPB100S 85kA UPB100H 100kA UPB100L 130kA UPB100X 150kA Rated current 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 75A 80A 100A 125A 3 pole Code UPB100S 3PT5S0000C 00015F UPB100S 3PT5S0000C 00016F UPB100S 3PT5S0000C 00020F UPB100S 3PT5S0000C 00025F UPB100S 3PT5S0000C 00030F UPB100S 3PT5S0000C 00032F UPB100S 3PT5S0000C 00040F UPB100S 3PT5S0000C 00050F UPB100S 3PT5S0000C 00060F UPB100S 3PT5S0000C 00063F UPB100S 3PT5S0000C 00075F UPB100S 3PT5S0000C 00080F UPB100S 3PT5S0000C 00100F UPB100S 3PT5S0000C 00125F UPB100H 3PT5S0000C 00015F UPB100H 3PT5S0000C 00016F UPB100H 3PT5S0000C 00020F UPB100H 3PT5S0000C 00025F UPB100H 3PT5S0000C 00030F UPB100H 3PT5S0000C 00032F UPB100H 3PT5S0000C 00040F UPB100H 3PT5S0000C 00050F UPB100H 3PT5S0000C 00060F UPB100H 3PT5S0000C 00063F UPB100H 3PT5S0000C 00075F UPB100H 3PT5S0000C 00080F UPB100H 3PT5S0000C 00100F UPB100H 3PT5S0000C 00125F UPB100L 3PT5S0000C 00015F UPB100L 3PT5S0000C 00016F UPB100L 3PT5S0000C 00020F UPB100L 3PT5S0000C 00025F UPB100L 3PT5S0000C 00030F UPB100L 3PT5S0000C 00032F UPB100L 3PT5S0000C 00040F UPB100L 3PT5S0000C 00050F UPB100L 3PT5S0000C 00060F UPB100L 3PT5S0000C 00063F UPB100L 3PT5S0000C 00075F UPB100L 3PT5S0000C 00080F UPB100L 3PT5S0000C 00100F UPB100L 3PT5S0000C 00125F UPB100X 3PT5S0000C 00015F UPB100X 3PT5S0000C 00016F UPB100X 3PT5S0000C 00020F UPB100X 3PT5S0000C 00025F UPB100X 3PT5S0000C 00030F UPB100X 3PT5S0000C 00032F UPB100X 3PT5S0000C 00040F UPB100X 3PT5S0000C 00050F UPB100X 3PT5S0000C 00060F UPB100X 3PT5S0000C 00063F UPB100X 3PT5S0000C 00075F UPB100X 3PT5S0000C 00080F UPB100X 3PT5S0000C 00100F UPB100X 3PT5S0000C 00125F Unit (EA) 4 pole Code Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 UPB100S 4PT5S0000C 00015F UPB100S 4PT5S0000C 00016F UPB100S 4PT5S0000C 00020F UPB100S 4PT5S0000C 00025F UPB100S 4PT5S0000C 00030F UPB100S 4PT5S0000C 00032F UPB100S 4PT5S0000C 00040F UPB100S 4PT5S0000C 00050F UPB100S 4PT5S0000C 00060F UPB100S 4PT5S0000C 00063F UPB100S 4PT5S0000C 00075F UPB100S 4PT5S0000C 00080F UPB100S 4PT5S0000C 00100F UPB100S 4PT5S0000C 00125F UPB100H 4PT5S0000C 00015F UPB100H 4PT5S0000C 00016F UPB100H 4PT5S0000C 00020F UPB100H 4PT5S0000C 00025F UPB100H 4PT5S0000C 00030F UPB100H 4PT5S0000C 00032F UPB100H 4PT5S0000C 00040F UPB100H 4PT5S0000C 00050F UPB100H 4PT5S0000C 00060F UPB100H 4PT5S0000C 00063F UPB100H 4PT5S0000C 00075F UPB100H 4PT5S0000C 00080F UPB100H 4PT5S0000C 00100F UPB100H 4PT5S0000C 00125F UPB100L 4PT5S0000C 00015F UPB100L 4PT5S0000C 00016F UPB100L 4PT5S0000C 00020F UPB100L 4PT5S0000C 00025F UPB100L 4PT5S0000C 00030F UPB100L 4PT5S0000C 00032F UPB100L 4PT5S0000C 00040F UPB100L 4PT5S0000C 00050F UPB100L 4PT5S0000C 00060F UPB100L 4PT5S0000C 00063F UPB100L 4PT5S0000C 00075F UPB100L 4PT5S0000C 00080F UPB100L 4PT5S0000C 00100F UPB100L 4PT5S0000C 00125F UPB100X 4PT5S0000C 00015F UPB100X 4PT5S0000C 00016F UPB100X 4PT5S0000C 00020F UPB100X 4PT5S0000C 00025F UPB100X 4PT5S0000C 00030F UPB100X 4PT5S0000C 00032F UPB100X 4PT5S0000C 00040F UPB100X 4PT5S0000C 00050F UPB100X 4PT5S0000C 00060F UPB100X 4PT5S0000C 00063F UPB100X 4PT5S0000C 00075F UPB100X 4PT5S0000C 00080F UPB100X 4PT5S0000C 00100F UPB100X 4PT5S0000C 00125F 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Molded Case Circuit Breaker_ 95 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UPB type / 160AF | •UPB160S 85kA •UPB160H 100kA •UPB160L 130kA •UPB160X 150kA UPB160S UPB160H UPB160L UPB160X Number of poles (P) 3, 4 Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection overload, inst., short-circuit Thermal magnetic type 100,125,160 Rated current (A) Electronic type 63-160 Rated insulation voltage [Ui] (V) AC750 Rating AC690 Rated operational voltage [Ue] (V) DC500 1) Rated impulse withstand voltage [Uimp] (kV) 8 AC660/690V, 50-60Hz 10 1025 25 Rated AC480/500V, 50-60Hz 50 6585 85 short-circuit Ultimate AC440/460V, 50-60Hz 65 85100 150 breaking [Icu] AC380/415V, 50-60Hz 85 100130 150 capacity (kA r.m.s.) AC220/240V, 50-60Hz 100 130150 200 1) 1) 1) 1) DC250V 65 85 100 50 IEC 60947-2 1) 1) 1) 1) DC125V 65 100 100 100 K 60947-2 Service [Ics] % of [Icu] 100 Fixed thermal, ○ Fixed instantaneous INST 10×In Thermal Adjustable thermal, LTD (0.8-0.9-1)×In magnetic Fixed instantaneous INST 10×In Adjustable thermal, LTD (0.8-0.9-1)×In Trip Adjustable instantaneous INST (5-6-7-8-9-10)×In mechanism & Protection Long time delay LTD 63,70,80,90,100,110,125,140,160 characteristics Short time delay STD (NON-2-3-4-5-6-7-8-9-10)×Ir Electronic Instantaneous INST 11×In Pre-trip alarm PTA 0.9×Ir Pick-up LED ○ Direct mounting by screw ○ Mounting Both line & load side ○2) for Plug-in Switchboard Line side only ○2) Screw ○ Terminal connection Bus bar ○ Durability Mechanical operation 25,000 (times) Electrical operation 10,000 a Width 105/140 d a c Dimensions b Height 165 3/4P b (mm) c Depth 86.5 d 112 2.0/2.4 Weight (kg, breaker only) 3/4P ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) DC is not applicable for electronic breaker. 2) Available for 3P breaker ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip 1) Under voltage trip 2) 96 1C, right-hand-side AUX 12UP R1 1C, left-hand-side ALT 12UP L1 DC24V SHT 12UP A DC24V ✽UVT 12UP J DC100-110V SHT 12UP C DC100-110V ✽UVT 12UP L AC100-120V SHT 12UP F AC100-120V ✽UVT 12UP N ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. AC200-230V SHT 12UP H AC200-230V ✽UVT 12UP P AC380-415V SHT 12UP B AC380-415V ✽UVT 12UP Q AC440-480V SHT 12UP D AC440-480V ✽UVT 12UP R MCCB •Operating Power supply direction Upper Right Left S type TFG 12UPS U4 TFG 12UPS R4 TFG 12UPS L4 Operating Surface L type TFG 12UPL U4 TFG 12UPL L4 handle 1) S type TFH 12UPS Extended L type TFH 12UPL DC24V AC/DC110V AC/DC220V Motor operator 2) MOT 12UP DC24 MOT 12UP ADC110 MOT 12UP ADC220 3 pole 4 pole Mechanical interlock MIF 12UP 3 MIF 12UP 4 PLD 12UP Padlock plate 3) ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting Plug-in 1) Structure Mounting base Connection 6C contact block 2) 12C contact For both line & load side TDM 12NEP CBM 26NE 6 CBM 26NE 63) For line side only TDM 12NEF - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 3) 2EA shall be ordered for 12C contact. •Terminal Terminal bus bar Cage terminal block Terminal cover 1) Interpole barrier 2) 3 pole (6EA/SET) 4 pole (8EA/SET) 3EA/SET 4EA/SET 3 pole 4 pole 4EA/SET TBB 12NE 3 TBB 12NE 4 CTB 12UP 3S CTB 12UP 4S TCF 12UP 3 TCF 12UP 4 TQQ 12NE 3P ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit •Electronic - LTD, STD, INST trip & PTA Model / Breaking capacity at AC380/415V UPB160S 85kA Rated current 3 pole Code 4 pole Unit (EA) Code Unit (EA) 160A UPB160S 3PESS0000X 00160 8 UPB160S 4PESS0000X 00160 6 UPB160H 100kA 160A UPB160H 3PESS0000X 00160 8 UPB160H 4PESS0000X 00160 6 UPB160L 130kA 160A UPB160L 3PESS0000X 00160 8 UPB160L 4PESS0000X 00160 6 UPB160X 150kA 160A UPB160X 3PESS0000X 00160 8 UPB160X 4PESS0000X 00160 6 UPB160S 85kA 160A UPB160S 3PESS0000Y 00160 8 UPB160S 4PESS0000Y 00160 6 UPB160H 100kA 160A UPB160H 3PESS0000Y 00160 8 UPB160H 4PESS0000Y 00160 6 UPB160L 130kA 160A UPB160L 3PESS0000Y 00160 8 UPB160L 4PESS0000Y 00160 6 UPB160X 150kA 160A UPB160X 3PESS0000Y 00160 8 UPB160X 4PESS0000Y 00160 6 Specification Category Screw type terminal connection, No option, 50Hz MCCB/M3 Screw type terminal connection, No option, 60Hz Molded Case Circuit Breaker_ 97 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V UPB160S 85kA Rated current 3 pole Code 4 pole Unit (EA) Code Unit (EA) 100A UPB160S 3PT4S0000C 00100 8 UPB160S 4PT4S0000C 00100 6 125A UPB160S 3PT4S0000C 00125 8 UPB160S 4PT4S0000C 00125 6 160A UPB160S 3PT4S0000C 00160 8 UPB160S 4PT4S0000C 00160 6 UPB160H 100kA 100A UPB160H 3PT4S0000C 00100 8 UPB160H 4PT4S0000C 00100 6 125A UPB160H 3PT4S0000C 00125 8 UPB160H 4PT4S0000C 00125 6 160A UPB160H 3PT4S0000C 00160 8 UPB160H 4PT4S0000C 00160 6 UPB160L 130kA 100A UPB160L 3PT4S0000C 00100 8 UPB160L 4PT4S0000C 00100 6 125A UPB160L 3PT4S0000C 00125 8 UPB160L 4PT4S0000C 00125 6 160A UPB160L 3PT4S0000C 00160 8 UPB160L 4PT4S0000C 00160 6 UPB160X 150kA 100A UPB160X 3PT4S0000C 00100 8 UPB160X 4PT4S0000C 00100 6 125A UPB160X 3PT4S0000C 00125 8 UPB160X 4PT4S0000C 00125 6 160A UPB160X 3PT4S0000C 00160 8 UPB160X 4PT4S0000C 00160 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V Rated current 3 pole Code 4 pole Unit (EA) Code Unit (EA) UPB160S 85kA 100A UPB160S 3PT5S0000C 00100 8 UPB160S 4PT5S0000C 00100 6 125A UPB160S 3PT5S0000C 00125 8 UPB160S 4PT5S0000C 00125 6 160A UPB160S 3PT5S0000C 00160 8 UPB160S 4PT5S0000C 00160 6 UPB160H 100kA 100A UPB160H 3PT5S0000C 00100 8 UPB160H 4PT5S0000C 00100 6 125A UPB160H 3PT5S0000C 00125 8 UPB160H 4PT5S0000C 00125 6 160A UPB160H 3PT5S0000C 00160 8 UPB160H 4PT5S0000C 00160 6 UPB160L 130kA 100A UPB160L 3PT5S0000C 00100 8 UPB160L 4PT5S0000C 00100 6 125A UPB160L 3PT5S0000C 00125 8 UPB160L 4PT5S0000C 00125 6 160A UPB160L 3PT5S0000C 00160 8 UPB160L 4PT5S0000C 00160 6 UPB160X 150kA 100A UPB160X 3PT5S0000C 00100 8 UPB160X 4PT5S0000C 00100 6 125A UPB160X 3PT5S0000C 00125 8 UPB160X 4PT5S0000C 00125 6 160A UPB160X 3PT5S0000C 00160 8 UPB160X 4PT5S0000C 00160 6 •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V 98 3 pole 4 pole Rated current Code Unit (EA) UPB160S 85kA 100A UPB160S 3PT4S0000C 00100F 8 UPB160S 4PT4S0000C 00100F 6 125A UPB160S 3PT4S0000C 00125F 8 UPB160S 4PT4S0000C 00125F 6 160A UPB160S 3PT4S0000C 00160F 8 UPB160S 4PT4S0000C 00160F 6 UPB160H 100kA 100A UPB160H 3PT4S0000C 00100F 8 UPB160H 4PT4S0000C 00100F 6 125A UPB160H 3PT4S0000C 00125F 8 UPB160H 4PT4S0000C 00125F 6 160A UPB160H 3PT4S0000C 00160F 8 UPB160H 4PT4S0000C 00160F 6 UPB160L 130kA 100A UPB160L 3PT4S0000C 00100F 8 UPB160L 4PT4S0000C 00100F 6 125A UPB160L 3PT4S0000C 00125F 8 UPB160L 4PT4S0000C 00125F 6 160A UPB160L 3PT4S0000C 00160F 8 UPB160L 4PT4S0000C 00160F 6 UPB160X 150kA 100A UPB160X 3PT4S0000C 00100F 8 UPB160X 4PT4S0000C 00100F 6 125A UPB160X 3PT4S0000C 00125F 8 UPB160X 4PT4S0000C 00125F 6 160A UPB160X 3PT4S0000C 00160F 8 UPB160X 4PT4S0000C 00160F 6 Code Unit (EA) MCCB 50℃ Model / Breaking capacity at AC380/415V 3 pole 4 pole Rated current Code Unit (EA) UPB160S 85kA 100A UPB160S 3PT5S0000C 00100F 8 UPB160S 4PT5S0000C 00100F 6 125A UPB160S 3PT5S0000C 00125F 8 UPB160S 4PT5S0000C 00125F 6 160A UPB160S 3PT5S0000C 00160F 8 UPB160S 4PT5S0000C 00160F 6 UPB160H 100kA 100A UPB160H 3PT5S0000C 00100F 8 UPB160H 4PT5S0000C 00100F 6 125A UPB160H 3PT5S0000C 00125F 8 UPB160H 4PT5S0000C 00125F 6 160A UPB160H 3PT5S0000C 00160F 8 UPB160H 4PT5S0000C 00160F 6 UPB160L 130kA 100A UPB160L 3PT5S0000C 00100F 8 UPB160L 4PT5S0000C 00100F 6 125A UPB160L 3PT5S0000C 00125F 8 UPB160L 4PT5S0000C 00125F 6 160A UPB160L 3PT5S0000C 00160F 8 UPB160L 4PT5S0000C 00160F 6 UPB160X 150kA 100A UPB160X 3PT5S0000C 00100F 8 UPB160X 4PT5S0000C 00100F 6 125A UPB160X 3PT5S0000C 00125F 8 UPB160X 4PT5S0000C 00125F 6 160A UPB160X 3PT5S0000C 00160F 8 UPB160X 4PT5S0000C 00160F 6 Code Unit (EA) Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 •Adjustable thermal & adjustable instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V 3 pole 4 pole Rated current Code Unit (EA) UPB160S 85kA 100A UPB160S 3PT4S0000C 00100H 8 UPB160S 4PT4S0000C 00100H 6 125A UPB160S 3PT4S0000C 00125H 8 UPB160S 4PT4S0000C 00125H 6 160A UPB160S 3PT4S0000C 00160H 8 UPB160S 4PT4S0000C 00160H 6 UPB160H 100kA 100A UPB160H 3PT4S0000C 00100H 8 UPB160H 4PT4S0000C 00100H 6 125A UPB160H 3PT4S0000C 00125H 8 UPB160H 4PT4S0000C 00125H 6 160A UPB160H 3PT4S0000C 00160H 8 UPB160H 4PT4S0000C 00160H 6 UPB160L 130kA 100A UPB160L 3PT4S0000C 00100H 8 UPB160L 4PT4S0000C 00100H 6 125A UPB160L 3PT4S0000C 00125H 8 UPB160L 4PT4S0000C 00125H 6 160A UPB160L 3PT4S0000C 00160H 8 UPB160L 4PT4S0000C 00160H 6 UPB160X 150kA 100A UPB160X 3PT4S0000C 00100H 8 UPB160X 4PT4S0000C 00100H 6 125A UPB160X 3PT4S0000C 00125H 8 UPB160X 4PT4S0000C 00125H 6 160A UPB160X 3PT4S0000C 00160H 8 UPB160X 4PT4S0000C 00160H 6 Rated current Code Unit (EA) UPB160S 85kA 100A UPB160S 3PT5S0000C 00100H 8 UPB160S 4PT5S0000C 00100H 6 125A UPB160S 3PT5S0000C 00125H 8 UPB160S 4PT5S0000C 00125H 6 160A UPB160S 3PT5S0000C 00160H 8 UPB160S 4PT5S0000C 00160H 6 UPB160H 100kA 100A UPB160H 3PT5S0000C 00100H 8 UPB160H 4PT5S0000C 00100H 6 125A UPB160H 3PT5S0000C 00125H 8 UPB160H 4PT5S0000C 00125H 6 160A UPB160H 3PT5S0000C 00160H 8 UPB160H 4PT5S0000C 00160H 6 UPB160L 130kA 100A UPB160L 3PT5S0000C 00100H 8 UPB160L 4PT5S0000C 00100H 6 125A UPB160L 3PT5S0000C 00125H 8 UPB160L 4PT5S0000C 00125H 6 160A UPB160L 3PT5S0000C 00160H 8 UPB160L 4PT5S0000C 00160H 6 UPB160X 150kA 100A UPB160X 3PT5S0000C 00100H 8 UPB160X 4PT5S0000C 00100H 6 125A UPB160X 3PT5S0000C 00125H 8 UPB160X 4PT5S0000C 00125H 6 160A UPB160X 3PT5S0000C 00160H 8 UPB160X 4PT5S0000C 00160H 6 Code Unit (EA) 50℃ Model / Breaking capacity at AC380/415V 3 pole 4 pole Code Unit (EA) Molded Case Circuit Breaker_ 99 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UPB type / 250AF | •UPB250S 85kA •UPB250H 100kA •UPB250L 130kA •UPB250X 150kA UPB250S UPB250H UPB250L UPB250X Number of poles (P) Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection overload, inst., short-circuit Thermal magnetic type 125,150,160,175,200,225,250 Rated current (A) Rating Electronic type Rated insulation voltage [Ui] (V) 3, 4 100-250 AC750 AC690 Rated operational voltage [Ue] (V) DC500 1) Rated impulse withstand voltage [Uimp] (kV) 8 AC660/690V, 50-60Hz 10 1025 Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) AC480/500V, 50-60Hz 50 6585 85 AC440/460V, 50-60Hz 65 85100 150 AC380/415V, 50-60Hz 85 100130 150 AC220/240V, 50-60Hz 100 130150 200 IEC 60947-2 K 60947-2 DC250V 50 1) 65 85 100 1) DC125V 65 1) 100 100 Service [Ics] % of [Icu] 1) 1) 1) 1) 100 1) 100 Fixed thermal, Fixed instantaneous INST 10×In Thermal magnetic Adjustable thermal, LTD (0.8-0.9-1)×In Fixed instantaneous INST 10×In ○ Adjustable thermal, Trip Adjustable instantaneous mechanism & Protection Long time delay characteristics Short time delay LTD (0.8-0.9-1)×In INST (5-6-7-8-9-10)×In LTD Electronic Instantaneous INST 11×In Pre-trip alarm PTA 0.9×Ir Pick-up LED STD Durability (times) (NON-2-3-4-5-6-7-8-9-10)×Ir ○ Both line & load side ○2) ○2) for Plug-in Switchboard Line side only Terminal connection 100,110,125,140,160,175,200,225,250 ○ Direct mounting by screw Mounting Screw ○ Bus bar ○ Mechanical operation 25,000 Electrical operation 10,000 a Width Dimensions 3/4P b (mm) b Height 165 c Depth 86.5 d 112 Weight (kg, breaker only) 3/4P 2.0/2.4 a d c 105/140 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) DC is not applicable for electronic breaker. 2) Available for 3P breaker 100 25 MCCB ■ Accessories •Signal 1C, right-hand-side Auxiliary switch AUX 12UP R1 1C, left-hand-side Trip alarm switch ALT 12UP L1 Shunt trip 1) Under voltage trip 2) DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V SHT 12UP A SHT 12UP C SHT 12UP F SHT 12UP H SHT 12UP B SHT 12UP D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V ✽UVT 12UP J ✽UVT 12UP L ✽UVT 12UP N ✽UVT 12UP P ✽UVT 12UP Q ✽UVT 12UP R ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. •Operating Upper Power supply direction S type Operating Surface L type handle 1) S type Extended L type Right TFG 12UPS U4 TFG 12UPS R4 TFG 12UPS L4 TFG 12UPL U4 - TFG 12UPL L4 TFH 12UPS TFH 12UPL DC24V Motor operator 2) AC/DC110VAC/DC220V MOT 12UP DC24 Mechanical interlock Padlock plate 3) Left MOT 12UP ADC110MOT 12UP ADC220 3 pole MIF 12UP 3 4 pole MIF 12UP 4 PLD 12UP ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting Structure Plug-in 1) For both line & load side For line side only TDM 12NEP TDM 12NEF Connection 6C contact CBM 26NE 6 - block 2) CBM 26NE 63) - Mounting base 12C contact ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 3) 2EA shall be ordered for 12C contact. •Terminal Terminal bus bar Cage terminal block Terminal cover 1) Interpole barrier 2) 3 pole (6EA/SET) TBB 12NE 3 4 pole (8EA/SET) TBB 12NE 4 3EA/SET CTB 12UP 3S 4EA/SET CTB 12UP 4S 3 pole TCF 12UP 3 4 pole TCF 12UP 4 4EA/SET TQQ 12NE 3P ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA Molded Case Circuit Breaker_ 101 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Electronic - LTD, STD, INST trip & PTA 102 Unit (EA) 4 pole Code Unit (EA) UPB250S 3PESS0000X 00250 8 UPB250S 4PESS0000X 00250 6 250A UPB250H 3PESS0000X 00250 8 UPB250H 4PESS0000X 00250 6 UPB250L 130kA 250A UPB250L 3PESS0000X 00250 8 UPB250L 4PESS0000X 00250 6 UPB250X 150kA 250A UPB250X 3PESS0000X 00250 8 UPB250X 4PESS0000X 00250 6 UPB250S 85kA 250A UPB250S 3PESS0000Y 00250 8 UPB250S 4PESS0000Y 00250 6 UPB250H 100kA 250A UPB250H 3PESS0000Y 00250 8 UPB250H 4PESS0000Y 00250 6 UPB250L 130kA 250A UPB250L 3PESS0000Y 00250 8 UPB250L 4PESS0000Y 00250 6 UPB250X 150kA 250A UPB250X 3PESS0000Y 00250 8 UPB250X 4PESS0000Y 00250 6 Model / Breaking capacity at AC380/415V Rated current UPB250S 85kA 250A UPB250H 100kA 3 pole Code Specification Category Screw type terminal connection, No option, 50Hz MCCB /M3 Screw type terminal connection, No option, 60Hz MCCB ■ Standard order code and unit •Fixed thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current UPB250S 85kA 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A UPB250H 100kA UPB250L 130kA UPB250X 150kA 3 pole Code UPB250S 3PT4S0000C 00125 UPB250S 3PT4S0000C 00150 UPB250S 3PT4S0000C 00160 UPB250S 3PT4S0000C 00175 UPB250S 3PT4S0000C 00200 UPB250S 3PT4S0000C 00225 UPB250S 3PT4S0000C 00250 UPB250H 3PT4S0000C 00125 UPB250H 3PT4S0000C 00150 UPB250H 3PT4S0000C 00160 UPB250H 3PT4S0000C 00175 UPB250H 3PT4S0000C 00200 UPB250H 3PT4S0000C 00225 UPB250H 3PT4S0000C 00250 UPB250L 3PT4S0000C 00125 UPB250L 3PT4S0000C 00150 UPB250L 3PT4S0000C 00160 UPB250L 3PT4S0000C 00175 UPB250L 3PT4S0000C 00200 UPB250L 3PT4S0000C 00225 UPB250L 3PT4S0000C 00250 UPB250X 3PT4S0000C 00125 UPB250X 3PT4S0000C 00150 UPB250X 3PT4S0000C 00160 UPB250X 3PT4S0000C 00175 UPB250X 3PT4S0000C 00200 UPB250X 3PT4S0000C 00225 UPB250X 3PT4S0000C 00250 Unit (EA) 4 pole Code Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 UPB250S 4PT4S0000C 00125 UPB250S 4PT4S0000C 00150 UPB250S 4PT4S0000C 00160 UPB250S 4PT4S0000C 00175 UPB250S 4PT4S0000C 00200 UPB250S 4PT4S0000C 00225 UPB250S 4PT4S0000C 00250 UPB250H 4PT4S0000C 00125 UPB250H 4PT4S0000C 00150 UPB250H 4PT4S0000C 00160 UPB250H 4PT4S0000C 00175 UPB250H 4PT4S0000C 00200 UPB250H 4PT4S0000C 00225 UPB250H 4PT4S0000C 00250 UPB250L 4PT4S0000C 00125 UPB250L 4PT4S0000C 00150 UPB250L 4PT4S0000C 00160 UPB250L 4PT4S0000C 00175 UPB250L 4PT4S0000C 00200 UPB250L 4PT4S0000C 00225 UPB250L 4PT4S0000C 00250 UPB250X 4PT4S0000C 00125 UPB250X 4PT4S0000C 00150 UPB250X 4PT4S0000C 00160 UPB250X 4PT4S0000C 00175 UPB250X 4PT4S0000C 00200 UPB250X 4PT4S0000C 00225 UPB250X 4PT4S0000C 00250 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Unit (EA) 4 pole Code Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 UPB250S 4PT5S0000C 00125 UPB250S 4PT5S0000C 00150 UPB250S 4PT5S0000C 00160 UPB250S 4PT5S0000C 00175 UPB250S 4PT5S0000C 00200 UPB250S 4PT5S0000C 00225 UPB250S 4PT5S0000C 00250 UPB250H 4PT5S0000C 00125 UPB250H 4PT5S0000C 00150 UPB250H 4PT5S0000C 00160 UPB250H 4PT5S0000C 00175 UPB250H 4PT5S0000C 00200 UPB250H 4PT5S0000C 00225 UPB250H 4PT5S0000C 00250 UPB250L 4PT5S0000C 00125 UPB250L 4PT5S0000C 00150 UPB250L 4PT5S0000C 00160 UPB250L 4PT5S0000C 00175 UPB250L 4PT5S0000C 00200 UPB250L 4PT5S0000C 00225 UPB250L 4PT5S0000C 00250 UPB250X 4PT5S0000C 00125 UPB250X 4PT5S0000C 00150 UPB250X 4PT5S0000C 00160 UPB250X 4PT5S0000C 00175 UPB250X 4PT5S0000C 00200 UPB250X 4PT5S0000C 00225 UPB250X 4PT5S0000C 00250 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V Rated current UPB250S 85kA 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A UPB250H 100kA UPB250L 130kA UPB250X 150kA 3 pole Code UPB250S 3PT5S0000C 00125 UPB250S 3PT5S0000C 00150 UPB250S 3PT5S0000C 00160 UPB250S 3PT5S0000C 00175 UPB250S 3PT5S0000C 00200 UPB250S 3PT5S0000C 00225 UPB250S 3PT5S0000C 00250 UPB250H 3PT5S0000C 00125 UPB250H 3PT5S0000C 00150 UPB250H 3PT5S0000C 00160 UPB250H 3PT5S0000C 00175 UPB250H 3PT5S0000C 00200 UPB250H 3PT5S0000C 00225 UPB250H 3PT5S0000C 00250 UPB250L 3PT5S0000C 00125 UPB250L 3PT5S0000C 00150 UPB250L 3PT5S0000C 00160 UPB250L 3PT5S0000C 00175 UPB250L 3PT5S0000C 00200 UPB250L 3PT5S0000C 00225 UPB250L 3PT5S0000C 00250 UPB250X 3PT5S0000C 00125 UPB250X 3PT5S0000C 00150 UPB250X 3PT5S0000C 00160 UPB250X 3PT5S0000C 00175 UPB250X 3PT5S0000C 00200 UPB250X 3PT5S0000C 00225 UPB250X 3PT5S0000C 00250 Molded Case Circuit Breaker_ 103 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit •Adjustable thermal & fixed instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current UPB250S 85kA 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A UPB250H 100kA UPB250L 130kA UPB250X 150kA 3 pole Code UPB250S 3PT4S0000C 00125F UPB250S 3PT4S0000C 00150F UPB250S 3PT4S0000C 00160F UPB250S 3PT4S0000C 00175F UPB250S 3PT4S0000C 00200F UPB250S 3PT4S0000C 00225F UPB250S 3PT4S0000C 00250F UPB250H 3PT4S0000C 00125F UPB250H 3PT4S0000C 00150F UPB250H 3PT4S0000C 00160F UPB250H 3PT4S0000C 00175F UPB250H 3PT4S0000C 00200F UPB250H 3PT4S0000C 00225F UPB250H 3PT4S0000C 00250F UPB250L 3PT4S0000C 00125F UPB250L 3PT4S0000C 00150F UPB250L 3PT4S0000C 00160F UPB250L 3PT4S0000C 00175F UPB250L 3PT4S0000C 00200F UPB250L 3PT4S0000C 00225F UPB250L 3PT4S0000C 00250F UPB250X 3PT4S0000C 00125F UPB250X 3PT4S0000C 00150F UPB250X 3PT4S0000C 00160F UPB250X 3PT4S0000C 00175F UPB250X 3PT4S0000C 00200F UPB250X 3PT4S0000C 00225F UPB250X 3PT4S0000C 00250F Unit (EA) 4 pole Code Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 UPB250S 4PT4S0000C 00125F UPB250S 4PT4S0000C 00150F UPB250S 4PT4S0000C 00160F UPB250S 4PT4S0000C 00175F UPB250S 4PT4S0000C 00200F UPB250S 4PT4S0000C 00225F UPB250S 4PT4S0000C 00250F UPB250H 4PT4S0000C 00125F UPB250H 4PT4S0000C 00150F UPB250H 4PT4S0000C 00160F UPB250H 4PT4S0000C 00175F UPB250H 4PT4S0000C 00200F UPB250H 4PT4S0000C 00225F UPB250F 4PT4S0000C 00250F UPB250L 4PT4S0000C 00125F UPB250L 4PT4S0000C 00150F UPB250L 4PT4S0000C 00160F UPB250L 4PT4S0000C 00175F UPB250L 4PT4S0000C 00200F UPB250L 4PT4S0000C 00225F UPB250L 4PT4S0000C 00250F UPB250X 4PT4S0000C 00125F UPB250X 4PT4S0000C 00150F UPB250X 4PT4S0000C 00160F UPB250X 4PT4S0000C 00175F UPB250X 4PT4S0000C 00200F UPB250X 4PT4S0000C 00225F UPB250X 4PT4S0000C 00250F 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Unit (EA) 4 pole Code Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 UPB250S 4PT5S0000C 00125F UPB250S 4PT5S0000C 00150F UPB250S 4PT5S0000C 00160F UPB250S 4PT5S0000C 00175F UPB250S 4PT5S0000C 00200F UPB250S 4PT5S0000C 00225F UPB250S 4PT5S0000C 00250F UPB250H 4PT5S0000C 00125F UPB250H 4PT5S0000C 00150F UPB250H 4PT5S0000C 00160F UPB250H 4PT5S0000C 00175F UPB250H 4PT5S0000C 00200F UPB250H 4PT5S0000C 00225F UPB250F 4PT5S0000C 00250F UPB250L 4PT5S0000C 00125F UPB250L 4PT5S0000C 00150F UPB250L 4PT5S0000C 00160F UPB250L 4PT5S0000C 00175F UPB250L 4PT5S0000C 00200F UPB250L 4PT5S0000C 00225F UPB250L 4PT5S0000C 00250F UPB250X 4PT5S0000C 00125F UPB250X 4PT5S0000C 00150F UPB250X 4PT5S0000C 00160F UPB250X 4PT5S0000C 00175F UPB250X 4PT5S0000C 00200F UPB250X 4PT5S0000C 00225F UPB250X 4PT5S0000C 00250F 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V Rated current UPB250S 85kA 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A UPB250H 100kA UPB250L 130kA UPB250X 150kA 104 3 pole Code UPB250S 3PT5S0000C 00125F UPB250S 3PT5S0000C 00150F UPB250S 3PT5S0000C 00160F UPB250S 3PT5S0000C 00175F UPB250S 3PT5S0000C 00200F UPB250S 3PT5S0000C 00225F UPB250S 3PT5S0000C 00250F UPB250H 3PT5S0000C 00125F UPB250H 3PT5S0000C 00150F UPB250H 3PT5S0000C 00160F UPB250H 3PT5S0000C 00175F UPB250H 3PT5S0000C 00200F UPB250H 3PT5S0000C 00225F UPB250H 3PT5S0000C 00250F UPB250L 3PT5S0000C 00125F UPB250L 3PT5S0000C 00150F UPB250L 3PT5S0000C 00160F UPB250L 3PT5S0000C 00175F UPB250L 3PT5S0000C 00200F UPB250L 3PT5S0000C 00225F UPB250L 3PT5S0000C 00250F UPB250X 3PT5S0000C 00125F UPB250X 3PT5S0000C 00150F UPB250X 3PT5S0000C 00160F UPB250X 3PT5S0000C 00175F UPB250X 3PT5S0000C 00200F UPB250X 3PT5S0000C 00225F UPB250X 3PT5S0000C 00250F MCCB ■ Standard order code and unit •Adjustable thermal & adjustable instantaneous / Thermal magnetic trip 40/45℃ Model / Breaking capacity at AC380/415V Rated current UPB250S 85kA 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A UPB250H 100kA UPB250L 130kA UPB250X 150kA 3 pole Code UPB250S 3PT4S0000C 00125H UPB250S 3PT4S0000C 00150H UPB250S 3PT4S0000C 00160H UPB250S 3PT4S0000C 00175H UPB250S 3PT4S0000C 00200H UPB250S 3PT4S0000C 00225H UPB250S 3PT4S0000C 00250H UPB250H 3PT4S0000C 00125H UPB250H 3PT4S0000C 00150H UPB250H 3PT4S0000C 00160H UPB250H 3PT4S0000C 00175H UPB250H 3PT4S0000C 00200H UPB250H 3PT4S0000C 00225H UPB250H 3PT4S0000C 00250H UPB250L 3PT4S0000C 00125H UPB250L 3PT4S0000C 00150H UPB250L 3PT4S0000C 00160H UPB250L 3PT4S0000C 00175H UPB250L 3PT4S0000C 00200H UPB250L 3PT4S0000C 00225H UPB250L 3PT4S0000C 00250H UPB250X 3PT4S0000C 00125H UPB250X 3PT4S0000C 00150H UPB250X 3PT4S0000C 00160H UPB250X 3PT4S0000C 00175H UPB250X 3PT4S0000C 00200H UPB250X 3PT4S0000C 00225H UPB250X 3PT4S0000C 00250H Unit (EA) 4 pole Code Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 UPB250S 4PT4S0000C 00125H UPB250S 4PT4S0000C 00150H UPB250S 4PT4S0000C 00160H UPB250S 4PT4S0000C 00175H UPB250S 4PT4S0000C 00200H UPB250S 4PT4S0000C 00225H UPB250S 4PT4S0000C 00250H UPB250H 4PT4S0000C 00125H UPB250H 4PT4S0000C 00150H UPB250H 4PT4S0000C 00160H UPB250H 4PT4S0000C 00175H UPB250H 4PT4S0000C 00200H UPB250H 4PT4S0000C 00225H UPB250H 4PT4S0000C 00250H UPB250L 4PT4S0000C 00125H UPB250L 4PT4S0000C 00150H UPB250L 4PT4S0000C 00160H UPB250L 4PT4S0000C 00175H UPB250L 4PT4S0000C 00200H UPB250L 4PT4S0000C 00225H UPB250L 4PT4S0000C 00250H UPB250X 4PT4S0000C 00125H UPB250X 4PT4S0000C 00150H UPB250X 4PT4S0000C 00160H UPB250X 4PT4S0000C 00175H UPB250X 4PT4S0000C 00200H UPB250X 4PT4S0000C 00225H UPB250X 4PT4S0000C 00250H 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Unit (EA) 4 pole Code Unit (EA) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 UPB250S 4PT5S0000C 00125H UPB250S 4PT5S0000C 00150H UPB250S 4PT5S0000C 00160H UPB250S 4PT5S0000C 00175H UPB250S 4PT5S0000C 00200H UPB250S 4PT5S0000C 00225H UPB250S 4PT5S0000C 00250H UPB250H 4PT5S0000C 00125H UPB250H 4PT5S0000C 00150H UPB250H 4PT5S0000C 00160H UPB250H 4PT5S0000C 00175H UPB250H 4PT5S0000C 00200H UPB250H 4PT5S0000C 00225H UPB250H 4PT5S0000C 00250H UPB250L 4PT5S0000C 00125H UPB250L 4PT5S0000C 00150H UPB250L 4PT5S0000C 00160H UPB250L 4PT5S0000C 00175H UPB250L 4PT5S0000C 00200H UPB250L 4PT5S0000C 00225H UPB250L 4PT5S0000C 00250H UPB250X 4PT5S0000C 00125H UPB250X 4PT5S0000C 00150H UPB250X 4PT5S0000C 00160H UPB250X 4PT5S0000C 00175H UPB250X 4PT5S0000C 00200H UPB250X 4PT5S0000C 00225H UPB250X 4PT5S0000C 00250H 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M2 50℃ Model / Breaking capacity at AC380/415V Rated current UPB250S 85kA 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A 125A 150A 160A 175A 200A 225A 250A UPB250H 100kA UPB250L 130kA UPB250X 150kA 3 pole Code UPB250S 3PT5S0000C 00125H UPB250S 3PT5S0000C 00150H UPB250S 3PT5S0000C 00160H UPB250S 3PT5S0000C 00175H UPB250S 3PT5S0000C 00200H UPB250S 3PT5S0000C 00225H UPB250S 3PT5S0000C 00250H UPB250H 3PT5S0000C 00125H UPB250H 3PT5S0000C 00150H UPB250H 3PT5S0000C 00160H UPB250H 3PT5S0000C 00175H UPB250H 3PT5S0000C 00200H UPB250H 3PT5S0000C 00225H UPB250H 3PT5S0000C 00250H UPB250L 3PT5S0000C 00125H UPB250L 3PT5S0000C 00150H UPB250L 3PT5S0000C 00160H UPB250L 3PT5S0000C 00175H UPB250L 3PT5S0000C 00200H UPB250L 3PT5S0000C 00225H UPB250L 3PT5S0000C 00250H UPB250X 3PT5S0000C 00125H UPB250X 3PT5S0000C 00150H UPB250X 3PT5S0000C 00160H UPB250X 3PT5S0000C 00175H UPB250X 3PT5S0000C 00200H UPB250X 3PT5S0000C 00225H UPB250X 3PT5S0000C 00250H Molded Case Circuit Breaker_ 105 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UPB type / 400AF | •UPB400S 85kA •UPB400H 100kA •UPB400L 130kA •UPB400X 150kA UPB400S UPB400H UPB400L UPB400X 3, 4 Number of poles (P) IP20 Degree of protection (with terminal cover) A Utilization category Suitability of isolation ○ Protection overload, inst., short-circuit Rated current (A) 200-400 Rated insulation voltage [Ui] (V) AC750 Rating Rated operational voltage [Ue] (V) AC690 Rated impulse withstand voltage [Uimp] (kV) 8 AC660/690V, 50-60Hz 10 1025 25 Rated Ultimate AC480/500V, 50-60Hz short-circuit 50 6585 85 breaking [Icu] AC440/460V, 50-60Hz 65 85100 150 capacity (kA r.m.s.) AC380/415V, 50-60Hz 85 100130 150 AC220/240V, 50-60Hz IEC 60947-2 100 130150 200 K 60947-2 Service [Ics] % of [Icu] 100 Long time delay LTD (0.5-1) 1) ×In (15 setting) Short time delay STD (2-4-6-8-10)×Ir Trip Instantaneous INST (3-6-8-10-11)×In mechanism Electronic Ground fault trip GFT (0.2-0.3-0.4)×In & Protection Pre-trip alarm PTA 0.9×Ir characteristics I2T lamp ○ Pick-up LED ○ Direct mounting by screw ○ Mounting Both line & load side ○2) for Plug-in Switchboard Line side only ○2) Screw ○ Terminal connection Bus bar ○ Durability Mechanical operation 20,000 (times) Electrical operation 6,000 a Width d 140/185 a c Dimensions b Height 255 3/4P b (mm) c Depth 117 d 159.5 Weight (kg, breaker only) 3/4P 6.0/7.8 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1) 2) Available for 3P breaker ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip 1) Under voltage trip 2) 1C, left-hand-side AUX 46UP L1 1C, right-hand-side ALT 46UP R1 DC24V SHT 46UP A DC24V ✽UVT 46UP J DC100-110V SHT 46UP C DC100-110V ✽UVT 46UP L AC100-120V SHT 46UP F AC100-120V ✽UVT 46UP N ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. 106 AC200-230V SHT 46UP H AC200-230V ✽UVT 46UP P AC380-415V SHT 46UP B AC380-415V ✽UVT 46UP Q AC440-480V SHT 46UP D AC440-480V ✽UVT 46UP R MCCB •Operating Power supply direction Upper RightLeft Operating Surface S type TFG 46UPS U4 TFG 46UPS R4 TFG 46UPS L4 handle 1) Extended S type TFH 46UPS DC24V AC/DC110VAC/DC220V Motor operator 2) MOT 46NE DC24 MOT 46NE ADC110MOT 46NE ADC220 3 pole 4 pole Mechanical interlock MIF 46UP 3 MIF 46UP 4 PLD 12UP Padlock plate 3) THA 46UP Extension handle 4) ※ 1) For detail type information, please refer to page 195-202. 3) Padlock is not supplied. 2) Motor operator is not recommended for marine application. 4) Supplied as standard component •Mounting Plug-in 1) Structure Mounting base Connection 6C contact block 2) 12C contact For both line & load side TDM 46NEP 3) CBM 26NE 6 CBM 26NE 64) For line side only TDM 46NEF - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 3) 2EA are required for both line & load side plug-in type 3P breaker. 4) 2EA shall be ordered for 12C contact. •Terminal 3 pole (6EA/SET) 4 pole (8EA/SET) 3EA/SET Cage terminal block 4EA/SET 3 pole Terminal cover 1) 4 pole Interpole barrier 2) 4EA/SET TBB 40NE 3 TBB 40NE 4 CTB 46UP 3S CTB 46UP 4S TCF 46UP 3 TCF 46UP 4 TQQ 46NE 3P Terminal bus bar ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit •Electronic - LTD, STD, INST trip & PTA Model / Breaking capacity at AC380/415V UPB400S 85kA UPB400H 100kA UPB400L 130kA UPB400X 150kA UPB400S 85kA UPB400H 100kA UPB400L 130kA UPB400X 150kA Rated current 400A 400A 400A 400A 400A 400A 400A 400A 3 pole Code UPB400S 3PESS0000X 00400 UPB400H 3PESS0000X 00400 UPB400L 3PESS0000X 00400 UPB400X 3PESS0000X 00400 UPB400S 3PESS0000Y 00400 UPB400H 3PESS0000Y 00400 UPB400L 3PESS0000Y 00400 UPB400X 3PESS0000Y 00400 4 pole Unit (EA) Code Unit (EA) 3 3 3 3 3 3 3 3 UPB400S 4PESS0000X 00400 UPB400H 4PESS0000X 00400 UPB400L 4PESS0000X 00400 UPB400X 4PESS0000X 00400 UPB400S 4PESS0000Y 00400 UPB400H 4PESS0000Y 00400 UPB400L 4PESS0000Y 00400 UPB400X 4PESS0000Y 00400 2 2 2 2 2 2 2 2 Specification Screw type terminal connection, No option, 50Hz Screw type terminal connection, No option, 60Hz Category MCCB/M3 •Electronic - LTD, STD, INST, GFT trip & PTA Model / Breaking capacity at AC380/415V UPB400S 85kA UPB400H 100kA UPB400L 130kA UPB400X 150kA UPB400S 85kA UPB400H 100kA UPB400L 130kA UPB400X 150kA Rated current 400A 400A 400A 400A 400A 400A 400A 400A 3 pole Code UPB400S 3PEGS0000X 00400 UPB400H 3PEGS0000X 00400 UPB400L 3PEGS0000X 00400 UPB400X 3PEGS0000X 00400 UPB400S 3PEGS0000Y 00400 UPB400H 3PEGS0000Y 00400 UPB400L 3PEGS0000Y 00400 UPB400X 3PEGS0000Y 00400 4 pole Unit (EA) Code Unit (EA) 3 3 3 3 3 3 3 3 UPB400S 4PEGS0000X 00400 UPB400H 4PEGS0000X 00400 UPB400L 4PEGS0000X 00400 UPB400X 4PEGS0000X 00400 UPB400S 4PEGS0000Y 00400 UPB400H 4PEGS0000Y 00400 UPB400L 4PEGS0000Y 00400 UPB400X 4PEGS0000Y 00400 2 2 2 2 2 2 2 2 Specification Screw type terminal connection, No option, 50Hz Screw type terminal connection, No option, 60Hz Category MCCB/M3 Molded Case Circuit Breaker_ 107 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | UPB type / 630AF | •UPB630S 85kA •UPB630H 100kA •UPB630L 130kA •UPB630X 150kA UPB630S UPB630H UPB630L UPB630X 3, 4 Number of poles (P) IP20 Degree of protection (with terminal cover) A Utilization category Suitability of isolation ○ Protection overload, inst., short-circuit Rated current (A) 320-630 Rated insulation voltage [Ui] (V) AC750 Rating Rated operational voltage [Ue] (V) AC690 Rated impulse withstand voltage [Uimp] (kV) 8 AC660/690V, 50-60Hz 10 1025 25 Rated Ultimate AC480/500V, 50-60Hz short-circuit 50 6585 85 breaking [Icu] AC440/460V, 50-60Hz 65 85100 150 capacity (kA r.m.s.) AC380/415V, 50-60Hz 85 100130 150 AC220/240V, 50-60Hz IEC 60947-2 100 130150 200 K 60947-2 Service [Ics] % of [Icu] 100 Long time delay LTD (0.5-1) 1) ×In (15 setting) Short time delay STD (2-4-6-8-10)×Ir Trip Instantaneous INST (3-6-8-10-11)×In mechanism Electronic Ground fault trip GFT (0.2-0.3-0.4)×In & Protection Pre-trip alarm PTA 0.9×Ir characteristics I2T lamp ○ Pick-up LED ○ Direct mounting by screw ○ Both line & load side ○2) Mounting for Plug-in Switchboard Line side only ○2) Screw ○ Terminal connection Bus bar ○ Mechanical operation Durability 20,000 (times) Electrical operation 6,000 a Width d 140/185 a c b Height 255 Dimensions 3/4P b (mm) c Depth 117 d 159.5 Weight (kg, breaker only) 3/4P 6.0/7.8 ※ - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1) 2) Available for 3P breaker ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip 1) Under voltage trip 2) 1C, left-hand-side AUX 46UP L1 1C, right-hand-side ALT 46UP R1 DC24V SHT 46UP A DC24V ✽UVT 46UP J DC100-110V SHT 46UP C DC100-110V ✽UVT 46UP L AC100-120V SHT 46UP F AC100-120V ✽UVT 46UP N ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. 108 AC200-230V SHT 46UP H AC200-230V ✽UVT 46UP P AC380-415V SHT 46UP B AC380-415V ✽UVT 46UP Q AC440-480V SHT 46UP D AC440-480V ✽UVT 46UP R MCCB •Operating Power supply direction Upper RightLeft Operating Surface S type TFG 46UPS U4 TFG 46UPS R4 TFG 46UPS L4 handle 1) Extended S type TFH 46UPS DC24V AC/DC110VAC/DC220V Motor operator 2) MOT 46NE DC24 MOT 46NE ADC110MOT 46NE ADC220 3 pole 4 pole Mechanical interlock MIF 46UP 3 MIF 46UP 4 PLD 12UP Padlock plate 3) Extension handle 4) THA 46UP ※ 1) For detail type information, please refer to page no. 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied.4) Supplied as standard component •Mounting Plug-in 1) Structure Mounting base Connection 6C contact block 2) 12C contact For both line & load side TDM 46NEP 3) CBM 26NE 6 CBM 26NE 64) For line side only TDM 46NEF - ※ 1) Available for 3P breaker 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 3) 2EA are required for both line & load side plug-in type 3P breaker. 4) 2EA shall be ordered for 12C contact. •Terminal TBB 60NE 3 TBB 60NE 4 CTB 46UP 3S CTB 46UP 4S TCF 46UP 3 TCF 46UP 4 TQQ 46NE 3P 3 pole (6EA/SET) 4 pole (8EA/SET) 3EA/SET Cage terminal block 4EA/SET 3 pole Terminal cover 1) 4 pole Interpole barrier 2) 4EA/SET Terminal bus bar ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA ■ Standard order code and unit •Electronic - LTD, STD, INST trip & PTA Model / Breaking capacity at AC380/415V UPB630S 85kA UPB630H 100kA UPB630L 130kA UPB630X 150kA UPB630S 85kA UPB630H 100kA UPB630L 130kA UPB630X 150kA Rated current 630A 630A 630A 630A 630A 630A 630A 630A 3 pole Code UPB630S 3PESS0000X 00630 UPB630H 3PESS0000X 00630 UPB630L 3PESS0000X 00630 UPB630X 3PESS0000X 00630 UPB630S 3PESS0000Y 00630 UPB630H 3PESS0000Y 00630 UPB630L 3PESS0000Y 00630 UPB630X 3PESS0000Y 00630 4 pole Unit (EA) Code Unit (EA) 3 3 3 3 3 3 3 3 UPB630S 4PESS0000X 00630 UPB630H 4PESS0000X 00630 UPB630L 4PESS0000X 00630 UPB630X 4PESS0000X 00630 UPB630S 4PESS0000Y 00630 UPB630H 4PESS0000Y 00630 UPB630L 4PESS0000Y 00630 UPB630X 4PESS0000Y 00630 2 2 2 2 2 2 2 2 Specification Screw type terminal connection, No option, 50Hz Screw type terminal connection, No option, 60Hz Category MCCB/M3 •Electronic - LTD, STD, INST, GFT trip & PTA Model / Breaking capacity at AC380/415V UPB630S 85kA UPB630H 100kA UPB630L 130kA UPB630X 150kA UPB630S 85kA UPB630H 100kA UPB630L 130kA UPB630X 150kA Rated current 630A 630A 630A 630A 630A 630A 630A 630A 3 pole Code UPB630S 3PEGS0000X 00630 UPB630H 3PEGS0000X 00630 UPB630L 3PEGS0000X 00630 UPB630X 3PEGS0000X 00630 UPB630S 3PEGS0000Y 00630 UPB630H 3PEGS0000Y 00630 UPB630L 3PEGS0000Y 00630 UPB630X 3PEGS0000Y 00630 4 pole Unit (EA) Code Unit (EA) 3 3 3 3 3 3 3 3 UPB630S 4PEGS0000X 00630 UPB630H 4PEGS0000X 00630 UPB630L 4PEGS0000X 00630 UPB630X 4PEGS0000X 00630 UPB630S 4PEGS0000Y 00630 UPB630H 4PEGS0000Y 00630 UPB630L 4PEGS0000Y 00630 UPB630X 4PEGS0000Y 00630 2 2 2 2 2 2 2 2 Specification Screw type terminal connection, No option, 50Hz Screw type terminal connection, No option, 60Hz Category MCCB/M3 Molded Case Circuit Breaker_ 109 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | Motor protection / UPB type 125AF | •UPB100H 100kA •UPB100L 130kA UPB100H UPB100L Number of poles (P) 3 Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection instantaneous, short-circuit Rated current (A) 2.5,3.2,6.3,12.5,20,32,50,63,80,100 Rated insulation voltage [Ui] (V) AC750 Rating AC690 Rated operational voltage [Ue] (V) DC500 Rated impulse withstand voltage [Uimp] (kV) 8 AC660/690V, 50-60Hz 10 25 Rated short-circuit Ultimate breaking [Icu] capacity (kA r.m.s.) AC480/500V, 50-60Hz 65 85 AC440/460V, 50-60Hz 85100 AC380/415V, 50-60Hz 100130 AC220/240V, 50-60Hz 130 150 IEC 60947-2 K 60947-2 DC250V 65 85 DC125V 100 100 Service [Ics] % of [Icu] Trip mechanism Thermal & Protection characteristics magnetic Adjustable instantaneous 100 (6-7-8-9-10-11-12-13)×In Direct mounting by screw ○ Mounting Both line & load side ○ for Plug-in Switchboard Line side only ○ Terminal connection Durability (times) Screw ○ Bus bar ○ Mechanical operation 25,000 Electrical operation a d c 10,000 a b Dimensions 3P b (mm) c Width 105 Height 165 Depth 86.5 d 112 Weight (kg, breaker only) 1.8 3P ※ The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 110 MCCB ■ Accessories •Signal 1C, right-hand-side AUX 12UP R1 1C, left-hand-side ALT 12UP L1 DC24V SHT 12UP A DC24V ✽UVT 12UP J Auxiliary switch Trip alarm switch Shunt trip 1) Under voltage trip 2) DC100-110V SHT 12UP C DC100-110V ✽UVT 12UP L AC100-120V SHT 12UP F AC100-120V ✽UVT 12UP N AC200-230V SHT 12UP H AC200-230V ✽UVT 12UP P AC380-415V SHT 12UP B AC380-415V ✽UVT 12UP Q AC440-480V SHT 12UP D AC440-480 ✽UVT 12UP R ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. •Operating Power supply direction Upper S type TFG 12UPS U4 Operating Surface L type TFG 12UPL U4 handle 1) S type Extended L type DC24V Motor operator 2) MOT 12UP DC24 Mechanical interlock Padlock plate 3) ※ 1) For detail type information, please refer to page 195-202. 3) Padlock is not supplied. RightLeft TFG 12UPS R4 TFG 12UPS L4 - TFG 12UPL L4 TFH 12UPS TFH 12UPL AC/DC110VAC/DC220V MOT 12UP ADC110MOT 12UP ADC220 MIF 12UP 3 PLD 12UP 2) Motor operator is not recommended for marine application. •Mounting Plug-in Structure Mounting base Connection 6C contact block 1) 12C contact For both line & load side TDM 12NEP CBM 26NE 6 CBM 26NE 62) For line side only TDM 12NEF - ※ 1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 2) 2EA shall be ordered for 12C contact. •Terminal Terminal bus bar Cage terminal block Terminal cover 1) Interpole barrier 2) 3 pole (6EA/SET) 3EA/SET 3 pole 4EA/SET TBB 12NE 3 CTB 12UP 3S TCF 12UP 3 TQQ 12NE 3P ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 4EA ■ Standard order code and unit •Adjustable instantaneous only / recommended for motor protection Model / Breaking capacity at AC380/415V UPB100H 100kA Rated current 2.5A 3.2A 6.3A 12.5A 20A 32A 50A 63A 80A 100A 3 pole Code UPB100H 3PMPS0000C 002.5 UPB100H 3PMPS0000C 003.2 UPB100H 3PMPS0000C 006.3 UPB100H 3PMPS0000C 012.5 UPB100H 3PMPS0000C 00020 UPB100H 3PMPS0000C 00032 UPB100H 3PMPS0000C 00050 UPB100H 3PMPS0000C 00063 UPB100H 3PMPS0000C 00080 UPB100H 3PMPS0000C 00100 Unit (EA) 8 8 8 8 8 8 8 8 8 8 Model / Breaking capacity at AC380/415V UPB100L 130kA 3 pole Rated current Code Unit (EA) 2.5A 3.2A 6.3A 12.5A 20A 32A 50A 63A 80A 100A UPB100L 3PMPS0000C 002.5 UPB100L 3PMPS0000C 003.2 UPB100L 3PMPS0000C 006.3 UPB100L 3PMPS0000C 012.5 UPB100L 3PMPS0000C 00020 UPB100L 3PMPS0000C 00032 UPB100L 3PMPS0000C 00050 UPB100L 3PMPS0000C 00063 UPB100L 3PMPS0000C 00080 UPB100L 3PMPS0000C 00100 8 8 8 8 8 8 8 8 8 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M4 Molded Case Circuit Breaker_ 111 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | Motor protection / UPB type 250AF | •UPB250H 100kA •UPB250L 130kA UPB250H UPB250L Number of poles (P) 3 Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Protection instantaneous, short-circuit Rated current (A) 125,150,175,200,225 Rated insulation voltage [Ui] (V) AC750 Rating AC690 Rated operational voltage [Ue] (V) DC500 Rated impulse withstand voltage [Uimp] (kV) 8 AC660/690V, 50-60Hz 10 25 Rated Ultimate short-circuit AC480/500V, 50-60Hz 65 85 AC440/460V, 50-60Hz 85100 breaking [Icu] capacity (kA r.m.s.) AC380/415V, 50-60Hz 100130 AC220/240V, 50-60Hz 130 150 IEC 60947-2 K 60947-2 DC250V 65 85 DC125V 100 100 Service [Ics] % of [Icu] Trip mechanism Thermal & Protection characteristics magnetic Adjustable instantaneous 100 (5-6-7-8-9-10)×In Direct mounting by screw ○ Mounting Both line & load side ○ for Plug-in Switchboard Line side only ○ Terminal connection Durability (times) Screw ○ Bus bar ○ Mechanical operation 25,000 Electrical operation a d c 10,000 a b Dimensions 3P b (mm) c Width 105 Height 165 Depth 86.5 d 112 Weight (kg, breaker only) 2.0 3P ※ The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 112 MCCB ■ Accessories •Signal 1C, right-hand-side AUX 12UP R1 1C, left-hand-side ALT 12UP L1 DC24V SHT 12UP A DC24V ✽UVT 12UP J Auxiliary switch Trip alarm switch Shunt trip 1) Under voltage trip 2) DC100-110V SHT 12UP C DC100-110V ✽UVT 12UP L AC100-120V SHT 12UP F AC100-120V ✽UVT 12UP N AC200-230V SHT 12UP H AC200-230V ✽UVT 12UP P AC380-415V SHT 12UP B AC380-415V ✽UVT 12UP Q AC440-480V SHT 12UP D AC440-480V ✽UVT 12UP R ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. •Operating Power supply direction Upper S type TFG 12UPS U4 Operating Surface L type TFG 12UPL U4 handle 1) S type Extended L type DC24V Motor operator 2) MOT 12UP DC24 Mechanical interlock Padlock plate3) ※ 1) For detail type information, please refer to page 195-202. 3) Padlock is not supplied. RightLeft TFG 12UPS R4 TFG 12UPS L4 - TFG 12UPL L4 TFH 12UPS TFH 12UPL AC/DC110VAC/DC220V MOT 12UP ADC110MOT 12UP ADC220 MIF 12UP 3 PLD 12UP 2) Motor operator is not recommended for marine application. •Mounting Plug-in Structure Mounting base Connection 6C contact block 1) 12C contact For both line & load side TDM 12NEP CBM 26NE 6 CBM 26NE 62) For line side only TDM 12NEF - ※ 1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 2) 2EA shall be ordered for 12C contact. •Terminal Terminal bus bar 3 pole (6EA/SET) Cage terminal block 3EA/SET Terminal cover 1) Interpole barrier 2) TBB 12NE 3 CTB 12UP 3S TCF 12UP 3 TCF 12UP 4 TQQ 12NE 3P 3 pole 4 pole 4EA/SET ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 4EA ■ Standard order code and unit •Adjustable instantaneous only / recommended for motor protection Model / Breaking capacity at AC380/415V Rated current Unit (EA) Model / Breaking capacity at AC380/415V 3 pole Code 3 pole Rated current Code Unit (EA) 125A UPB250H 3PMPS0000C 00125 8 125A UPB250L 3PMPS0000C 00125 8 UPB250H 150A UPB250H 3PMPS0000C 00150 8 150A UPB250L 3PMPS0000C 00150 8 175A UPB250H 3PMPS0000C 00175 8 UPB250L 175A UPB250L 3PMPS0000C 00175 8 200A UPB250H 3PMPS0000C 00200 8 200A UPB250L 3PMPS0000C 00200 8 225A UPB250H 3PMPS0000C 00225 8 225A UPB250L 3PMPS0000C 00225 8 100kA 130kA Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M4 Molded Case Circuit Breaker_ 113 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | Q-class (for nuclear power plant application) / HBL type 100AF | •HBL103U 85kA •HBL103UQ 85kA •HBL103UM 85kA •HBL103UMQ 85kA HBL103U HBL103UQ HBL103UM HBL103UMQ 3 Number of poles (P) IP20 Degree of protection (with terminal cover) A Utilization category ○ Suitability of isolation overload, inst., short-circuit instantaneous, short-circuit Protection 15,20,30,40,50,60,75,100 2.5,3.2,6.3,12.5,20,32,50,63,80,100 Rated current (A) AC750 Rated insulation voltage [Ui] (V) Rating AC690 Rated operational voltage [Ue] (V) DC500 Rated impulse withstand voltage [Uimp] (kV) 8 AC660/690V, 50-60Hz 25252525 Rated AC480/500V, 50-60Hz 85858585 short-circuit Ultimate AC440/460V, 50-60Hz 100100 100 100 breaking [Icu] AC380/415V, 50-60Hz 150150 150 150 capacity (kA r.m.s.) AC220/240V, 50-60Hz 200200 200 200 DC250V 100100 100 100 IEC 60947-2 DC125V 100100 100 100 K 60947-2 Service [Ics] % of [Icu] 100 Fixed thermal, ○ Trip mechanism Thermal & Protection Fixed instantaneous INST 10×In magnetic characteristics -(6-7-8-9-10-11-12-13)×In Adjustable instantaneous Non-E1 ○ -○Q-class E1 -○-○ Mounting Direct mounting by screw ○ Screw ○ Terminal connection Bus bar ○ Mechanical operation 25,000 Durability (times) Electrical operation 10,000 a Width 105 d a c b Height 165 Dimensions 3P b c Depth 86.5 (mm) 112 d Weight (kg, breaker only) 3P 1.8 ※ The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip 1) Under voltage trip 2) 1C, right-hand-side AUX 12UP R1 1C, left-hand-side ALT 12UP L1 DC24V SHT 12UP A DC24V ✽UVT 12UP J DC100-110V SHT 12UP C DC100-110V ✽UVT 12UP L AC100-120V SHT 12UP F AC100-120V ✽UVT 12UP N ※ - Signal accessories shall be installed in breaker before ex-working. 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. 114 AC200-230V SHT 12UP H AC200-230V ✽UVT 12UP P AC380-415V SHT 12UP B AC380-415V ✽UVT 12UP Q AC440-480V SHT 12UP D AC440-480V ✽UVT 12UP R MCCB •Operating Power supply direction Operating HBL103U, HBL103UM 1) Surface handle HBL103UQ, HBL103UMQ Upper TFG 20U U4 TFG 20UQ U4 DC24V MOT 12UP DC24 Motor operator 2) Mechanical interlock Padlock plate 3) Left TFG 20U L4 TFG 20UQ L4 AC/DC110V MOT 12UP ADC110 MIF 12UP 3 PLD 12UP AC/DC220V MOT 12UP ADC220 ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Terminal Terminal bus bar Cage terminal block TBB 12NE 3 6EA/SET 3EA/SET CTB 12UP 3S 4EA/SET TQQ 12NE 3P TCF 12UP 3 Terminal cover 1) Interpole barrier 2) ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 4EA ■ Standard order code and unit •Fixed thermal & fixed instantaneous 40/45℃ Model / Breaking capacity at AC480/500V HBL103U 85kA Rated current 15A 20A 30A 40A 50A 60A 75A 100A 3 pole, Non-E1 class Model / Breaking capacity at AC480/500V Rated current Code Unit (EA) HBL103U 3PT4S0000C 00015 HBL103U 3PT4S0000C 00020 HBL103U 3PT4S0000C 00030 HBL103U 3PT4S0000C 00040 HBL103U 3PT4S0000C 00050 HBL103U 3PT4S0000C 00060 HBL103U 3PT4S0000C 00075 HBL103U 3PT4S0000C 00100 8 8 8 8 8 8 8 8 HBL103UQ 85kA 15A 20A 30A 40A 50A 60A 75A 100A Code Unit (EA) Rated current HBL103U 3PT5S0000C 00015 HBL103U 3PT5S0000C 00020 HBL103U 3PT5S0000C 00030 HBL103U 3PT5S0000C 00040 HBL103U 3PT5S0000C 00050 HBL103U 3PT5S0000C 00060 HBL103U 3PT5S0000C 00075 HBL103U 3PT5S0000C 00100 8 8 8 8 8 8 8 8 Model / Breaking capacity at AC480/500V 3 pole, E1 class Code Unit (EA) HBL103UQ 3PT4S0000C 00015 HBL103UQ 3PT4S0000C 00020 HBL103UQ 3PT4S0000C 00030 HBL103UQ 3PT4S0000C 00040 HBL103UQ 3PT4S0000C 00050 HBL103UQ 3PT4S0000C 00060 HBL103UQ 3PT4S0000C 00075 HBL103UQ 3PT4S0000C 00100 8 8 8 8 8 8 8 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M1 50℃ Model / Breaking capacity at AC480/500V HBL103U 85kA Rated current 15A 20A 30A 40A 50A 60A 75A 100A 3 pole, Non-E1 class HBL103UQ 85kA 15A 20A 30A 40A 50A 60A 75A 100A 3 pole, E1 class Code Unit (EA) HBL103UQ 3PT5S0000C 00015 HBL103UQ 3PT5S0000C 00020 HBL103UQ 3PT5S0000C 00030 HBL103UQ 3PT5S0000C 00040 HBL103UQ 3PT5S0000C 00050 HBL103UQ 3PT5S0000C 00060 HBL103UQ 3PT5S0000C 00075 HBL103UQ 3PT5S0000C 00100 8 8 8 8 8 8 8 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M1 •Adjustable instantaneous only / recommended for motor protection Model / Breaking capacity at AC480/500V HBL103UM 85kA Rated current 2.5A 3.2A 6.3A 12.5A 20A 32A 50A 63A 80A 100A 3 pole, Non-E1 class Code HBL103UM 3PMPS0000C 002.5 HBL103UM 3PMPS0000C 003.2 HBL103UM 3PMPS0000C 006.3 HBL103UM 3PMPS0000C 012.5 HBL103UM 3PMPS0000C 00020 HBL103UM 3PMPS0000C 00032 HBL103UM 3PMPS0000C 00050 HBL103UM 3PMPS0000C 00063 HBL103UM 3PMPS0000C 00080 HBL103UM 3PMPS0000C 00100 Unit (EA) 8 8 8 8 8 8 8 8 8 8 Model / Breaking capacity at AC480/500V HBL103UMQ 85kA Rated current 2.5A 3.2A 6.3A 12.5A 20A 32A 50A 63A 80A 100A 3 pole, E1 class Code Unit (EA) HBL103UMQ 3PMPS0000C 002.5 HBL103UMQ 3PMPS0000C 003.2 HBL103UMQ 3PMPS0000C 006.3 HBL103UMQ 3PMPS0000C 012.5 HBL103UMQ 3PMPS0000C 00020 HBL103UMQ 3PMPS0000C 00032 HBL103UMQ 3PMPS0000C 00050 HBL103UMQ 3PMPS0000C 00063 HBL103UMQ 3PMPS0000C 00080 HBL103UMQ 3PMPS0000C 00100 8 8 8 8 8 8 8 8 8 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M4 Molded Case Circuit Breaker_ 115 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | Q-class (for nuclear power plant application) / HBL type 225AF | •HBL203U 85kA •HBL203UQ 85kA •HBL203UM 85kA •HBL203UMQ 85kA HBL203U HBL203UQ HBL203UM HBL203UMQ 3 Number of poles (P) IP20 Degree of protection (with terminal cover) A Utilization category ○ Suitability of isolation overload, inst., short-circuit instantaneous, short-circuit Protection 125,150,175,200,225 Rated current (A) AC750 Rated insulation voltage [Ui] (V) AC690 Rating Rated operational voltage [Ue] (V) DC500 Rated impulse withstand voltage [Uimp] (kV) 8 25252525 AC660/690V, 50-60Hz Rated 85858585 AC480/500V, 50-60Hz short-circuit 100100 100 100 Ultimate AC440/460V, 50-60Hz breaking 150150 150 150 [Icu] AC380/415V, 50-60Hz capacity 200200 200 200 (kA r.m.s.) AC220/240V, 50-60Hz 100100 100 100 DC250V IEC 60947-2 100100 100 100 DC125V K 60947-2 Service [Ics] % of [Icu] 100 Fixed thermal, ○ Trip mechanism Thermal & Protection magnetic Fixed instantaneous INST 10×In characteristics Adjustable instantaneous -(5-6-7-8-9-10)×In Non-E1 ○ -○Q-class E1 -○-○ Direct mounting by screw ○ Mounting Both line & load side ○ for Plug-in Switchboard Line side only ○ Screw ○ Terminal connection Bus bar ○ Mechanical operation 25,000 Durability (times) Electrical operation 10,000 a Width 105 d a c b Height 165 Dimensions 3P b (mm) c Depth 86.5 d 112 2.0 Weight (kg, breaker only) 3P ※ The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. ■ Accessories •Signal Auxiliary switch Trip alarm switch Shunt trip 1) Under voltage trip 2) 116 1C, right-hand-side AUX 12UP R1 1C, left-hand-side ALT 12UP L1 DC24V SHT 12UP A DC24V ✽UVT 12UP J DC100-110V SHT 12UP C DC100-110V ✽UVT 12UP L AC100-120V SHT 12UP F AC100-120V ✽UVT 12UP N ※ - Signal accessories shall be installed in breaker before ex-working. 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. AC200-230V SHT 12UP H AC200-230V ✽UVT 12UP P AC380-415V SHT 12UP B AC380-415V ✽UVT 12UP Q AC440-480V SHT 12UP D AC440-480V ✽UVT 12UP R MCCB •Operating Power supply direction Upper Left HBL203U, HBL203UM TFG 20U U4 TFG 20U L4 Operating Surface HBL203UQ, HBL203UMQ TFG 20UQ U4 TFG 20UQ L4 handle 1) HBL203U, HBL203UM TFH 20U Extended HBL203UQ, HBL203UMQ TFH 20UQ DC24VAC/DC110V Motor operator 2) MOT 12UP DC24 MOT 12UP ADC110 Mechanical interlock MIF 12UP 3 Padlock plate 3) PLD 12UP AC/DC220V MOT 12UP ADC220 ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Terminal Terminal bus bar 6EA/SET TBB 12NE 3 Cage terminal block 3EA/SET CTB 12UP 3S 4EA/SET TQQ 12NE 3P Terminal cover 1) Interpole barrier 2) TCF 12UP 3 ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 4EA ■ Standard order code and unit •Fixed thermal & fixed instantaneous 40/45℃ Model / Breaking capacity at Rated current AC480/500V HBL203U 85kA 125A 150A 175A 200A 225A 3 pole, Non-E1 class Code HBL203U 3PT4S0000C 00125 HBL203U 3PT4S0000C 00150 HBL203U 3PT4S0000C 00175 HBL203U 3PT4S0000C 00200 HBL203U 3PT4S0000C 00225 Model / Unit Breaking capacity at AC480/500V (EA) 8 8 8 8 8 HBL203UQ 85kA Rated current 125A 150A 175A 200A 225A 3 pole, E1 class Code HBL203UQ 3PT4S0000C 00125 HBL203UQ 3PT4S0000C 00150 HBL203UQ 3PT4S0000C 00175 HBL203UQ 3PT4S0000C 00200 HBL203UQ 3PT4S0000C 00225 Unit (EA) 8 8 8 8 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M1 50℃ Model / Breaking capacity at Rated current AC480/500V HBL203U 85kA 125A 150A 175A 200A 225A 3 pole, Non-E1 class Code HBL203U 3PT5S0000C 00125 HBL203U 3PT5S0000C 00150 HBL203U 3PT5S0000C 00175 HBL203U 3PT5S0000C 00200 HBL203U 3PT5S0000C 00225 Model / Unit Breaking capacity at AC480/500V (EA) 8 8 8 8 8 HBL203UQ 85kA Rated current 125A 150A 175A 200A 225A 3 pole, E1 class Code HBL203UQ 3PT5S0000C 00125 HBL203UQ 3PT5S0000C 00150 HBL203UQ 3PT5S0000C 00175 HBL203UQ 3PT5S0000C 00200 HBL203UQ 3PT5S0000C 00225 Unit (EA) 8 8 8 8 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M1 •Adjustable instantaneous only / recommended for motor protection Model / Breaking capacity at Rated current AC480/500V HBL203UM 85kA 125A 150A 175A 200A 225A 3 pole, Non-E1 class Code HBL203UM 3PMPS0000C 00125 HBL203UM 3PMPS0000C 00150 HBL203UM 3PMPS0000C 00175 HBL203UM 3PMPS0000C 00200 HBL203UM 3PMPS0000C 00225 Model / Unit Breaking capacity at AC480/500V (EA) 8 8 8 8 8 HBL203UMQ 85kA Rated current 125A 150A 175A 200A 225A 3 pole, E1 class Code HBL203UMQ 3PMPS0000C 00125 HBL203UMQ 3PMPS0000C 00150 HBL203UMQ 3PMPS0000C 00175 HBL203UMQ 3PMPS0000C 00200 HBL203UMQ 3PMPS0000C 00225 Unit (EA) 8 8 8 8 8 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M4 Molded Case Circuit Breaker_ 117 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | Switch disconnector / UAD type 50-100AF | •UAD50C •UAD50S •UAD100R UAD50C UAD50S 50AF Ampere frame size 3 3 Number of poles (P) IP20 IP20 Degree of protection (with terminal cover) A A Utilization category ○○ Suitability of isolation 50 50 Conventional thermal current [Ith] (A) 50 50 Rated current (A) AC690 AC690 Rated insulation voltage [Ui] (V) AC660 AC660 Rating Rated operational voltage [Ue] (V) DC250 DC250 6 6 Rated impulse withstand voltage [Uimp] (kV) 1752.5 Rated short-circuit making capacity [Icm] (kA peak at AC460V) 1 1 Rated short-time withstand current for 1sec. [Icw] (kA r.m.s) 25,000 25,000 Mechanical operation Durability (times) 15,000 15,000 Electrical operation ○○ Direct mounting by screw ○○ for Both line & load side Switchboard Line side only ○○ Mounting Plug-in ○○ for Distribution board -○ DIN-rail with DIN-rail adaptor ○○ Terminal connection Screw d a a c b Dimensions 3P b (mm) c d Weight (kg, breaker only) 3P Width Height Depth 75 75 130 130 60 60 82 82 0.65 0.78 UAD100R 100AF 3 IP20 A ○ 100 100 AC690 AC660 DC250 6 52.5 1 25,000 10,000 ○ ○ ○ ○ ○ ○ 75 130 60 82 0.78 ■ Accessories •Signal Auxiliary switch UAD50C UAD50S, UAD100R Trip alarm switch UAD50C UAD50S, UAD100R Shunt trip 1) UAD50C UAD50S, UAD100R Under voltage trip2) UAD50C UAD50S, UAD100R 1C, right-hand-side AUX 10A R1 AUX 10UA R1 1C, right-hand-side ALT 10A R1 ALT 10UA R1 DC24V SHT 10A A SHT 10UA A DC24V ✽UVT 10A J UVT 10UA J 1C, left-hand-side 2C,right-hand-side AUX 10A R2 AUX 10UA L1 1C, left-hand-side ALT 10UA L1 DC100-110V AC100-120V AC200-230V SHT 10A C SHT 10A F SHT 10UA F SHT 10UA H DC100-110V AC100-120V AC200-230V ✽UVT 10A L ✽UVT 10A N ✽UVT 10A P UVT 10UA L UVT 10UA N UVT 10UA P ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. 118 AC380-415V AC440-480V SHT 10A H SHT 10UA B SHT 10UA D AC380-415V AC440-480V ✽UVT 10A Q ✽UVT 10A R UVT 10UA Q UVT 10UA R MCCB •Operating Power supply direction Upper S type TFG 10AS U4 Operating Surface L type TFG 10AL U4 handle 1) S type Extended L type Motor operator 2) UAD50C UAD50S, UAD100R Right Left Upper Right Left TFG 10AS R4 TFG 10AS L4 TFG 10UAS U4 TFG 10UAS R4 TFG 10UAS L4 - TFG 10AL L4 TFG 10UAL U4 - TFG 10UAL L4 TFH 10AS TFH 10AL TFH 10UAS TFH 10UAL DC24V AC/DC110V AC/DC220V DC24V AC/DC110V AC/DC220V MOT 10A DC24 MOT 10A ADC110 MOT 10A ADC220 MOT 10UA DC24 MOT 10UA ADC110 MOT 10UA ADC220 Mechanical interlock Padlock plate3) MIF 10A 3 MIF 10UA 3 PLD 10UA ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting DIN-rail adaptor 1) Structure Mounting base Plug-in Connection 2C contact block 2) 3C contact Conn block barrier DRA 10UA For both line & load side TDM 10AP CBM 10AB 2 CBM 10AB 3 CBM BARR For line side only TDM 10AF - ※ 1) Available for UAD50S, UAD100R 2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. •Terminal Cage terminal block 3EA/SET UAD50C, UAD50S UAD100R CTB 10A 3S50 CTB 10A 3S100 TCF 10AP 3 Terminal cover 1) Interpole barrier 2) TQQ 10A 3PLINE 2EA/SET ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 4EA ■ Standard order code and unit Model Rated current 3 pole Code Unit (EA) Originated MCCB model UAD50C 50A UAD50C 3PDS0000C 00050 20 UAB50C UAD50S 50A UAD50S 3PDS0000C 00050 20 UAB50S UAD100R 100A UAD100R 3PDS0000C 00100 20 UAB100R Specification Category Screw type terminal connection, No option, 50/60Hz MCCB/M5 Molded Case Circuit Breaker_ 119 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | Switch disconnector / UCD type 50-250AF | •UCD50H •UCD100H •UCD250S UCD50H •UCD100S •UCD160H •UCD250H Ampere frame size 50AF Number of poles (P) 3 Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Conventional thermal current [Ith] (A) Rated current (A)50 Rated insulation voltage [Ui] (V) AC690 AC660 DC250 Rated impulse withstand voltage [Uimp] (kV) 6 Rated short-circuit making capacity [Icm] (kA peak at AC460V) 105 Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.) 1 Mechanical operation 25,000 Durability (times) Electrical operation 10,000 ○ Direct mounting by screw ○ Both line & load side for Mounting Switchboard Line side only○ Plug-in ○ for Distribution board ○ Screw Terminal connection Bus bar a Width 90 d a c b Height Dimensions 155 3P b (mm) c Depth 60 d 84.5 Weight (kg, breaker only) 3P 1 Rating Rated operational voltage [Ue] (V) UCD100S UCD100H UCD160H UCD250S 100AF 3 IP20 A ○ 125AF 3 IP20 A ○ 160AF 3 IP20 A ○ 3 IP20 A ○ 3 IP20 A ○ 100 AC690 AC660 DC250 6 73.5 1 25,000 10,000 ○ ○ ○ ○ ○ 125 AC690 AC660 DC250 6 105 1 25,000 10,000 ○ ○ ○ ○ ○ 250 AC690 AC660 DC250 6 73.5 2 25,000 10,000 ○ ○ ○ ○ ○ ○ 250 AC690 AC660 DC250 6 105 2 25,000 10,000 ○ ○ ○ ○ ○ ○ 105 164 60 84 1.2 105 165 60 84.5 1.3 - - 160 AC690 AC660 DC250 6 105 2 25,000 10,000 ○ ○ ○ ○ ○ ○ 90 155 60 84.5 1 90 155 60 84.5 1 105 165 60 84.5 1.3 UCD250H 250AF ■ Accessories •Signal Auxiliary switch 1C, left-hand-side UCD100S UCD250S 2C, left-hand-side AUX 10B L1 - AUX 20C L1 UCD50H, UCD100H, UCD160H, UCD250H AUX 20FG L1 Trip alarm switch 1C, right-hand-side AUX 12FG L2 1C, left-hand-side UCD100S - UCD250S - ALT 20C L UCD50H, UCD100H, UCD160H, UCD250H ALT 12FG R1 DC24V DC100-110V AC100-120V ALT 12FG L1 AC380-415V Shunt trip 1) UCD100S SHT 10B A ALT 10B L1 AC200-230V SHT 10B F UCD250S SHT 20C A SHT 20C F SHT 20C H UCD50H, UCD100H, UCD160H, UCD250H SHT 12FG A SHT 12FG C SHT 12FG F SHT 12FG H SHT 12FG B SHT 12FG D DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V UCD100S UVT 10B J UVT 10B L UVT 10B N UVT 10B P UVT 10B Q UVT 10B R UCD250S UVT 20C J UVT 20C L UVT 20C N UVT 20C P UVT 20C Q UVT 20C R UCD50H, UCD100H, UCD160H, UCD250H UVT 12FG J UVT 12FG L UVT 12FG N UVT 12FG P UVT 12FG Q UVT 12FG R Under voltage trip 2) ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) 120 AC440-480V SHT 10B H - Be sure not to use UVT for the electrical interlock system. MCCB •Operating Power supply direction S type Operating Surface L type handle 1) S type Extended L type Motor operator 2) UCD50H, UDC100H Right Left Upper Right Left TFG 10UFS U4 TFG 10UFS R4 TFG 10UFS L4 TFG 10BS U4 TFG 10BS R4 TFG 10BS L4 - TFG 10UFL L4 TFG 10BL U4 - TFG 10BL L4 TFG 10UFL U4 TFH 10UFS TFH 10UFL TFH 10BL AC/DC110V AC/DC220V DC24V AC/DC110V AC/DC220V MOT 10F DC24 MOT 10F ADC110 MOT 10F ADC220 MOT 10UB DC24 MOT 10UB ADC110 MOT 10UB ADC220 Padlock plate 3) MIF 10UF 3 S type Operating Surface L type handle 1) S type Extended L type MIF 10UF 3 PLD 10UF UCD250S UCD160H, UCD250H Upper Right Left Upper Right Left TFG 20CS U4 TFG 20CS R4 TFG 20CS L4 TFG 20UGS U4 TFG 20UGS R4 TFG 20UGS L4 - TFG 20CL L4 TFG 20UGL U4 - TFG 20UGL L4 TFG 20CL U4 DC24V Motor operator 2) TFH 10BS DC24V Mechanical interlock Power supply direction UCD100S Upper TFH 20CS TFH 20UGS TFH 20CL TFH 20UGL AC/DC110V MOT 20UC DC24 AC/DC220V MOT 20UC ADC110 MOT 20UC ADC220 Mechanical interlock Padlock plate 3) DC24V AC/DC110V AC/DC220V MOT 20G DC24 MOT 20G ADC110 MOT 20G ADC220 MIF 20UG 3 MIF 20UG 3 PLD 20UG ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. •Mounting UCD50H, UCD100S, UCD100H Structure For both line & load side For line side only Mounting base TDM 10BP TDM 10BF Plug-in Connection 2C contact CBM 10AB 2 block 1) 3C/5C contact CBM 10AB 3 3) Conn. block barrier CBM BARR - UCD160H, UCD250S, UCD250H For both line & load side For line side only TDM 20CF 2) TDM 20CF CBM 20C 2 CBM 20C 5 3) - - ※ 1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 2) 2EA are required for both line & load side plug-in type 3P breaker. 3) CBM 10AB 3: 3C, CBM 20C 5: 5C •Terminal UCD100S Cage terminal block UCD250S UCD160H, UCD250H 3EA/SET CTB 10B 3S CTB 20C 3S 2EA/SET TQQ 10B 3PLINETQQ 12FG 3PLINE TQQ 20C 3PLINETQQ 12FG 3PLINE TCF 10BP 3 TCF 10FP 3 Terminal cover 1) Interpole barrier 2) UCD50H, UCD100H - - TBB 20C 3 Terminal bus bar TCF 20CP 3 TCF 20GP 3 ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 4EA ■ Standard order code and unit 3 pole Originated MCCB model Rated current Code UCD50H 50A UCD50H 3PDS0000C 00050 8 UCB50H UCD100S 100A UCD100S 3PDS0000C 00100 10 UCB100S UCD100H 125A UCD100H 3PDS0000C 00125 8 UCB100H UCD160H 160A UCD160H 3PDS0000C 00160 8 UCB160H UCD250S 250A UCD250S 3PDS0000C 00250 10 UCB250S UCD250H 250A UCD250H 3PDS0000C 00250 8 UCB250H Model Unit (EA) Specification Category Screw type terminal connection, No option, 50/60Hz MCCB/M5 Molded Case Circuit Breaker_ 121 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | Switch disconnector / UCD type 400-1250AF | •UCD400S •UCD630S •UCD800S •UCD1000S •UCD1250S UCD400S UCD630S UCD800S UCD1000S UCD1250S AC660 DC250 630AF 3 IP20 A ○ 630 630 AC690 AC660 DC250 800AF 3 IP20 A ○ 800 800 AC690 AC660 DC250 1000AF 3 IP20 1) A ○ 1,000 1,000 AC750 AC690 1250AF 3 IP20 1) A ○ 1,250 1,250 AC750 AC690 - - 6 187 4 20,000 6,000 ○ ○ ○ ○ ○ 140 257 110 145 4.5 6 187 6.3 20,000 6,000 ○ ○ ○ ○ ○ 210 280 110 145 9.5 6 187 8 10,000 3,000 ○ ○ ○ ○ ○ 210 280 110 145 9.5 8 165 10 10,000 3,000 8 165 12.5 10,000 3,000 Ampere frame size 400AF Number of poles (P) 3 Degree of protection (with terminal cover) IP20 Utilization category A Suitability of isolation ○ Conventional thermal current [Ith] (A) 400 Rated current (A)400 Rated insulation voltage [Ui] (V) AC690 Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) Rated short-circuit making capacity [Icm] (kA peak at AC460V) Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.) Durability Mechanical operation (times) Electrical operation Direct mounting by screw Mounting Both line & load side for Plug-in Switchboard Line side only Screw Terminal connection Bus bar a Width d a c b Height Dimensions 3P b (mm) c Depth d Weight (kg, breaker only) 3P - - - - - - - - ○ 210 370 110 159 13 ○ 210 370 110 159 13.5 ※ 1) IP20 without terminal bus bar ■ Accessories •Signal Auxiliary switch 1C, right-hand-side 2C, right-hand-side 3C, right-hand-side UCD400, UCD630, UCD800 AUX 46D R1 UCD1000, UCD1250 AUX 80NE R1 AUX 80NE R2 AUX 80NE R3 Trip alarm switch 1C, left-hand-side 1C, right-hand-side UCD400, UCD630, UCD800 ALT 46D L1 UCD1000, UCD1250 ALT 80NE R1 Shunt trip 1) DC24V DC100-110V AC100-120V UCD400, UCD630, UCD800 SHT 46D A SHT 46D C SHT 46D F SHT 120NE A SHT 120NE C SHT 120NE F UCD1000, UCD1250 DC24V DC100-110V AC100-120V Under voltage trip 2) ✽UVT 46D J ✽UVT 46D L ✽UVT 46D N UCD400, UCD630,UCD800 UVT 120NE J UVT 120NE L UVT 120NE N UCD1000, UCD1250 ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. 122 AC200-230V SHT 46D H SHT 120NE H AC200-230V ✽UVT 46D P UVT 120NE P AC380-415V SHT 46D B SHT 120NE B AC380-415V ✽UVT 46D Q UVT 120NE Q AC440-480V SHT 46D D SHT 120NE D AC440-480V ✽UVT 46D R UVT 120NE R MCCB •Operating UCD400, UCD630, UCD800 Power supply direction Upper Right Left Operating Surface S type handle 1) Extended S type TFG 46DS U4 TFG 46DS R4 TFG 46DS L4 TFH 46DS UCD400 DC24VAC/DC110V Motor operator 2) UCD630, UCD800UCD1000, UCD1250 AC/DC220V DC24V AC/DC110VAC/DC220V MOT 40D DC24MOT 40D ADC110 MOT 40D ADC220 MOT 68E DC24 DC24V AC/DC110V AC/DC220V MOT 68E ADC110MOT 68E ADC220 MOT 80NE DC24 MOT 80NE ADC110 MOT 80NE ADC220 Mechanical interlock MIF 40D 3 Padlock plate3) PLD 40D PLD 120NE Extension handle 4) THA 46D THA 120NE MIF 80E 3 - ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. 4) Supplied as standard component. •Mounting UCD400 Structure Mounting base Plug-in Connection 2C contact 5C contact block 1) For both line & load side TDM 4BA 2) TYA 5/2 3) TYA 5/5 3) UCD630, UCD800 For line side only For both line & load side For line side only TDM 4BA - TDM 5BA 2) TYA 5/2 3) TYA 5/5 3) TDM 5BA - ※ 1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 2) 2EA are required for both line & load side plug-in type 3P breaker. 3) TYA type connection blocks are to be installed with separate mounting angle. Separate mounting angle is not supplied. •Terminal Terminal bus bar Cage terminal block 3EA/SET Terminal cover 1) Interpole barrier 2) UCD400 UCD630UCD800 UCD1000, UCD1250 TBB 4S 3 TBB 6S 3 TBB 8S 3 - CTB 40D 3S CTB 80E 3S TCF 40D 3 TCF 80E 3 2EA/SET TQQ 4BA 3PLINETQQ 5BA 3PLINE TQQ 80NE 3P ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 4EA ■ Standard order code and unit 3 pole Code Originated MCCB model Model Rated current UCD400S 400A UCD400S 3PDS0000C 00400 3 UCB400S UCD630S 630A UCD630S 3PDS0000C 00630 2 UCB630S UCD800S 800A UCD800S 3PDS0000C 00800 2 UCB800S UCD1000S 1000A UCD1000S 3PDB0000C 01000 1 UCB1000S UCD1250S 1250A UCD1250S 3PDB0000C 01250 1 UCB1250S Unit (EA) Specification Screw type terminal connection, No option, 50/60Hz Category MCCB/M5 Bus bar type terminal connection, No option, 50/60Hz Molded Case Circuit Breaker_ 123 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | Switch disconnector / UPD type 125-630AF | UPD100S UPD160S UPD250S UPD400S UPD630S Ampere frame size 125AF 160AF 250AF 400AF 630AF Number of poles (P) 3 3 3 3 3 Degree of protection (with terminal cover) IP20 IP20 IP20 IP20 IP20 Utilization category A A A A A Suitability of isolation ○ ○ ○ ○ ○ Conventional thermal current [Ith] (A) 125 160 250 400 630 Rated current (A)125 160 250 400 630 AC750 AC750 AC750 AC750 AC750 AC690 AC690 AC690 AC690 AC690 DC500 DC500 DC500 - - 8 8 8 8 8 Rated short-circuit making capacity [Icm] (kA peak at AC460V) 200 200 200 200 200 Rated short-time withstand current for 1sec. [Icw] (kA r.m.s) 1 •UPD100S •UPD160S •UPD250S •UPD400S •UPD630S Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) Rated impulse withstand voltage [Uimp] (kV) 25,000 Durability Mechanical operation (times) 10,000 Electrical operation Direct mounting by screw Mounting Plug-in Terminal connection 1.6 2.5 4 6.3 25,000 25,000 20,000 20,000 10,000 10,000 6,000 6,000 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ Both line & load side for Switchboard Line side only ○ ○ ○ ○ ○ Screw ○ ○ ○ ○ ○ Bus bar ○ ○ ○ ○ ○ d a a Width 105 105 105 140 140 Dimensions 3P b (mm) b Height 165 165 165 255 255 c Depth 86.5 86.5 86.5 117 117 d 112 112 112 159.5 159.5 1.8 2 2 6 6 c Weight (kg, breaker only) 3P ■ Accessories •Signal Auxiliary switch 1C, right-hand-side 1C, left-hand-side UPD100, UPD160,UPD250 AUX 12UP R1 UPD400, UPD630 AUX 46UP L1 Trip alarm switch 1C, right-hand-side 1C, left-hand-side ALT 12UP L1 UPD100, UPD160,UPD250 ALT 46UP R1 UPD400, UPD630 DC24V DC100-110V Shunt trip 1) SHT 12UP A SHT 12UP C UPD100, UPD160,UPD250 UPD400, UPD630 SHT 46UP A SHT 46UP C Under voltage trip 2) DC24V DC100-110V ✽UVT 12UP J ✽UVT 12UP L UPD100, UPD160,UPD250 ✽UVT 46UP J ✽UVT 46UP L UPD400, UPD630 AC100-120V SHT 12UP F SHT 46UP F AC100-120V ✽UVT 12UP N ✽UVT 46UP N ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) The permissible operating voltage: 85-110% of rated voltage(AC), 85-125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC) Be sure not to use UVT for the electrical interlock system. ✽Reset is possible without power. 124 AC200-230V SHT 12UP H SHT 46UP H AC200-230V ✽UVT 12UP P ✽UVT 46UP P AC380-415V SHT 12UP B SHT 46UP B AC380-415V ✽UVT 12UP Q ✽UVT 46UP Q AC440-480V SHT 12UP D SHT 46UP D AC440-480V ✽UVT 12UP R ✽UVT 46UP R MCCB •Operating Power supply direction S type Operating Surface L type handle 1) S type Extended L type UPD100, UPD160, UPD250 Right Left Upper Right Left TFG 12UPS U4 TFG 12UPS R4 TFG 12UPS L4 TFG 46UPS U4 TFG 46UPS R4 TFG 46UPS L4 - TFG 12UPL L4 - - - TFG 12UPL U4 TFH 12UPS TFH 46UPS TFH 12UPL DC24V Motor operator 2) UPD400, UPD630 Upper AC/DC110V MOT 12UP DC24 AC/DC220V - DC24V MOT 12UP ADC110 MOT 12UP ADC220 AC/DC110V MOT 46NE DC24 AC/DC220V MOT 46NE ADC110 MOT 46NE ADC220 Mechanical interlock MIF 12UP 3 MIF 46UP 3 Padlock plate 3) PLD 12UP PLD 12UP Extension handle 4) - THA 46UP ※ 1) For detail type information, please refer to page 195-202. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied. 4) Supplied as standard component. •Mounting UPD100, UPD160, UPD250 Structure Plug-in UPD400, UPD630 For both line & load side For line side only For both line & load side For line side only Mounting base TDM 12NEP TDM 12NEF TDM 46NEP TDM 46NEF Connection 6C contact block 1) 12C contact CBM 26NE 6 - CBM 26NE 6 - CBM 26NE 62) - CBM 26NE 62) - ※ 1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker. 2) 2EA shall be ordered for 12C contact. •Terminal UPD100, UPD160, UPD250 UPD400 UPD630 6EA/SET TBB 12NE 3 TBB 40NE 3 TBB 60NE 3 Cage terminal block 3EA/SET CTB 12UP 3S CTB 46UP 3S Terminal cover 1) TCF 12UP 3 TCF 46UP 3 TQQ 12NE 3P TQQ 46NE 3P Terminal bus bar Interpole barrier 2) 4EA/SET ※ 1) For both line and load side of breaker, 2EA shall be ordered. 2) Supplied as standard component Required quantity for both line and load side of breaker: 4EA ■ Standard order code and unit 3 pole Unit (EA) Originated MCCB model UPD100S 3PDS0000C 00125 8 UPB100S UPD160S 3PDS0000C 00160 8 UPB160S UPD250S 3PDS0000C 00250 8 UPB250S 400A UPD400S 3PDS0000C 00400 3 UPB400S 630A UPD630S 3PDS0000C 00630 3 UPB630S Model Rated current UPD100S 125A UPD160S 160A UPD250S 250A UPD400S UPD630S Code Specification Category Screw type terminal connection, No option, 50/60Hz MCCB/M5 Molded Case Circuit Breaker_ 125 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes | Miniature type / Molded case circuit breaker UMB type 30-50AF | •UMB30Ra 2.5kA •UMB30Sg 5kA •UMB50Sg 5kA •UMB30Rb 2.5kA •UMB30Hg 10kA •UMB50Hg 10kA UMB30Ra Ampere frame size Number of poles (P) Degree of protection Utilization category Protection Rating UMB30Rb UMB30Hg UMB50Sg 30AF 2 IP20 A overload, short-circuit UMB50Hg 50AF 2 IP20 A overload, short-circuit Rated current (A) Rated insulation voltage [Ui] (V) AC250 AC250 Rated operational voltage [Ue] (V) AC220 AC220 Rated impulse withstand voltage [Uimp] (kV) 15, 20, 30 15, 20, 30, 40, 50 6 Ultimate [Icu] Rated 2.5 AC220/240V, 50-60Hz short-circuit (kA r.m.s.) breaking capacity IEC 60947-2 Service [Ics] % of [Icu] K 60947-2 Trip mechanism UMB30Sg Hydraulic magnetic ○ Thermal magnetic Mounting Direct mounting by screw Screw 510 50 ○ ○ ○ - 50 ○ ○ - ○ ○ ○ ○ - DIN-rail Terminal connection 5 10 6 ○ ○ a Width 33 35 35 Dimensions b Height 70 80 80 c Depth 60 a d c 2P b (mm) Weight (kg, breaker only) 2P d 42 60 60 57 75 76 76 0.1 0.12 0.13 0.15 ※ - KS certified products. English nameplate and 50Hz marking are not available. - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. ■ Standard order code and unit 40/45℃ Model / Breaking capacity at AC220/240V UMB30Ra 2.5kA UMB30Rb 2.5kA UMB30Sg 2.5kA UMB30Hg 2.5kA UMB50Sg 5kA UMB50Hg 10kA 126 Rated current 2 pole Code Specification Category 15A 20A 30A 15A 20A 30A 15A 20A 30A 15A 20A 30A 15A 20A 30A 40A 50A 15A 20A 30A 40A 50A UMB30RA 2PT4S0000C 00015 UMB30RA 2PT4S0000C 00020 UMB30RA 2PT4S0000C 00030 UMB30RB 2PT4S0000C 00015 UMB30RB 2PT4S0000C 00020 UMB30RB 2PT4S0000C 00030 UMB30SG 2PT4S0000C 00015 UMB30SG 2PT4S0000C 00020 UMB30SG 2PT4S0000C 00030 UMB30HG 2PT4S0000C 00015 UMB30HG 2PT4S0000C 00020 UMB30HG 2PT4S0000C 00030 UMB50SG 2PT4S0000C 00015 UMB50SG 2PT4S0000C 00020 UMB50SG 2PT4S0000C 00030 UMB50SG 2PT4S0000C 00040 UMB50SG 2PT4S0000C 00050 UMB50HG 2PT4S0000C 00015 UMB50HG 2PT4S0000C 00020 UMB50HG 2PT4S0000C 00030 UMB50HG 2PT4S0000C 00040 UMB50HG 2PT4S0000C 00050 Screw type terminal connection, No option, 50/60Hz MCCB/M1 MCCB | Miniature type / Molded case circuit breaker UDB type 30-100AF | •UDB30S 5kA •UDB50S 5kA •UDB100S 5kA •UDB30H 10kA •UDB50H 10kA •UDB100H 10kA UDB30S UDB30H UDB50S UDB50H UDB100S UDB100H Ampere frame size 30AF50AF100AF Number of poles (P) 2, 32, 3✽2, 3 Degree of protection IP20IP20IP20 Utilization category AAA overload, short-circuit Protection 3 1) ,5,10,15,20,30 Rated current (A) Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) overload, short-circuit 5,10,15,20,30,40,50 overload, short-circuit 15,20,30,40,50,60,75,100 AC460AC460AC460 2P: AC220 2P: AC220 2P: AC220 3P: AC220/4603P: AC220/4603P: AC220/460 666 Rated impulse withstand voltage [Uimp] (kV) 5-10A: 2.5 5-10A: 2.5 AC440/460V, 50-60Hz 2.5 2.5 2.5 5 Rated 15-30A: 5 15-50A: 5 short-circuit Ultimate 5-10A: 2.5 5-10A: 2.5 AC380/415V, 50-60Hz 2.5 2.5 2.5 5 breaking capacity [Icu] 15-30A: 5 15-50A: 5 (kA r.m.s.) 5-10A: 5 5-10A: 5 IEC 60947-2 AC220/240V, 50-60Hz 5 5 5 10 15-30A: 10 15-50A: 10 K 60947-2 Service [Ics] % of [Icu] 505050 Trip mechanism Hydraulic magnetic ○○○ Direct mounting by screw ○○○ Mounting DIN-rail Terminal connection Screw ○○○ ○○○ Width 50/7550/75 75 2) /75 d a c a Dimensions 2/3P b (mm) b Height 969696 c Depth 606060 d 808080 Weight (kg, breaker only) 0.2/0.350.2/0.350.2/0.35 2/3P ※ - KS certified products. English nameplate and 50Hz marking are not available. - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) 3A is not applicable for UDB30H. 2) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. ■ Accessories •Signal Auxiliary switch 1C, left-hand-side 2 pole Trip alarm switch 1C, left-hand-side 3 pole Shunt trip 1) AUX 10UD L1 AUX 10UD L1T 2) ALT 10UD 2L1 ALT 10UD 2L1T 2) ALT 10UD 3L1 ALT 10UD 3L1T 2) DC24V DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V SHT 10UD A SHT 10UD C SHT 10UD F SHT 10UD H SHT 10UD B SHT 10UD D SHT 10UD AT 2) SHT 10UD CT 2) SHT 10UD FT 2) SHT 10UD HT 2) SHT 10UD BT 2) SHT 10UD DT 2) ※ 1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC 2) Terminal block type •Terminal Interpole barrier 1) 2EA/SET TQQ 10A 3PLINE ※ 1) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA Molded Case Circuit Breaker_ 127 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit 40/45℃ 128 Model / Breaking capacity at AC220/240V Rated current 3A UDB30S 2PT4S0000C 00003 46 UDB30S 3PT4S0000C 00003 32 5A UDB30S 2PT4S0000C 00005 46 UDB30S 3PT4S0000C 00005 32 UDB30S 10A UDB30S 2PT4S0000C 00010 46 UDB30S 3PT4S0000C 00010 32 3 pole 2 pole Code Unit (EA) Code Unit (EA) 5kA 15A UDB30S 2PT4S0000C 00015 46 UDB30S 3PT4S0000C 00015 32 20A UDB30S 2PT4S0000C 00020 46 UDB30S 3PT4S0000C 00020 32 30A UDB30S 2PT4S0000C 00030 46 UDB30S 3PT4S0000C 00030 32 5A UDB30H 2PT4S0000C 00005 46 UDB30H 3PT4S0000C 00005 32 UDB30H 10A UDB30H 2PT4S0000C 00010 46 UDB30H 3PT4S0000C 00010 32 5-10A : 5kA 15-30A : 10kA 15A UDB30H 2PT4S0000C 00015 46 UDB30H 3PT4S0000C 00015 32 20A UDB30H 2PT4S0000C 00020 46 UDB30H 3PT4S0000C 00020 32 30A UDB30H 2PT4S0000C 00030 46 UDB30H 3PT4S0000C 00030 32 5A UDB50S 2PT4S0000C 00005 46 UDB50S 3PT4S0000C 00005 32 10A UDB50S 2PT4S0000C 00010 46 UDB50S 3PT4S0000C 00010 32 15A UDB50S 2PT4S0000C 00015 46 UDB50S 3PT4S0000C 00015 32 UDB50S 20A UDB50S 2PT4S0000C 00020 46 UDB50S 3PT4S0000C 00020 32 5kA 30A UDB50S 2PT4S0000C 00030 46 UDB50S 3PT4S0000C 00030 32 40A UDB50S 2PT4S0000C 00040 46 UDB50S 3PT4S0000C 00040 32 50A UDB50S 2PT4S0000C 00050 46 UDB50S 3PT4S0000C 00050 32 5A UDB50H 2PT4S0000C 00005 46 UDB50H 3PT4S0000C 00005 32 10A UDB50H 2PT4S0000C 00010 46 UDB50H 3PT4S0000C 00010 32 UDB50H 15A UDB50H 2PT4S0000C 00015 46 UDB50H 3PT4S0000C 00015 32 5-10A : 5kA 15-50A : 10kA 20A UDB50H 2PT4S0000C 00020 46 UDB50H 3PT4S0000C 00020 32 30A UDB50H 2PT4S0000C 00030 46 UDB50H 3PT4S0000C 00030 32 40A UDB50H 2PT4S0000C 00040 46 UDB50H 3PT4S0000C 00040 32 50A UDB50H 2PT4S0000C 00050 46 UDB50H 3PT4S0000C 00050 32 15A UDB100S 2PT4S0000C 00015 32 UDB100S 3PT4S0000C 00015 32 20A UDB100S 2PT4S0000C 00020 32 UDB100S 3PT4S0000C 00020 32 30A UDB100S 2PT4S0000C 00030 32 UDB100S 3PT4S0000C 00030 32 UDB100S 40A UDB100S 2PT4S0000C 00040 32 UDB100S 3PT4S0000C 00040 32 5kA 50A UDB100S 2PT4S0000C 00050 32 UDB100S 3PT4S0000C 00050 32 60A UDB100S 2PT4S0000C 00060 32 UDB100S 3PT4S0000C 00060 32 75A UDB100S 2PT4S0000C 00075 32 UDB100S 3PT4S0000C 00075 32 100A UDB100S 2PT4S0000C 00100 32 UDB100S 3PT4S0000C 00100 32 15A UDB100H 2PT4S0000C 00015 32 UDB100H 3PT4S0000C 00015 32 20A UDB100H 2PT4S0000C 00020 32 UDB100H 3PT4S0000C 00020 32 30A UDB100H 2PT4S0000C 00030 32 UDB100H 3PT4S0000C 00030 32 UDB100H 40A UDB100H 2PT4S0000C 00040 32 UDB100H 3PT4S0000C 00040 32 10kA 50A UDB100H 2PT4S0000C 00050 32 UDB100H 3PT4S0000C 00050 32 60A UDB100H 2PT4S0000C 00060 32 UDB100H 3PT4S0000C 00060 32 75A UDB100H 2PT4S0000C 00075 32 UDB100H 3PT4S0000C 00075 32 100A UDB100H 2PT4S0000C 00100 32 UDB100H 3PT4S0000C 00100 32 Specification Category Screw type terminal connection, No option, 50/60Hz MCCB /M1 MCCB | Miniature type / Earth leakage circuit breaker UMG type 30-50AF | •UMG30Ca 1.5kA •UMG30Ra 2.5kA •UMG30Cd 1.5kA •UMG30Sg 5kA •UMG50Sg 5kA •UMG30Cb 1.5kA •UMG30Rb 2.5kA •UMG30Rd 2.5kA •UMG30Hg 10kA •UMG50Hg 10kA UMG30Ca UMG30Cb UMG30Ra UMG30Rb UMG30Cd UMG30Rd UMG30Sg UMG30Hg UMG50Sg UMG50Hg Ampere frame size 30AF 30AF 30AF 50AF Number of poles (P) 2 2 2 2 Degree of protection IP20 IP20 IP20 IP20 Utilization category A A A A earth leakage, overload, short-circuit Protection Rated current (A) Rating 15, 20, 30 15, 20, 30 15, 20, 30 Rated residual current [I△n] (mA) 15, 30 15, 30 15, 30 15, 30 Rated insulation voltage [Ui] (V) AC250 AC250 AC250 AC250 Rated operational voltage [Ue] (V) AC220 AC220 AC220 AC220 Rated impulse withstand voltage [Uimp] (kV) Rated operating time (sec.) Rated Ultimate [Icu] AC220/240V, 50-60Hz 1.5 short-circuit (kA r.m.s.) breaking capacity IEC 60947-2 Service [Ics] % of [Icu] K 60947-2 Earth leakage protection Trip mechanism earth leakage, overload, earth leakage, overload, earth leakage, overload, short-circuit short-circuit short-circuit Earth leakage detection 6 6 6 6 0.03 0.03 0.03 0.03 2.5 1.5 50 2.5 5 50 by current transformer Earth leakage test button 15, 20, 30, 40, 50 ○ ○ 10 5 50 10 50 by current transformer by current transformer by current transformer ○ ○ ○ Hydraulic magnetic - - - - ○ - Thermal magnetic ○ ○ ○ ○ - ○ ○ - Mounting Direct mounting by screw - - ○ - - DIN-rail ○ ○ - ○ ○ Terminal connection Screw d a Dimensions c a b 2P b (mm)c ○ ○ ○ ○ ○ Width 33 33 62 35 35 Height 70 70 82 80 80 60 42 60 42 60 42 60 d 57 76 57 76 58 76 Weight (kg, breaker only) 0.1 0.12 0.1 0.12 0.21 2P Depth 0.13 76 0.15 0.13 0.15 ※ - KS certified products. English nameplate and 50Hz marking are not available. - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. Molded Case Circuit Breaker_ 129 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit 15mA Model / Breaking capacity at AC220/240V Rated current 2 pole Code Unit(EA) 15A UMG30R 2PG3S0000C 00015 150 20A UMG30R 2PG3S0000C 00020 150 30A UMG30R 2PG3S0000C 00030 150 15A UMG30S 2PG3S0000C 00015 80 20A UMG30S 2PG3S0000C 00020 80 30A UMG30S 2PG3S0000C 00030 80 15A UMG30H 2PG3S0000C 00015 80 20A UMG30H 2PG3S0000C 00020 80 30A UMG30H 2PG3S0000C 00030 80 15A UMG50S 2PG3S0000C 00015 80 UMG50S 20A UMG50S 2PG3S0000C 00020 80 30A UMG50S 2PG3S0000C 00030 80 UMG30R 2.5kA UMG30S 5kA UMG30H 10kA 5kA 40A UMG50S 2PG3S0000C 00040 80 50A UMG50S 2PG3S0000C 00050 80 15A UMG50H 2PG3S0000C 00015 80 UMG50H 20A UMG50H 2PG3S0000C 00020 80 10kA 30A UMG50H 2PG3S0000C 00030 80 40A UMG50H 2PG3S0000C 00040 80 50A UMG50H 2PG3S0000C 00050 80 Specification Category 15mA, 40/45℃, Screw type terminal connection, No option, 50/60Hz ELCB/M6 Specification Category 30mA Model / Breaking capacity at AC220/240V UMG30R 2 pole Code Unit(EA) 15A UMG30R 2PG4S0000C 00015 150 20A UMG30R 2PG4S0000C 00020 150 30A UMG30R 2PG4S0000C 00030 150 15A UMG30S 2PG4S0000C 00015 80 20A UMG30S 2PG4S0000C 00020 80 30A UMG30S 2PG4S0000C 00030 80 15A UMG30H 2PG4S0000C 00015 80 20A UMG30H 2PG4S0000C 00020 80 30A UMG30H 2PG4S0000C 00030 80 15A UMG50S 2PG4S0000C 00015 80 UMG50S 20A UMG50S 2PG4S0000C 00020 80 30A UMG50S 2PG4S0000C 00030 80 2.5kA UMG30S 5kA UMG30H 10kA 5kA 40A UMG50S 2PG4S0000C 00040 80 50A UMG50S 2PG4S0000C 00050 80 15A UMG50H 2PG4S0000C 00015 80 UMG50H 20A UMG50H 2PG4S0000C 00020 80 10kA 130 Rated current 30A UMG50H 2PG4S0000C 00030 80 40A UMG50H 2PG4S0000C 00040 80 50A UMG50H 2PG4S0000C 00050 80 30mA, 40/45℃, Screw type terminal connection, No option, 50/60Hz ELCB/M6 MCCB | Miniature type / Earth leakage circuit breaker UDG type 30-100AF | •UDG30S 5kA •UDG50S 5kA •UDG100S 5kA •UDG30H 10kA •UDG50H 10kA •UDG100H 10kA UDG30S UDG30H UDG50S UDG50H UDG100S UDG100H Ampere frame size 30AF50AF100AF 2, 3 2, 3 *2, 3 IP20IP20IP20 AAA earth leakage, overload, short-circuit earth leakage, overload, short-circuit earth leakage, overload, short-circuit 3 1), 5,10,15,20,30 5,10,15,20,30,40,50 15,20,30,40,50,60,75,100 15, 30 15, 30 30, 100 AC460AC460AC460 2P: AC220 2P: AC220 2P: AC220 3P: AC220/4603P: AC220/4603P: AC220/460 Rated impulse withstand voltage [Uimp] (kV) 666 Rated operating time (sec.) 0.030.030.03 5-10A: 2.5 5-10A: 2.5 AC440/460V, 50-60Hz 2.5 2.5 2.5 5 Rated 15-30A: 5 15-50A: 5 Ultimate short-circuit 5-10A: 2.5 5-10A: 2.5 AC380/415V, 50-60Hz 2.5 2.5 2.5 5 breaking capacity [Icu] 15-30A: 5 15-50A: 5 (kA r.m.s.) 5-10A: 5 5-10A: 5 IEC 60947-2 AC220/240V, 50-60Hz 5 5 5 10 15-30A: 10 15-50A: 10 K 60947-2 Service [Ics] % of [Icu] 505050 Earth leakage detection by current transformer by current transformer by current transformer Earth leakage ○○○ Earth leakage test button protection ○○○ Earth leakage indicator Trip mechanism Hydraulic magnetic ○○○ Direct mounting by screw ○○○ Mounting DIN-rail ○○○ Terminal connection Screw ○○○ d a a Width 50/7550/7575 2)/75 c Dimensions b Height 969696 2/3P b (mm) c Depth 606060 d 808080 Weight (kg, breaker only) 2/3P 0.33/0.440.33/0.440.46/0.63 Number of poles (P) Degree of protection Utilization category Protection Rated current (A) Rated residual current [I△n] (mA) Rated insulation voltage [Ui] (V) Rating Rated operational voltage [Ue] (V) ※ - KS certified products. English nameplate and 50Hz marking are not available. - The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue. 1) 3A is not applicable for UDG30H. 2) ✽2P breaker has same dimension as 3P breaker, but the middle pole is removed. ■ Accessories •Signal Auxiliary switch 1C, left-hand-side Trip alarm switch 1C, left-hand-side AUX 10UD L1 2 pole ALT 10UD 2L1 3 pole ALT 10UD 3L1 •Terminal Interpole barrier 1) 2EA/SET TQQ 10A 3PLINE ※ 1) Supplied as standard component Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA Molded Case Circuit Breaker_ 131 U-Series / Molded Case Circuit Breaker Specifications and Standard Order Codes ■ Standard order code and unit 15mA Model / Breaking capacity at AC220/240V Rated current 3A UDG30S 2PG3S0000C 00003 46 UDG30S 3PG3S0000C 00003 32 5A UDG30S 2PG3S0000C 00005 46 UDG30S 3PG3S0000C 00005 32 UDG30S 5kA 10A UDG30S 2PG3S0000C 00010 46 UDG30S 3PG3S0000C 00010 32 15A UDG30S 2PG3S0000C 00015 46 UDG30S 3PG3S0000C 00015 32 20A UDG30S 2PG3S0000C 00020 46 UDG30S 3PG3S0000C 00020 32 30A UDG30S 2PG3S0000C 00030 46 UDG30S 3PG3S0000C 00030 32 5A UDG30H 2PG3S0000C 00005 46 UDG30H 3PG3S0000C 00005 32 UDG30H 10A UDG30H 2PG3S0000C 00010 46 UDG30H 3PG3S0000C 00010 32 5-10A : 5kA 15-30A : 10kA 15A UDG30H 2PG3S0000C 00015 46 UDG30H 3PG3S0000C 00015 32 20A UDG30H 2PG3S0000C 00020 46 UDG30H 3PG3S0000C 00020 32 30A UDG30H 2PG3S0000C 00030 46 UDG30H 3PG3S0000C 00030 32 5A UDG50S 2PG3S0000C 00005 46 UDG50S 3PG3S0000C 00005 32 10A UDG50S 2PG3S0000C 00010 46 UDG50S 3PG3S0000C 00010 32 UDG50S 5kA 15A UDG50S 2PG3S0000C 00015 46 UDG50S 3PG3S0000C 00015 32 20A UDG50S 2PG3S0000C 00020 46 UDG50S 3PG3S0000C 00020 32 30A UDG50S 2PG3S0000C 00030 46 UDG50S 3PG3S0000C 00030 32 40A UDG50S 2PG3S0000C 00040 46 UDG50S 3PG3S0000C 00040 32 50A UDG50S 2PG3S0000C 00050 46 UDG50S 3PG3S0000C 00050 32 5A UDG50H 2PG3S0000C 00005 46 UDG50H 3PG3S0000C 00005 32 10A UDG50H 2PG3S0000C 00010 46 UDG50H 3PG3S0000C 00010 32 UDG50H 15A UDG50H 2PG3S0000C 00015 46 UDG50H 3PG3S0000C 00015 32 5-10A : 5kA 15-50A : 10kA 20A UDG50H 2PG3S0000C 00020 46 UDG50H 3PG3S0000C 00020 32 30A UDG50H 2PG3S0000C 00030 46 UDG50H 3PG3S0000C 00030 32 40A UDG50H 2PG3S0000C 00040 46 UDG50H 3PG3S0000C 00040 32 50A UDG50H 2PG3S0000C 00050 46 UDG50H 3PG3S0000C 00050 32 2 pole Code Unit (EA) 3 pole Code Unit (EA) Specification Category 15mA, 40/45℃, Screw type terminal connection, No option, 50/60Hz ELCB /M6 30mA 132 Model / Breaking capacity at AC220/240V Rated current 3A UDG30S 2PG4S0000C 00003 46 UDG30S 3PG4S0000C 00003 32 5A UDG30S 2PG4S0000C 00005 46 UDG30S 3PG4S0000C 00005 32 UDG30S 5kA 10A UDG30S 2PG4S0000C 00010 46 UDG30S 3PG4S0000C 00010 32 15A UDG30S 2PG4S0000C 00015 46 UDG30S 3PG4S0000C 00015 32 20A UDG30S 2PG4S0000C 00020 46 UDG30S 3PG4S0000C 00020 32 30A UDG30S 2PG4S0000C 00030 46 UDG30S 3PG4S0000C 00030 32 5A UDG30H 2PG4S0000C 00005 46 UDG30H 3PG4S0000C 00005 32 30mA, 40/45℃, UDG30H 10A UDG30H 2PG4S0000C 00010 46 UDG30H 3PG4S0000C 00010 32 5-10A : 5kA 15-30A : 10kA 15A UDG30H 2PG4S0000C 00015 46 UDG30H 3PG4S0000C 00015 32 20A UDG30H 2PG4S0000C 00020 46 UDG30H 3PG4S0000C 00020 32 Screw type terminal connection, No option, 50/60Hz 2 pole Code Unit (EA) 3 pole Code Unit (EA) 30A UDG30H 2PG4S0000C 00030 46 UDG30H 3PG4S0000C 00030 32 5A UDG50S 2PG4S0000C 00005 46 UDG50S 3PG4S0000C 00005 32 10A UDG50S 2PG4S0000C 00010 46 UDG50S 3PG4S0000C 00010 32 UDG50S 5kA 15A UDG50S 2PG4S0000C 00015 46 UDG50S 3PG4S0000C 00015 32 20A UDG50S 2PG4S0000C 00020 46 UDG50S 3PG4S0000C 00020 32 30A UDG50S 2PG4S0000C 00030 46 UDG50S 3PG4S0000C 00030 32 40A UDG50S 2PG4S0000C 00040 46 UDG50S 3PG4S0000C 00040 32 50A UDG50S 2PG4S0000C 00050 46 UDG50S 3PG4S0000C 00050 32 Specification Category ELCB /M6 MCCB Model / Breaking capacity at AC220/240V Rated current 5A UDG50H 2PG4S0000C 00005 46 UDG50H 3PG4S0000C 00005 10A UDG50H 2PG4S0000C 00010 46 UDG50H 3PG4S0000C 00010 32 UDG50H 5-10A : 5kA 15-50A : 10kA 15A UDG50H 2PG4S0000C 00015 46 UDG50H 3PG4S0000C 00015 32 20A UDG50H 2PG4S0000C 00020 46 UDG50H 3PG4S0000C 00020 32 30A UDG50H 2PG4S0000C 00030 46 UDG50H 3PG4S0000C 00030 32 40A UDG50H 2PG4S0000C 00040 46 UDG50H 3PG4S0000C 00040 32 50A UDG50H 2PG4S0000C 00050 46 UDG50H 3PG4S0000C 00050 32 15A UDG100S 2PG4S0000C 00015 32 UDG100S 3PG4S0000C 00015 32 20A UDG100S 2PG4S0000C 00020 32 UDG100S 3PG4S0000C 00020 32 30A UDG100S 2PG4S0000C 00030 32 UDG100S 3PG4S0000C 00030 32 30mA, 40/45℃, UDG100S 5kA 40A UDG100S 2PG4S0000C 00040 32 UDG100S 3PG4S0000C 00040 32 50A UDG100S 2PG4S0000C 00050 32 UDG100S 3PG4S0000C 00050 32 60A UDG100S 2PG4S0000C 00060 32 UDG100S 3PG4S0000C 00060 32 75A UDG100S 2PG4S0000C 00075 32 UDG100S 3PG4S0000C 00075 32 Screw type terminal connection, No option, 50/60Hz 100A UDG100S 2PG4S0000C 00100 32 UDG100S 3PG4S0000C 00100 32 15A UDG100H 2PG4S0000C 00015 32 UDG100H 3PG4S0000C 00015 32 20A UDG100H 2PG4S0000C 00020 32 UDG100H 3PG4S0000C 00020 32 30A UDG100H 2PG4S0000C 00030 32 UDG100H 3PG4S0000C 00030 32 32 UDG100H 3PG4S0000C 00040 32 2 pole Code Unit (EA) 3 pole Code Unit (EA) Specification Category 32 UDG100H 10kA 40A UDG100H 2PG4S0000C 00040 50A UDG100H 2PG4S0000C 00050 32 UDG100H 3PG4S0000C 00050 32 60A UDG100H 2PG4S0000C 00060 32 UDG100H 3PG4S0000C 00060 32 75A UDG100H 2PG4S0000C 00075 32 UDG100H 3PG4S0000C 00075 32 100A UDG100H 2PG4S0000C 00100 32 UDG100H 3PG4S0000C 00100 32 Unit (EA) 3 pole Code Unit (EA) ELCB /M6 100mA Model / Breaking capacity at AC220/240V Rated current 15A UDG100S 2PG5S0000C 00015 32 UDG100S 3PG5S0000C 00015 32 20A UDG100S 2PG5S0000C 00020 32 UDG100S 3PG5S0000C 00020 32 30A UDG100S 2PG5S0000C 00030 32 UDG100S 3PG5S0000C 00030 32 UDG100S 5kA 40A UDG100S 2PG5S0000C 00040 32 UDG100S 3PG5S0000C 00040 32 50A UDG100S 2PG5S0000C 00050 32 UDG100S 3PG5S0000C 00050 32 60A UDG100S 2PG5S0000C 00060 32 UDG100S 3PG5S0000C 00060 32 100mA, 40/45℃, 75A UDG100S 2PG5S0000C 00075 32 UDG100S 3PG5S0000C 00075 32 100A UDG100S 2PG5S0000C 00100 32 UDG100S 3PG5S0000C 00100 32 15A UDG100H 2PG5S0000C 00015 32 UDG100H 3PG5S0000C 00015 32 20A UDG100H 2PG5S0000C 00020 32 UDG100H 3PG5S0000C 00020 32 30A UDG100H 2PG5S0000C 00030 32 UDG100H 3PG5S0000C 00030 32 Screw type terminal connection, No option, 50/60Hz UDG100H 10kA 40A UDG100H 2PG5S0000C 00040 32 UDG100H 3PG5S0000C 00040 32 50A UDG100H 2PG5S0000C 00050 32 UDG100H 3PG5S0000C 00050 32 60A UDG100H 2PG5S0000C 00060 32 UDG100H 3PG5S0000C 00060 32 75A UDG100H 2PG5S0000C 00075 32 UDG100H 3PG5S0000C 00075 32 100A UDG100H 2PG5S0000C 00100 32 UDG100H 3PG5S0000C 00100 32 2 pole Code Specification Category ELCB /M6 Molded Case Circuit Breaker_ 133 Characteristic Curves & Dimensions + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UAB type / 30-100AF, 5-10kA | Tripping & temperature derating curves 36±12 60±20 120±40 180±60 240±80 360±120 480±160 600±200 720±240 900±300 1200±400 Max. (3-30A) 3-100A Tripping time Minute Max. (40-100A) Max. (3-30A) Max. (40-100A) •UAB50C •UAB50R •UAB60C •UAB60R Ambient temperature (°C) Min. (40-100A) Ambient temperature (°C) Min. (3-30A) Second •UAB100C •UAD50C Min. (3-30A) Second •UAB30R Tripping time •UAB30C Derating rate for tripping time (%) Inst. trip current (A) 3 5 10 15 20 30 40 50 60 75 100 Derating rate for tripping time (%) Minute 3-100A Rated current (A) Min. (40-100A) ※Characteristic curves are not applicable. Percentage for rated current (%) Current Dimensions : Center line ※ Percentage for rated current (%) Direct mounting 2P Mounting hole : Handle center line 3P (Unit: mm) M5 screw (3-50A) (Standard connection torque : 20-30 kgf.cm) Current Mounting hole • The allowance of 1.5mm is given around the handle frame. Mounting hole M8 screw (60-100A) 4P (Standard connection torque : 100-120 kgf.cm) [Connection conductor] 24 7 (Max.) 5.5(3~50A) 9(60~100A) 30.5 15 (Max.) 82 50 130 115 16 C3.5 6 Trip button Trip button 25 50 37.5 12.5 25 25 25 6 100 75 50 8 50 17 10 2P 3P 4P 3P 2P 4P 24 M4×0.7 mounting screw 60 (Standard connection torque : 15-20 kgf.cm) 82 [Drilling holes for mounting] 7.5 Trip button 7.5 [Terminal part] [Panel cut-out] 2P 3P 4P 110 R5 12.5 25 ※Distance between mounting holes when installing the product side by side : 51mm(2P), 76mm(3P), 101mm(4P) 136 25 M4×0.7 tapped hole (Standard connection torque : 15-20 kgf.cm) 25 for handle exposure (total breaker height: 64mm) 48 12.5 71 35.5 for handle and trip button exposure (total breaker height: 60mm) 96 MCCB Dimensions ※ : Center line : Handle center line (Unit: mm) • The allowance of 1.5mm is given around the handle frame. Plug-in mounting [Mounting base] [Plug-in connection part] 41 M4 nut+S/W+P/W (Standard connection torque : 15-20 kgf.cm) (Standard connection torque : 15-20 kgf.cm) 20 50 25 162 115 130 87 6 180 10.2 28 (Standard connection torque : 15-20 kgf.cm) 80 M4 nut+S/W+P/W 18.5 RH screw M4×L18+S/W+P/W M6 nut+S/W+P/W 28 (Standard connection torque : 40-50 kgf.cm) 18.5 2 23.5 80 2 22 102 [Panel cut-out] [Drilling holes for mounting] 83 B 34 [Connection conductor] 25 A 4- 6 hole 108 55 6.5 34 19.5 81 21(Max.) 10(Max.) 25 A : Cut-out before bus bar assembly. B : Cut-out for wiring of signal accessories. ※ TDF 10A for line side only type plug-in mounting, please refer to page 210. Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Right Left Handle [ Front ] ※ - AXT is combintaion of AUX and ALT. - In case of 2P, all signal accessories shall be installed in left side of breaker. - UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller. Molded Case Circuit Breaker_ 137 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UAB type / 50-100AF, 25-30kA | •UAB50S •UAB50H •UAB100R 240 180 150 240 120 180 100 150 80 120 60 100 80 40 60 15-32A Rated 15-32A Inst. trip current (A) current (A) 15 16 20 25 30 32 20 40 20 10 8 6 10 8 4 6 4 2 •UAB100S 300±60 320±72 400±80 500±100 600±120 640±128 Max. Max. 2 1 40 1 40 20 Second Second Second Tripping Tripping Tripping time time time Minute Minute Minute Tripping & temperature derating curves 20 10 8 6 10 4 8 6 4 2 Min. Min. 2 1 0.8 0.6 1 0.8 0.4 0.6 0.4 0.2 •UAD50S 0.02 0.01 0.01 •UAD100R 100 120 150 200 300 400 500600 800 1000 18002200 3000 4000 6000 800010000 18002200 3000 Percentage for800rated (%) 100 120 150 200 300 400 500600 1000 current 4000 6000 800010000 Percentage for rated current (%) Current ※Characteristic curves are not applicable. 240 180 150 240 120 180 100 150 80 120 60 100 80 40 60 40-100A 40-100A Rated current (A) Inst. trip current (A) 40 50 60 63 75 80 100 400±80 500±100 600±120 630±126 750±150 800±160 1000±200 40 20 20 10 8 6 10 8 4 6 4 2 2 1 40 1 40 20 Second Second Second Tripping Tripping Tripping time time time Minute Minute Minute Current Derating Derating Derating rate raterate for for rated rated for rated current current current (%) (%) (%) 0.1 0.2 0.08 0.06 0.1 0.04 0.08 0.06 0.04 0.02 Max. Max. 10 20 8 6 10 4 8 6 2 4 Min. Min. 2 1 0.8 0.6 1 0.4 0.8 0.6 0.4 0.2 0.1 0.2 0.08 0.06 0.1 0.04 0.08 0.06 0.02 0.04 0.02 0.01 0.01 100 120 150 200 300 400 500600 800 1000 18002200 3000 4000 6000 800010000 Percentage for (%) 100 120 150 200 300 400 500600 800rated 1000 current 18002200 3000 4000 6000 800010000 Percentage for rated current (%) Current Current Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Right Left Handle [ Front ] 138 ※ - AXT is combintaion of AUX and ALT. - In case of 2P, all signal accessories shall be installed in left side of breaker. - UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller. 130 130 120 120 110 110 100 100 90 90 80 80 0 0 10 20 30 40 50 10 20temperature 30 40 (˚C) 50 Ambient Ambient temperature (˚C) MCCB Dimensions : Center line ※ : Handle center line Direct mounting M5 screw (3-50A) 2P Mounting hole (Unit: mm) • The allowance of 1.5mm is given around the handle frame. 3P (Standard connection torque : 20-30 kgf.cm) 4P Mounting hole M8 screw (60-100A) Mounting hole (Standard connection torque : 100-120 kgf.cm) [Connection conductor] 24 7 (Max.) 5.5(15~30A) 9(60~100A) 8.6 C3.5 [Terminal part] Trip button 7.2 22 7 Trip button 83.5 50 115 130 20.5 Trip button 15 (Max.) 25 50 37.5 75 25 25 100 4.6 50 [Drilling holes for mounting] M4×0.7 mounting screw (Standard connection torque : 15-20 kgf.cm) 82 [Panel cut-out] 4P 3P 2P 4P 24 2P 3P 4P 110 3P 8 16.4 10 53 2P 50 56 60 25 18.5 18.5 M4 nut+S/W+P/W M4 nut+S/W+P/W [Mounting base] [Mounting base] 12.5 torque71 35.5 41 25 (Standard connection torque kgf.cm)connection 41 : 15-20 (Standard : 15-20 kgf.cm) 25 12.5[Plug-in connection 80 80 96 48 RH screw RH screw part] 25 [Plug-in connection part] M4×L18+S/W+P/W M4×L18+S/W+P/W 50 50 M4×0.7 tapped hole (Standard connection 20handle 20 (Standard connection M4 nut+S/W+P/W M4 nut+S/W+P/W for exposure for handle and trip button exposure (Standard connection torque : 15-20 kgf.cm) 25 25 torque : 15-20 kgf.cm) (totaltorque : 15-20height: kgf.cm) 64mm) (Standard connection (Standard connection breaker (total breaker height: 60mm) torque : 15-20 kgf.cm) torque : 15-20 kgf.cm) 56 56 10.2 10.2 28 115 162 115 162 87 180 115 162 115 162 10.2 10.2 28 18.5 28 18.5 55 21(Max.) 6.5 10(Max.) 10(Max.) 6.5 25 21(Max.) 21(Max.) 6.5 6.5 10(Max.) 19.5 [Connection conductor] [Connection conductor] 4- 6 hole 4- 6 hole 10(Max.) 34 34 A : Cut-out before bus bar assembly. A : Cut-out before bus accessories. bar assembly. B : Cut-out for wiring of signal 25 180 A 34 19.5 4- 6 hole 21(Max.) [Drilling holes for mounting] [Drilling holes for mounting] A ※ TDF 10A for line side only type plug-in mounting, please refer to page 210. 81 180 180 4- 6 hole : Cut-out A : Cut-out before bus assembly. A bar B bus bar assembly. before B signal accessories. B : Cut-out for wiringBof :signal accessories. Cut-out for wiring of 81 18.5 [Connection conductor] [Connection conductor] B 34 83 25 22 25 180 34 19.5 81 B [Panel cut-out] 83 [Panel cut-out] 25 25 A 55 34 81 A 22 180 83 25 22 28 [Panel cut-out] 180 83 25 55 [Panel cut-out] 22 80 2 80 2 101 [Drilling holes for mounting] [Drilling holes for mounting] 101 55 23.5 19.5 23.5 18.5 torque : 40-50 kgf.cm) 2 2 28 torque : 40-50 kgf.cm) connection (Standard 2 34 80 101 6 87 130 M6 nut+S/W+P/W (Standard connection M6 nut+S/W+P/W 34 180 87 6 101 130 28 18.5 20 (Standard connection M4M6 nut+S/W+P/W M4×L18+S/W+P/W nut+S/W+P/W M6 nut+S/W+P/W torque : 15-20 kgf.cm) connection (Standard connection (Standard M4 nut+S/W+P/W (Standard connection (Standard connection torque : 15-20 kgf.cm) (Standard connection torque : 40-50 torque torque : 40-50 kgf.cm) kgf.cm): 15-20 56kgf.cm) torque : 15-20 2 kgf.cm) 56 23.5 80 2 18.5 2 23.5 [Mounting base] M4 nut+S/W+P/W 6 (Standard connection torque : 15-20 kgf.cm) [Mounting base] M4 nut+S/W+P/W 80 41 (Standard connection torque : 15-20 kgf.cm) 80 50 50 25 20 25 6 41 28 RH screw [Plug-in connection part] RH screw [Plug-in connection part] M4×L18+S/W+P/W 87 130 Plug-in mounting 130 28 ※Distance between mounting holes when installing the product side by side : 51mm(2P), 76mm(3P), 101mm(4P) Molded Case Circuit Breaker_ 139 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UCB type / 50-100AF, 25-36kA | Tripping & temperature derating curves 30 20 14 10 30 20 14 10 1 1 30 20 30 20 5 Tripping time 2 2 ※Characteristic curves are not applicable. Second Second •UCD100S 0.2 Max. (15-30A) 130 120 130 120 15-40A 110 50-125A 100 90 80 0 0.5 10 15-40A 110 50-125A 100 90 80 30 20 400 50 10 20 30 40 0.1 0.05 0.05 0.02 0.02 0.01 100 125 200 300100 400 125 500 600700 200 1000 300 1500 400 5002000 600700 3000 10004000 1500 2000 3000 4000 Percentage for rated current (%) for rated current (%) Percentage Current Dimensions Current : Center line ※ : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting Mounting hole 3P 4P Mounting hole M8 screw (Standard connection torque : 100-120 kgf.cm) [Connection conductor] 24 8.5(Max.) 2P Mounting hole 101.5 50 155 16 134 9 hole 17 (Max.) M4×0.7 mounting screw Trip button 30 60 60 90 (Standard connection torque : 15-20 kgf.cm) 37 [Terminal part] 30 30 15 22 30 10 45 60 6.5 17.4 84.5 120 7.3 Trip button 24 10.5 Trip button Inhex bolt M8×L25 (Standard connection torque : 100-120 kgf.cm) [Drilling holes for mounting] 15 30 4P 3P 2P 4P 2P 3P 4P 53 3P [Panel cut-out] 132 2P 30 15 30 M4×0.7 tapped hole 59 44 88 26 (Standard connection torque : 15-20 kgf.cm) for handle exposure (total breaker height: 64mm) 140 50 Ambient temperature (˚C) Ambient temperature (˚C) 0.2 0.1 0.01 Max. (15-30A) Min. (15-30A) 1 0.5 Max. (40, 50A) Min. (40-100A) 5 150±30 160±32 200±40 250±50 300±60 320±64 400±80 500±100 600±120 630±126 750±150 800±160 1000±200 Max. (60-100A) Max. (40, 50A) Min. (15-30A) 1 •UCB100S Max. (60-100A) 10 Min. (40-100A) 2 •UCB100R 6 4 2 Inst. trip current (A) 15 16 20 25 30 32 40 50 60 63 75 80 100 Derating rate for rated current (%) 1 10 15-100A Rated current (A) Derating rate for rated current (%) 1 6 4 15-100A 2 Minute Minute 2 Tripping time •UCB50R 4 Hour Hour 4 for handle and trip button exposure (total breaker height: 60mm) 118 MCCB Dimensions ※ : Center line : Handle center line (Unit: mm) • The allowance of 1.5mm is given around the handle frame. Plug-in mounting [Plug-in connection part] (Standard connection torque : 20-30 kgf.cm) M5 nut+S/W+P/W 94 (Standard connection torque : 20-30 kgf.cm) (Standard connection torque : 20-30 kgf.cm) M5 nut+S/W+P/W [Mounting base] 41 RH screw M5×L20+S/W+P/W 21 60 46 27.5 (Standard connection torque : 40-50 kgf.cm) 2 134 M6 nut+S/W+P/W 172.5 191 99 155 6 13.5 48 27.5 30 23.5 81 2 105.5 [Panel cut-out] 26.5 [Drilling holes for mounting] 97 80 A 30 4- 5.5 hole 33.5 26(Max.) 191 55 33.5 93 19.5 6.5 13(Max.) [Connection conductor] B A : Cut-out before bus bar assembly. B : Cut-out for wiring of signal accessories. ※ TDF 10B for line side only type plug-in mounting, please refer to page 210. Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Right Left Handle ※ - AXT is combintaion of AUX and ALT. - In case of 2P, all signal accessories shall be installed in left side of breaker. SHT and UVT are not applicable to 2P. - UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller. [ Front ] Molded Case Circuit Breaker_ 141 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UCB type / 50-125AF, 42-50kA | Hour Hour 4 15-32A Tripping & temperature derating curves 4 1 2 15-32A 2 30 •UCB100H •UCB100L Hour Hour •UCD50H •UCD100H Min. Second Second MinuteMinute Tripping Tripping time time Tripping Tripping time time Second Second 100 125 Max. Min. Max. Min. 200 200 Min. 300 400 500 600700 1000 1500 2000 3000 4000 Percentage for rated current (%) 300 400 500 600700 1000 Current 1500 2000 3000 4000 Current 200 200 300 400 500 600700 40-125A 1000 1500 2000 3000 4000 Percentage for rated current (%) 40-125A 300 400 500 600700 1000 1500 2000 Current Right Handle [ Front ] 142 10 10 20 30 40 Ambient16-30A temperature (˚C) 20 30 40 50 60 50 60 Ambient16-30A temperature (˚C) 80 90 0 80 0 10 10 20 30 40 Ambient temperature (˚C) 20 30 40 50 60 50 60 Ambient temperature (˚C) Percentage for rated current (%) Current Max. (60-125A) 40-125A Max. (60-125A) 40-125A Rated Inst. trip Max. 50A) (A) current (A)(40,current Max. (60-125A) Min. (40-125A) Max. (60-125A) Min. (40-125A) 40 400±80 60 63 75 80 100 125 600±120 630±126 750±150 800±160 1000±200 1250±250 50 (40, 500±100 Max. 50A) Max. (40, 50A) Max. (40, 50A) Min. (40-125A) Min. (40-125A) 200 300 400 500 600 700 1000 1500 2000 3000 4000 Percentage for rated current (%) 200 300 400 500 600 700 1000 Current 1500 2000 3000 4000 Percentage for rated current (%) 200 300 400 500 600 700 1000 1500 2000 3000 4000 Percentage for rated current (%) 200 300 400 500 600 700 1000 Current 1500 2000 130 120 130 40-125A 110 120 100 110 90 100 130 80 90 120 0 130 80 110 0 120 40-125A 10 10 20 30 40 Ambient40-125A temperature (˚C) 20 30 40 50 60 50 60 Ambient40-125A temperature (˚C) 100 110 90 100 Current 3000 4000 Under voltage trip 3 Left 16-30A 100 110 3000 4000 Installation of signal accessories Shunt trip 16-30A 110 120 100 110 Current Trip alarm switch 120 130 90 100 130 80 90 120 0 130 80 110 0 120 Percentage for rated current (%) No. of Auxiliary poles switch 130 90 100 Percentage for rated current (%) Hour Hour MinuteMinute ※Characteristic curves are not applicable. 225±45 240±48 300±60 375±75 450±90 480±96 Derating Derating rate forrate rated forcurrent rated current (%) (%) Derating Derating rate forrate rated forcurrent rated current (%) (%) Second Second •UCB50L 15 16 Max. 20 25 Max. 30 32 Derating Derating rate forrate rated forcurrent rated current (%) (%) Derating Derating rate forrate rated forcurrent rated current (%) (%) •UCB50H 15-32A Rated Inst. trip current (A) current (A) 15-32A Second Second MinuteMinute Tripping Tripping time time Tripping Tripping time time Hour Hour MinuteMinute 20 1 14 10 30 20 6 414 4 10 23 6 44 11 2 30 3 30 20 11 1420 10 3010 30 20 620 14 4 5 10 10 3 6 2 4 5 11 3 2 300.5 20 11 0.2 10 300.5 200.1 5 100.2 0.05 2 50.1 0.02 1 0.05 2 0.01 0.5 0.02 1 0.2 100 125 0.01 0.5 0.1 0.2 100 125 0.05 0.1 0.02 0.05 0.01 0.02 4 100 125 0.01 2 4 1 100 2 125 30 20 1 14 10 30 20 6 414 4 10 23 6 44 11 2 30 3 30 20 11 1420 10 3010 30 20 620 14 45 1010 32 6 45 11 32 300.5 20 11 10 300.2 0.5 200.1 5 100.2 0.05 2 50.1 0.02 1 0.05 2 0.01 0.5 0.02 1 0.2 100 125 0.01 0.5 0.1 0.2 100 125 0.05 0.1 0.02 0.05 0.01 0.02 100 125 0.01 ※ - AXT is combintaion of AUX and ALT. - UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller. 80 90 0 80 0 10 10 20 30 40 Ambient temperature (˚C) 20 30 40 Ambient temperature (˚C) 50 60 50 60 Dimensions : Center line ※ : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 2P, 3P 4P M8 screw 24 (Standard connection torque : 100-120 kgf.cm) [Connection conductor] 8.5(Max.) 9 hole 101 M4×0.7 mounting screw 17 (Max.) (Standard connection torque : 15-20 kgf.cm) [Terminal part] 30 90 30 120 30 10 48 55 10 60 84.5 18 [Drilling holes for mounting] 30 30 4P 3P 4P 3P 53 4P (Standard connection torque : 100-120 kgf.cm) [Panel cut-out] 132 3P 24 Inhex bolt M8×L25 25 30 53 30 53 30 8.5 8 37 10.5 Trip• button Trip button 155 16 50 134 •• 44 88 118 M4 tapped hole (Standard connection torque : 15-20 kgf.cm) for handle exposure (total breaker height: 66mm) for handle and trip button exposure (total breaker height: 60mm) [Mounting base] [Plug-in connection part] M5[Mounting nut+S/W+P/W base] [Plug-in connection part] 41 M5 nut+S/W+P/W (Standard connection torque : RH screw 94 M5 nut+S/W+P/W 41 part] (Standard connection base] [Plug-in connection RHconnection screw 21torque : 20-30 kgf.cm)[Mounting base][Mounting [Plug-in connection part] 94 M5×L20+S/W+P/W 60 torque : Plug-in mounting M5 nut+S/W+P/W (Standard M5 nut+S/W+P/W M5 nut+S/W+P/W 20-30 kgf.cm) 21 81 2 30 B 6.5 191 55 191 191 55 19.5 19.5 19.5 19.5 26(Max.) 6.5 172.5 134 134 172.5 26(Max.) 6.5 26(Max.) 6.5 191 B B 172.5 13.5 13.5 26(Max.) 55 B [Connection conductor] 4- 5.5 hole [Connection conductor] [Connection conductor] 4- 5.5 hole conductor] [Connection 4- 5.5 hole 4- 5.5 hole30 13(Max.) 13(Max.) A 55 93 33.5 33.5 93 33.5 97 A80 33.5 33.5 33.5 93 93 33.5 A 97 80 26.5 26.5 [Panel cut-out] [Drilling holes for mounting] [Panel cut-out] [Drilling holes for mounting] 97 30 97 [Panel cut-out] [Drilling holes for mounting] [Panel cut-out] [Drilling mounting] 80 A 30 holes for 80 26.5 26.5 105.5 105.5 134 191 2 172.5 134 46 191 99 2 6 13(Max.) 81 81 105.5 30 94 60 30 13(Max.) 2 27.5 27.0 99 27.5 27.0 13.5 46 46 99 46 191 46 13.5 191 M6 nut+S/W+P/W (Standard connection torque : (Standard connection2torque : 40-50 kgf.cm) M6 nut+S/W+P/W M6 nut+S/W+P/W 2 40-50 kgf.cm) 23.5 connection torque : (Standard connection torque(Standard : 23.5 2 40-50 kgf.cm) 40-50 kgf.cm) 2 81 23.5 23.5 105.5 6 99 155 M6 nut+S/W+P/W 6 27.0 46 27.0 46 6 155 155 155 27.5 27.5 46 (Standard connection torque kgf.cm) 60 torque : 41 41: 20-30 kgf.cm) (Standard connection torque : 20-30 M5×L20+S/W+P/W connection RH screw (Standard connection torque(Standard : RH screw 94 nut+S/W+P/W M5 nut+S/W+P/W M5 (Standard connection torque : 20-30 kgf.cm) 20-30 kgf.cm) 20-30 kgf.cm)30 20-30 kgf.cm) 21 21 M5×L20+S/W+P/W M5×L20+S/W+P/W 60 connection torque : (Standard connection torque(Standard : connection torque : 20-30 kgf.cm) 20-30 kgf.cm) (Standard connection torque(Standard : 20-30 kgf.cm) 20-30 kgf.cm) 30 33.5 53 MCCB A : Cut-out before bus bar assembly. A : Cut-out before bus bar assembly. B : Cut-out for wiring of signal accessories. : Cut-out for wiring ofAbus signal B : Cut-out before bus bar assembly. A : Cut-out before baraccessories. assembly. ※ TDF 10B for line side only type plug-in mounting, please refer to page 210. Cut-out wiring of signal accessories. B :of signal for accessories. B : Cut-out for wiring Molded Case Circuit Breaker_ 143 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UCB type / 250AF, 18-36kA | Tripping & temperature derating125-250A curves 2 4 1 Min. 5 Min. 2 0.5 1 0.2 0.1 130 120 110 100 90 80 0.5 0 130 120 110 100 10 90 20 30 40 50 80 Ambient temperature (˚C) 0 0.2 10 20 30 60 40 50 60 Ambient temperature (˚C) 0.1 0.02 ※Characteristic curves are not applicable. Max. 10 0.05 •UCD250S Max. Derating rate for rated current (%) Second •UCB250N Tripping time 30 20 Second Tripping time 1 10 1 1250±250 1500±300 1750±350 2000±400 2250±450 2500±500 2 30 20 2 •UCB250S 6 4 Inst. trip current (A) Derating rate for rated current (%) 2 1 •UCB250R 125 150 175 200 225 250 30 20 14 10 6 4 5 Rated current (A) 1 Minute Minute 30 20 14 10 125-250A 2 Hour Hour 4 0.05 0.01 0.02 100 125 0.01 200 300 400 500 600 700 1000 1500 2000 3000 4000 Percentage for rated current (%) 100 125 200 300 400 500 600 700 1000 Current 1500 2000 3000 4000 Percentage for rated current (%) Current Dimensions ※ : Center line : Handle center line • The allowance of 1.5mm is given around the handle frame. Direct mounting 97 Mounting hole 23 M8 screw 23 [with terminal bus bar] option (Standard connection torque : 100-120 kgf.cm) 24 [Terminal part] 35 35 11 140 [Drilling holes for mounting] 4P 35 8 11 23 35 35 35 11 23(Max.) [Panel cut-out] 4P 3P 125 3P 12 55 60 84 3P 4P 28 53 105 35 52.5 9 (Standard connection torque : 15-20 kgf.cm) 26 M4×0.7 tapped hole 103 51.5 138 (Standard connection torque : 15-20 kgf.cm) for handle exposure (total breaker height: 64mm) 144 (Standard connection torque : 100-120 kgf.cm) 11(Max.) 70 4 24 Inhex bolt M8×L25 [Connection conductor] 35 Trip button M4×0.7 mounting screw 24 11.5 Trip button 23 25 4 53 35.5 7 49.5 14.5 23.5 26.5 143 164 44.5 51.5 11 10.5 4P 23 35 Mounting hole 3P (Unit: mm) for handle and trip button exposure (total breaker height: 60mm) MCCB Dimensions ※ : Center line : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) [Mounting base] Plug-in mounting M5 nut+S/W+P/W (Standard connection torque : 20-30 kgf.cm) 8 M5 screw+S/W+P/W 21 19.5 42 74 24 (Standard connection torque : 20-30 kgf.cm) 12.5 25.5 70 112 185 143 28.5 [Plug-in connection part] M8 nut+S/W+P/W (Standard connection torque : 100-120 kgf.cm) 24.7 77.5 57.5 28 25.5 Max. width of conductor : 25mm [Drilling holes for mounting] Attaching angle 25×25×t3 45 6 hole for CBM 20C 2/5 25 19 6 53 13 24 12 15 0.0 6 hole -0.2 70 Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Right Left ※ - AXT is combintaion of AUX and ALT. - UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller. Handle [ Front ] Molded Case Circuit Breaker_ 145 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UCB type / 160-250AF, 42-50kA | Tripping & temperature derating curves 4 100-250A Hour 2 Rated current (A) 1 100 125 150 160 175 200 225 250 30 20 14 10 Minute 6 4 1000±200 1250±250 1500±300 1600±320 1750±350 2000±400 2250±450 2500±500 Derating rate for rated current (%) 2 Inst. trip current (A) 1 Tripping time •UCB160H Max. 30 20 10 Min. 5 2 •UCB160L •UCB250L 120 110 100 90 80 1 Second •UCB250H 130 0 10 20 30 40 50 60 Ambient temperature (˚C) 0.5 0.2 0.1 0.05 •UCD160H 0.02 •UCD250H 0.01 ※Characteristic curves are not applicable. 100 125 200 300 400 500 600 700 1000 1500 3000 4000 Percentage for rated current (%) Current : Center line : Handle center line Direct mounting 4P Mounting hole 97 23 M8 screw (Standard connection torque : 100-120 kgf.cm) 24 4 [Terminal part] [with terminal bus bar] option 23 23 35 Mounting hole 3P 23 11 4 M4×0.7 mounting screw (Standard connection torque : 15-20 kgf.cm) 45 [Connection conductor] 9 8 35 10 48 55 60 84.5 10 35 11 35 35 4P 3P 35 22 (Max.) 35 4P 3P 53 125 4P 35 [Panel cut-out] [Drilling holes for mounting] 3P 23 35 25 53 35 140 11.5 35 53 35 35 105 103 51.5 138 M4 tapped hole (Standard connection torque : 15-20 kgf.cm) 146 for handle exposure (total breaker height: 66mm) 24 Inhex bolt M8×L25 (Standard connection torque : 100-120 kgf.cm) 24 11(Max.) 101 16 50 144 165 23 44.5 (Unit: mm) • The allowance of 1.5mm is given around the handle frame. 11 ※ 10.5 Dimensions for handle and trip button exposure (total breaker height: 60mm) MCCB Dimensions : Center line ※ : Handle center line Plug-in mounting • The allowance of 1.5mm is given around the handle frame. (Unit: mm) M5 nut+S/W+P/W (Standard connection torque : 20-30 kgf.cm) M5 nut+S/W+P/W M5 screw+S/W+P/W (Standard connection torque : 20-30 kgf.cm) (Standard connection torque : 20-30 kgf.cm) [Plug-inM5 connection part] screw+S/W+P/W (Standard connection torque : 20-30 kgf.cm) [Mounting base] [Mounting base] M8 nut+S/W+P/W 42 186 144 42 19.5 Max. width of conductor : 25mm 12.5 25.5 186 12.5 28 144 74 19.5 74 24 8 24 8 (Standard connection torque : 100-120 kgf.cm) 25.5 28.5 25.5 28.5 70 70 112 112 24.7 24.7 77.5 77.5 57.5 57.5 [Drilling holes for mounting] [Drilling holes for mounting] Attaching angle 25×25×t3 Attaching angle 6 hole for CBM 20C 2/545 45 25×25×t3 6 hole for CBM 20C 2/5 Attaching angle 25×25×t3 6 hole for CBM 20C 2/5 45 6 hole fo 25 12 25 13 24 13 24 24 19 19 6 6 19 19 6 6 53 53 53 24 13 13 12 70 15 0.0 6 hole -0.2 6 hole 15 0.0 6 hole -0.2 6 hole 70 70 Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Right Left [ Front ] ※ - AXT is combintaion of AUX and ALT. - UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller. Handle Molded Case Circuit Breaker_ 147 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UCB type / 400AF, 30-100kA | Tripping & temperature derating curves Hour 4 250-400A 2 Rated current (A) 1 250 300 320 350 400 40 Minute 20 10 Inst. trip current (A) 2500±500 3000±600 3200±640 3500±700 4000±800 6 4 Derating rate for rated current (%) 2 1 Tripping time 40 •UCB400R •UCB400S Max. 20 10 Min. 6 4 2 Second •UCB400H •UCB400L 1 115 110 105 100 95 90 85 80 0 5 10 15 20 25 30 35 40 45 50 55 60 Ambient temperature (˚C) 0.6 0.4 0.2 0.1 •UCD400S 0.06 0.04 ※Characteristic curves are not applicable. 0.02 0.01 100 150 200 300 400 500 600 800100012001500 2000 3000 4000 6000 8000 Percentage for rated current (%) Current Dimensions ※ : Center line : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 표면접속 2P, 3P 59 59 12.5 12.5 59 59 84 37 8 4 12.5 13.5 150 95 40 51 24.5 40 257 24.5 317 225 215 150 95 30 11 30 11 44 4P 202 59 44 9.5 12.5 143 51 M6 mounting screw 15 25 25 44 44 25 25 44 140 25 44 185 25 44 25 80 (Standard connection torque : 100-120 kgf.cm) 13 29 30.5 [Connection conductor] Inhex bolt M8×L30 11 12.5(Max.) [Terminal part] 30(Max.) 148 8 95 110 115.5 145 2 37 (Standard connection torque : 40-50 kgf.cm) MCCB Dimensions : Center line ※ : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) [Panel cut-out] [Panel cut-out] [Drilling holes forfor mounting] [Drilling holes mounting] 4P4P 9595 112 112 4444 98 98 215 215 98 98 2P, 3P3P 2P, 5454 (143) 2P, 3P3P (143) 2P, (188) 4P4P (188) forfor handle exposure handle exposure (Standard connection torque : : (Standard connection torque 100-120 kgf.cm) 100-120 kgf.cm) [Drilling holes forfor mounting] [Drilling holes mounting] [Mounting base] [Mounting base] Attaching angle Attaching angle 54 20 15 54 89 20 15 89 112.5 112.5 139.5 139.5 6060 Supportor Supportor M5M5 screw screw 112.5 112.5 139.5 139.5 (Standard (Standard connection connection torque : : torque 20-30 kgf.cm) 20-30 kgf.cm) 4545 1515 9090 140 140 44.5 21 44.5 21 65.5 65.5 M8M8 mounting screw mounting screw 21 44.5 21 44.5 65.5 65.5 Plug-in mounting forfor handle and trip button exposure handle and trip button exposure [Plug-in connection part] [Plug-in connection part] 2222 113 113 71.5 71.5 6 for supportor 6 for supportor 1010 99 6060 Max. with of of conductor : 35mm Max. with conductor : 35mm M10 screw M10 screw (Standard connection torque : 160-230 kgf.cm) (Standard connection torque : 160-230 kgf.cm) 181846.5 46.5 3535 Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Right Left ※ UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller. Handle [ Front ] Molded Case Circuit Breaker_ 149 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UCB type / 630AF, 45-100kA | Tripping & temperature derating curves Hour 4 500-630A 2 1 40 Rated current (A) Inst. trip current (A) 500 630 5000±1000 6300±1260 10 6 4 2 Max. 1 40 Tripping time •UCB630R •UCB630S Derating rate for rated current (%) Minute 20 20 Min. 10 6 4 2 Second •UCB630H •UCB630L 115 110 105 100 95 90 85 80 0 1 5 10 15 20 25 30 35 40 45 50 55 60 Ambient temperature (˚C) 0.6 0.4 0.2 0.1 •UCD630S 0.06 0.04 ※Characteristic curves are not applicable. 0.02 0.01 100 150 200 300 400 500 600 80010001200 1500 2000 3000 4000 6000 8000 Percentage for rated current (%) Current Dimensions : Center line ※ : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 표면접속 4P 210 280 70 70 84 8 34.5 70 70 6 75 280 24.5 75 150 95 243 150 95 24.5 280 8 70 32 16.5 70 13.5 70 9.5 2P, 3P 58 58 M6 mounting screw 70 70 (Standard connection torque : 40-50 kgf.cm) 40 70 40 70 12.5 31 46 150 Inhex bolt M12×L30 [Connection conductor] 12.5(Max.) [Terminal part] 13 (Standard connection torque : 400-450 kgf.cm) 45 (Max.) 80 4 8 34.5 15 95 110 115.5 145 MCCB Dimensions : Center line ※ : Handle center line (Unit: mm) • The allowance of 1.5mm is given around the handle frame. [Drilling holes for mounting] [Panel cut-out] 4P 2P, 3P [Drilling holes for mounting] [Drilling holes for mounting] [Panel cut-out] [Panel cut-out] 4P 4P 95 112 70 61 98 98 98 98 98 243 243 243 98 2P, 3P 2P, 3P 2P, 3P (213) 4P (283) 95 95 112 112 70 70 for handle exposure 61 61 4P (283) 4P (283) [Drilling holes for mounting] [Mounting base] M10 mounting screw for handle exposure for handle exposure (Standard connection torque : 160-230 kgf.cm) Plug-in mounting for handle andbutton trip button exposure for handle and trip exposure 90 M5 screw (Standard Supportor Supportor connection torque : [Plug-in 20-30 kgf.cm) 116.2116.2 151.5 151.5 121.5 45 121.5 59 connection part] 140 140 21 20 210 210 M5 screw M5 screw (Standard (Standard connection connection torque :torque : 20-30 kgf.cm) 20-30 kgf.cm) Attaching Attaching angleangle 45 45 15 15 6 for supportor [Plug-in connection [Plug-in connection part]part] 21 2021 20 44 90 Max. with of conductor : 40mm for supportor 6 for 6supportor M16 screw 59 59 45 45 45 15 60 90 90 46.5 25 71.5 140 210 25 25 46.5 46.5 71.571.5 46.5 25 71.5 90 90 [Drilling holes for mounting] [Drilling holes for mounting] 25 46.5 71.5 25 46.5 71.5 151.5 Supportor 151.5 121.5121.5 151.5 151.5 121.5 121.5 (Standard connection : (Standard connection torque torque : 160-230160-230 kgf.cm)kgf.cm) Attaching angle 30 32 18 20 30 32 18 20 100 100 30 32 18 20 100 [Mounting base] [Mounting base] mounting screw M10 M10 mounting screw 116.2 for handle and trip button exposure 2P,(213) 3P (213) 2P, 3P 11 11 11 (Standard connection torque : 1,000-1,150 kgf.cm) of conductor : 40mm Max.Max. with with of conductor : 40mm screw M16 M16 screw 44 44 60 60 (Standard connection : (Standard connection torque torque : 1,000-1,150 1,000-1,150 kgf.cm)kgf.cm) Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Right Left [ Front ] ※ UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller. Handle Molded Case Circuit Breaker_ 151 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UCB type / 800AF, 45-100kA | Tripping & temperature derating curves Hour 4 700-800A 2 1 Rated current (A) Inst. trip current (A) 40 700 800 7000±1400 8000±1600 Minute 20 10 6 4 2 Derating rate for rated current (%) Max. 1 Tripping time 40 •UCB800R •UCB800S 20 Min. 10 6 4 2 Second •UCB800H •UCB800L 1 115 110 105 100 95 90 85 80 0 5 10 15 20 25 30 35 40 45 50 55 60 Ambient temperature (˚C) 0.6 0.4 0.2 0.1 •UCD800S 0.06 0.04 ※Characteristic curves are not applicable. 0.02 0.01 100 150 200 300 400 500 600 80010001200 1500 2000 3000 4000 6000 8000 Percentage for rated current (%) Current Dimensions : Center line ※ : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 4P 70 280 70 84 10 34.5 6 75 58 9.5 280 24.5 75 150 95 24.5 280 243 150 95 8 13.5 70 70 70 70 32 16.5 70 210 58 M6 mounting screw 70 70 (Standard connection torque : 40-50 kgf.cm) 40 70 40 70 12.5 31 46 152 Inhex bolt M12×L30 [Connection conductor] 12.5(Max.) [Terminal part] 13 (Standard connection torque : 400-450 kgf.cm) 45 (Max.) 80 4 10 34.5 15 95 110 115.5 145 MCCB Dimensions : Center line ※ : Handle center line (Unit: mm) • The allowance of 1.5mm is given around the handle frame. [Drilling holes for mounting] [Panel cut-out] 4P 2P, 3P [Drillingholes holesfor formounting] mounting] [Drilling [Panelcut-out] cut-out] [Panel 4P 4P 95 112 70 98 98 98 243 243 98 98 243 98 2P,3P 3P 2P, 2P, 3P (213) 61 4P (283) 95 95 112 112 70 70 (213) 2P,button 3P(213) for handle and2P, trip exposure 3P 61 61 for handle exposure (283) 4P(283) 4P forhandle handleexposure exposure for M10 mounting screw (Standard connection torque : 160-230 kgf.cm) Plug-in mounting 90 M5 screw 121.5 121.5 151.5 151.5 (Standard connection torque : 20-30 kgf.cm) 59 116.2 116.2 (Standard (Standard connection connection torque: : torque 20-30kgf.cm) kgf.cm) 20-30 45 59 59 M5screw screw M5 46.5 25 71.5 140 210 [Drillingholes holesfor formounting] mounting] [Drilling Attachingangle angle Attaching 45 15 45 45 [Plug-in connection part] 140 140 210 21210 20 15 15 [Plug-inconnection connectionpart] part] [Plug-in 6 for supportor 25 46.5 46.5 25 46.571.5 25 71.5 71.5 Supportor Supportor 90 90 Attaching angle 11 90 25 25 46.5 46.5 71.5 71.5 151.5 Supportor 121.5 151.5 121.5 121.5 151.5 151.5 121.5 (Standardconnection connectiontorque torque: : (Standard 160-230kgf.cm) kgf.cm) 160-230 [Mountingbase] base] [Mounting 30 32 18 20 20 30 30 32 32 18 18 20 100 100 100 M10mounting mountingscrew screw M10 116.2 forhandle handleand andtrip tripbutton buttonexposure exposure for [Drilling holes for mounting] [Mounting base] 2120 20 21 forsupportor supportor Max. with of conductor : 40mm 66for 90 90 45 45 44 M16 screw 60 44 44 11 11 Max.with with conductor 40mm (Standard connection torque : 1,000-1,150 kgf.cm) Max. ofofconductor : :40mm 60 60 M16screw screw M16 (Standardconnection connectiontorque torque: 1,000-1,150 : 1,000-1,150kgf.cm) kgf.cm) (Standard Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Right Left ※ UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller. Handle [ Front ] Molded Case Circuit Breaker_ 153 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UCB type / 1000AF, 100-130kA | Tripping curves Hour 4 3 2 Protection characteristics Minute 505, 535, 565, 600, 630, 640, 680, 720, 760, 800, 850, 900, 950, 1000 Long time setting [tr] 2-4-6-8-12 sec. at Ir x 600% Short time current Ir x NON-200-400-600-800setting [Isd] (A) 1000% STD1) Time delay setting 0-0.1-0.2-0.3 sec. at definite [tsd]1) time-limit section Instantaneous In x NON-300-600-800INST current setting 1000-1100% [Ii] (A) Ground fault In x NON-20-30-40% current [Ig] (A) GFT2) Ground fault delay 0.1-0.2-0.3-0.4-0.8 sec. at setting [tg] definite time-limit section Pre-trip alarm Ir x 90% PTA current [Ip] (A) Rated current LTD setting [Ir] (A) Isd Ii Tripping time 1 50 40 30 20 12 10 8 6 5 4 3 2 for I2t "ON" 1 0.8 0.6 0.5 0.4 0.3 0.2 •UCD1000S ※Characteristics are not applicable. for I2t "OFF" ±20% ±15% + 50ms - 20ms ±20% ±15% + 50ms - 20ms ±10% ※ -T he default values are underlined. Please check and adjust the setting condition of each characteristic before use. -1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob. -2) GFT protection is option. 3000 2500 Ir×% 2000 400 500 600 700 800 900 1000 1100 1200 1300 1500 In×% 300 250 200 125 150 50 80 90 100 40 30 10 20 0.1 0.08 0.06 0.05 0.04 0.03 0.02 0.01 0.008 0.006 0.005 Tolerance Rated (CT) current [In] (A) 1000 10 8 6 5 4 3 2 Second •UCB1000L Setting value or range Characteristics Ip 1 50 40 30 20 •UCB1000S 505-1000A Ir Ig Current Dimensions : Center line ※ Direct mounting : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) UCB1000S Mounting hole M8 mounting screw 4P (Standard connection torque : 100-120 kgf.cm) 73 3P 30 N 14 [Connection conductor] 36 20 16 36 73 45 70 210 70 70 280 45 70 14 25 110 115 159 5 7 80 4P 3P 4P 3P 99 61.5 338 78.5 44 M8 tapped hole 154 70 8 for trip button 25 Inhex bolt M10×L30 (Standard connection torque : 160-230 kgf.cm) [Panel cut-out] [Drilling holes for mounting] (Standard connection torque : 100-120 kgf.cm) 25 45 37.5 70 16 13 14 516 310 [Terminal part] 21 370 45 MCCB Dimensions ※ Direct mounting : Center line : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) UCB1000L Mounting hole M8 screw (Standard connection torque : 100-120 kgf.cm) 4P 73 3P 120 N [Connection conductor] 14 36 20 310 516 370 45 70 45 70 70 70 210 16 73 14 5 70 7 280 80 25 45 115 200 25 14 45 115 Inhex bolt M10×L30 (Standard connection torque : 160-230 kgf.cm) 205 249 [Panel cut-out] [Drilling holes for mounting] 4P 3P 4P 3P 61.5 99 338 78.5 37.5 13 16 36 21 [Terminal part] 44 M8 tapped hole (Standard connection torque : 100-120 kgf.cm) 70 8 for trip button Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Left Right [ Front ] ※ AXT is combintaion of AUX and ALT. Handle Molded Case Circuit Breaker_ 155 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UCB type / 1250AF, 100-130kA | Tripping curves Hour 4 3 2 Protection characteristics Minute •UCD1250S 630, 670, 710, 750, 790, 800, 850, 900, 950, 1000, 1060, 1125, 1190, 1250 Long time setting [tr] 2-4-6-8-12 sec. at Ir x 600% Short time current Ir x NON-200-400-600-800setting [Isd] (A) 1000% STD1) Time delay setting 0-0.1-0.2-0.3 sec. at definite [tsd]1) time-limit section Instantaneous In x NON-300-600-800INST current setting 1000-1100% [Ii] (A) Ground fault In x NON-20-30-40% current [Ig] (A) GFT2) Ground fault delay 0.1-0.2-0.3-0.4-0.8 sec. at setting [tg] definite time-limit section Pre-trip alarm Ir x 90% PTA current [Ip] (A) Rated current LTD setting [Ir] (A) Isd 10 8 6 5 4 3 2 Ii 12 10 8 6 5 4 3 2 ※Characteristics are not applicable. for I2t "ON" 1 0.8 0.6 0.5 0.4 0.3 0.2 for I2t "OFF" 0.1 0.08 0.06 0.05 0.04 0.03 0.02 ± 20% ± 15% + 50ms - 20ms ± 20% ± 15% + 50ms - 20ms ± 10% In×% 3000 2500 2000 400 500 600 700 800 900 1000 1100 1200 1300 1500 300 250 200 125 150 50 80 90 100 40 30 ※ -T he default values are underlined. Please check and adjust the setting condition of each characteristic before use. -1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob. -2) GFT protection is option. 10 20 0.01 0.008 0.006 0.005 Tolerance Rated (CT) current [In] (A) 1250 20 Second •UCB1250L Setting value or range Characteristics Ip 1 50 40 30 Tripping time •UCB1250S 630-1250A Ir Ig 1 50 40 30 20 Ir×% Current Dimensions : Center line ※ Direct mounting : Handle center line T he allowance of 1.5mm is given around the handle frame. (Unit: mm) UCB1250S Mounting hole M8 mounting screw 4P (Standard connection torque : 100-120 kgf.cm) 73 3P 30 N 14 [Connection conductor] 36 20 310 [Terminal part] 70 70 280 45 70 17 25 110 115 159 5 7 80 [Drilling holes for mounting] 4P 3P 99 61.5 338 78.5 44 M8 tapped hole 156 70 8 for trip button 25 Inhex bolt M10×L30 (Standard connection torque : 160-230 kgf.cm) [Panel cut-out] 4P 3P (Standard connection torque : 100-120 kgf.cm) 25 45 14 45 70 210 37.5 70 16 36 73 13 16 21 370 516 45 MCCB Dimensions : Center line ※ Direct mounting : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) UCB1250L Mounting hole (Standard connection torque : 100-120 kgf.cm) 4P 73 3P M8 mounting screw 120 N 14 [Connection conductor] 36 20 310 516 370 45 45 70 70 210 70 16 73 17 70 5 280 7 80 115 25 45 200 14 45 70 25 115 Inhex bolt M10×L30 205 (Standard connection torque : 160-230 kgf.cm) 249 [Panel cut-out] [Drilling holes for mounting] 4P 3P 4P 3P 61.5 99 338 78.5 37.5 13 16 36 21 [Terminal part] 44 M8 tapped hole (Standard connection torque : 100-120 kgf.cm) 70 8 for trip button Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Left Right [ Front ] AXT is combintaion of AUX and ALT. Handle Molded Case Circuit Breaker_ 157 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UCB type / 1600AF, 65kA | Tripping curves Protection characteristics 10000 640-1600A 5000 2000 1000 500 200 Characteristics 100 I2 •UCB1600S Setting value or range Tolerance Rated (CT) current [In] (A) 1600 20 Second Tripping time 50 LTD 10 5 Rated current setting [I1] (A) 640, 800, 960, 1120, 1250, 1440, 1520, 1600 Instantaneous INST current setting [I2] (A) 2 1 0.5 I1 x 200-300-400-500-600700-800-1000% ±10% ※ -T he default values are underlined. Please check and adjust the setting condition of each characteristic before use. 0.2 ±20% 0.1 0.05 0.02 0.01 0.005 100 200 300 400 500600 800 1000 2000 3000 Percentage for rated current (%) Current Dimensions : Center line ※ : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) [with terminal cover and extension handle] 21 [Drilling holes for mounting] 139 151 51 17 24 13 100 32 15 Direct mounting 338 395 16 110 338 568 371 105 45 25 7 151 170 212 40 293 210 50 109 [Extension handle] R25 36 151 [Terminal cover] 60 70 158 70 70 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UPB type / 125-250AF, 85-150kA / Adjustable thermal | Tripping & temperature derating curves 15 16 20 25 30 32 10 8 6 5 4 3 2 Min. 0.1 0.08 0.06 0.05 0.04 0.03 0.02 Inst. trip current (A) 630±126 800±160 1000±200 1250±250 1 0.8 0.6 0.5 0.4 0.3 0.2 95 90 85 80 25 30 35 40 45 Ambient temperature (˚C) 50 55 60 6000 7000 8000 5000 4000 3000 2500 2000 1500 1200 600 700 800 900 1000 500 400 300 Min. Max. 6000 7000 8000 5000 4000 3000 2500 2000 1500 1200 600 700 800 900 1000 500 400 0.01 0.008 0.006 0.005 300 6000 7000 8000 5000 4000 0.1 0.08 0.06 0.05 0.04 0.03 0.02 Current 100 20 250 10 8 6 5 4 3 2 Percentage for rated current (%) 105 15 1250± 375 250 1500± 450 300 1600± 480 320 1750± 525 350 2000± 600 400 2250± 675 450 2500± 750 500 Current 110 10 Inst. trip current (A) 125 150 160 175 200 225 250 Percentage for rated current (%) 115 5 3000 2500 2000 1500 1200 600 700 800 900 1000 500 Max. 400 250 200 100 105 125 150 0.01 0.008 0.006 0.005 300 Min. 0.1 0.08 0.06 0.05 0.04 0.03 0.02 10 8 6 5 4 3 2 Rated current (A) 1 50 40 30 20 Second 1 0.8 0.6 0.5 0.4 0.3 0.2 200 20 Tripping time Tripping time 10 8 6 5 4 3 2 125-250A 1 50 40 30 250 10 8 6 5 4 3 2 4 3 2 200 63 80 100 125 1 50 40 30 20 Second 100 105 125 150 6000 7000 8000 5000 4000 3000 63-125A Rated current (A) 100 105 125 150 Minute 2500 Current 1 50 40 30 Derating rate for rated current (%) Max. Percentage for rated current (%) 20 160 Min. 0.1 0.08 0.06 0.05 0.04 0.03 0.02 Current 4 3 2 0 1 0.8 0.6 0.5 0.4 0.3 0.2 Percentage for rated current (%) •UPD250S Hour 2000 1500 1200 600 700 800 900 1000 500 100 105 125 150 •UPD100S •UPD160S ※Characteristic curves are not applicable. 10 8 6 5 4 3 2 0.01 0.008 0.006 0.005 0.01 0.008 0.006 0.005 250 •UPB250L •UPB250X 200 •UPB250S •UPB250H 400±80 500±100 10 8 6 5 4 3 2 Max. 400 •UPB160L •UPB160X 300 •UPB160S •UPB160H Inst. trip current (A) 40 50 1 50 40 30 20 Second 1 0.8 0.6 0.5 0.4 0.3 0.2 40-50A Rated current (A) 20 Tripping time Tripping time 10 8 6 5 4 3 2 Second •UPB100L •UPB100X 150±30 160±32 200±40 250±50 300±60 320±64 1 50 40 30 20 4 3 2 1 50 40 30 Hour Minute 20 •UPB100S •UPB100H Inst. trip current (A) Minute 1 50 40 30 Hour 15-30A Rated current (A) Minute Hour 4 3 2 MCCB Dimensions : Center line ※ : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 23 35 (Standard connection torque : 100-120 kgf.cm) 35 [Panel cut-out] 4P 3P 112 A 4P 3P 144 144 165 144 165 146 20 11 35 [Drilling holes for mounting] M8 bolt 75.5 4P 140 27.5 3P 105 35 (Standard connection torque : 15-20 kgf.cm) 11 90 113 11 20 11 19 45 45 71 86.5 35 35 23 35 M4 tap 0.7 35 30 (Standard connection torque : 15-20 kgf.cm) 128 [Connection conductor] [Terminal part] [with terminal bus bar] option 23(Max.) 9.5 9.5 Dimension A 24 Line side : 24mm for UPB100 26mm for UPB160, UPB250 Load side : 24mm 24 8.5 (Max.)9 9 10 R5 M4×0.7 tapped hole t4 A Plug-in mounting [Panel cut-out] [Mounting base] 96 41 24 5 109 35 4- 6 mounting hole [Plug-in connection part] 4-M5 tap 26.5 (Standard connection torque : 20-30 kgf.cm) 30 15 37 35 70 105 75 4- 6 tap 31 92.5 110 190 179 113 144 175 190 35 107 30 31 (Standard connection torque : 100-120 kgf.cm) 15 M8 bolt [Drilling holes for mounting] 70 M8 mounting screw (Standard connection torque : 100-120 kgf.cm) 22.5 26 Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Left Right [ Front ] Handle Molded Case Circuit Breaker_ 161 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UPB type / 125-250AF, 85-150kA / Electronic | Tripping curves Hour 4 3 2 50-250A Minute 1 50 40 30 20 1 50 40 30 Tripping time •UPB100S •UPB100H •UPB100L •UPB100X •UPB160S •UPB160H 20 10 8 6 5 4 3 2 •UPB250S •UPB250H •UPB250L •UPB250X Isd = 2..... 10 x Ir 1 0.8 0.6 0.5 0.4 0.3 0.2 Second •UPB160L •UPB160X Ir = 125, 160, 250 10 8 6 5 4 3 2 0.1 0.8 0.6 0.5 0.4 0.3 0.2 0.01 0.8 0.6 0.5 Max. total breaking time t < 10ms Ii = 11 x In 50 70 100 150 200 300 400 500 700 1000 1500 2000 3000 4000 50007000 8000 10000 15000 20000 30000 Ir×% Current Protection characteristics Characteristics Rated (CT) current [In] (A) LTD STD PTA UPB100 UPB160 UPB250 125 160 250 Rated current setting [Ir] (A) 50, 55, 63, 70, 63, 70, 80, 90, 100, 110, 125, 80, 90, 100, 100, 110, 125, 140, 160, 175, 115, 125 140, 160 200, 225, 250 Long time setting [tr] 6.25 sec. at Ir x 600% Short time current setting Ir x NON-200-300-400-500-600-700-800-900- [Isd] (A) 1000% Time delay setting [tsd] INST Setting value or range Instantaneous current setting [Ii] (A) Pre-trip alarm current [Ip] (A) Tolerance ±20% 0.05-0.1-0.2-0.3 sec. at definite time-limit + 50ms section - 20ms In x 1100% ±20% Ir x 90% ±10% ※ -The default values are underlined. Please check and adjust the setting condition of each characteristic before use. 162 MCCB Dimensions : Center line ※ : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 23 35 (Standard connection torque : 100-120 kgf.cm) 35 [Panel cut-out] 4P 3P 112 A 4P 3P 144 144 165 144 165 146 20 11 35 [Drilling holes for mounting] M8 bolt 75.5 4P 140 27.5 3P 105 35 (Standard connection torque : 15-20 kgf.cm) 11 90 113 11 20 11 19 45 45 71 86.5 35 35 23 35 M4 tap 0.7 35 30 (Standard connection torque : 15-20 kgf.cm) 128 [Connection conductor] [Terminal part] [with terminal bus bar] option 23(Max.) 9.5 9.5 Dimension A 24 Line side : 24mm for UPB100 26mm for UPB160, UPB250 Load side : 24mm 24 8.5 (Max.)9 9 10 R5 M4×0.7 tapped hole t4 A Plug-in mounting [Panel cut-out] [Mounting base] 96 41 24 5 109 35 4- 6 mounting hole [Plug-in connection part] 4-M5 tap 26.5 (Standard connection torque : 20-30 kgf.cm) 30 15 37 35 70 105 75 4- 6 tap 31 92.5 110 190 179 113 144 175 190 35 107 30 31 (Standard connection torque : 100-120 kgf.cm) 15 M8 bolt [Drilling holes for mounting] 70 M8 mounting screw (Standard connection torque : 100-120 kgf.cm) 22.5 26 Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Left Right [ Front ] Handle Molded Case Circuit Breaker_ 163 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | UPB type / 400-630AF, 85-150kA | Tripping curves Hour 4 3 2 Protection characteristics 200-630A Ir Ig 1 Setting value or range Characteristics Ip Minute 20 Isd 10 8 6 5 4 3 Ii Tripping time 1 50 40 30 Long time setting [tr] Short time current setting [Isd] (A) 1) STD Time delay setting [tsd] 1) Instantaneous INST current setting [Ii] (A) Ground fault current [Ig] (A) GFT2) Ground fault delay setting [tg] Pre-trip alarm PTA current [Ip] (A) 20 12 10 8 6 5 4 3 2 •UPB630S •UPB630H for I2t "ON" 1 0.8 0.6 0.5 0.4 0.3 0.2 Second •UPB400L •UPB400X •UPB630L •UPB630X for I t "OFF" 2 0.1 0.08 0.06 0.05 0.04 0.03 Ir×% Current Dimensions Direct mounting ※ : Center line 4P 27.5 : Handle center line 320, 340, 360, 380, 400, 430, 450, 480, 500, 540, 570, 600, 630 2-4-6-8-12 sec. at Ir x 600% Ir x NON-200-400-600-8001000% 0-0.1-0.2-0.3 sec. at definite time-limit section ± 20% ± 15% + 50ms - 20ms In x NON-300-600-8001000-1100% ± 20% In x NON-20-30-40% ± 15% 0.1-0.2-0.3-0.4-0.8 sec. at definite time-limit section + 50ms - 20ms Ir x 90% ± 10% • The allowance of 1.5mm is given around the handle frame. (Unit: mm) 15 12.5 (Standard connection torque : 160-230 kgf.cm) 201 112.5 142.5 161.5 98.5 128.5 255 M5 mounting screw 16 47 13 60 52.5 30 60 210 60 10 [Connection conductor] [Terminal part] 15 (Max.) 113 63 30 (Max.) 14 16 10.5 100 130 45 119.5 159.5 [Panel cut-out] 4P 3P [Drilling holes for mounting] 4P 3P M5 tapped hole 15 (Standard connection torque : 20-30 kgf.cm) 15 150 81 16 16 16 47 30 60 60 6 M10 screw option 39.5 16 16 16 47 24 15 [with terminal bus bar] 27.5 16 47 185 24 12.5 15 140 15 13 164 200, 215, 225, 240, 250, 255, 270, 290, 300, 320, 340, 360, 380, 400 Tolerance UPB400, UPD400S 3P (Standard connection torque : 20-30 kgf.cm) UPB630 630 ※ -T he default values are underlined. Please check and adjust the setting condition of each characteristic before use. -1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob. -2) GFT protection is option. 2000 2500 3000 1500 600 700 800 900 1000 1100 1200 1300 In×% 400 500 250 300 200 50 80 90 100 125 150 40 30 0.01 0.008 0.006 0.005 ※Characteristics are not applicable. 10 20 0.02 •UPD400S •UPD630S Rated current setting [Ir] (A) LTD 2 •UPB400S •UPB400H UPB400 400 Rated (CT) current [In] (A) 50 40 30 34 33.5 Inhex bolt M10×L30 (Standard connection torque : 160-230 kgf.cm) MCCB option option option [with terminal bus bar] [with terminal bus bar] option [with terminal bus bar] [with terminal bus bar] [with terminal bus bar] 85.5 55 15 [Panel cut-out] 144 M5 mounting mounting screw M5mounting mounting screw 45screw M5 M5 mounting screw M5 screw 16 47 22.5 (Standard connection torque : (Standard connection torque : torque (Standard connection (Standard connection torque : (Standard connection torque : : 20-30 kgf.cm) 20-30 kgf.cm) 20-30kgf.cm) kgf.cm) 20-30 kgf.cm)20-30 10 10119.5 119.5 119.5 119.5 10 10 119.5 10 159.5 159.5 159.5 159.5 159.5 15 15 15 15 15 81 15 15 15 81 1581 81 81 [Mounting base] 57.7 33.5 5 16 47 16 47 1616 47 47 16 47 15 41.5 41.5 41.541.5 41.5 8 8 M10 screw screw M10 screw M10M10 screw 130 1352.530 52.5 30 3052.5 30 52.5 13 52.5 30 13 60 6060 60 60 60 60 60 60 60 60 6060 60 60 210 210 210210 210 option M10 screw 8 8 : 160-2308kgf.cm) (Standard connection torque (Standard connection torque : 160-230 (Standard connection torque :kgf.cm) 160-230kgf.cm) kgf.cm) (Standard connection torque : 160-230 kgf.cm) (Standard connection torque : 160-230 115.5 102.5 16 24 15 4724 16 16 16 16 15 16 15 16 47 47 16 16 16 16 15 15 47 47 30 13 30 13 30 30 13 13 60 30 13 60 60 60 6060 60 6060 60 150 150 150 150 150 15 15 13 13 16 16 47 16 16 47 1616 16 16 47 47 140 185 185 185 185 27.5 27.5 4P 4P 4P185 27.5 27.5 27.5 27.5 27.527.527.527.5 140 4P 4P 12.5 12.5 15 12.5 15 12.5 12.5 12.5 12.512.5 15 15 12.5 12.5 15 (Unit: mm) • The allowance of 1.5mm is given around the handle frame. 24 24 24 24 24 16 16 16 15 24 128.5 98.5 24 16 15 16 16 47 142.5 112.5 128.5 98.5 47 255 142.5 112.5 16 16 16 15 16 1616 2415 128.5 128.5 255 98.5 98.5 47 47 142.5 112.5 142.5 112.5 255 16 16 16 15 255 128.5 98.5 47 142.5 112.5 255 UPB630, UPD630S 3P 1403P 3P 3P 3P 140 140 15 15 Direct mounting : Handle center line 85.5 5585.5 55 85.5 85.5 55 55 : Center line ※ 115.5 102.5 115.5 102.5 115.5 115.5 102.5 102.5 Dimensions 45 119.5 124.5 164.5 298 274 188 227 270 298 14 16 14 14 16 16 14 16 14 16 15 (Max.) 63 63 63 10.5 3433.5 33.5 33.5 34 33.5 34 33.5 Inhex bolt M10×L30 Inhex bolt M10×L30 Inhex bolt M10×L30 Inhex bolt M10×L30 45 Inhex bolt(Standard M10×L30 connection torque : (Standard connection torque : torque 30 (Max.) 30(Max.) (Max.) (Standard connection connection torque : 30 (Max.) (Max.) 30 39 (Standard connection torque : : 52.5 160-230 kgf.cm) 90 (Standard 160-230 kgf.cm) 30 160-230 kgf.cm) 160-230 kgf.cm) 160-230 kgf.cm) 140 34 34 22.5 45 45 63 63 15 (Max.) 15 (Max.) 37.5 30 37.5 180 15 (Max.) 15 (Max.) 45 113 41.5 (Standard connection (Standard connection (Standard connection (Standard connection (Standard connection torque : 20-30 kgf.cm) torque : 20-30 kgf.cm) torque : 20-30kgf.cm) kgf.cm) torque : 20-30 kgf.cm) torque : 20-30 45 130 130 tapped hole tapped holeM5hole M5 tapped M5 M5 tapped hole M5 tapped hole 10.5 10.510.5 10.5 130 130 113 100 100 41.5113 41.5 130 113 100 113 41.5 41.5 100 100 [Panel cut-out] [Drilling holes for mounting] [Panel cut-out] [Drilling holes for mounting] [Panel cut-out] [Drilling holes for mounting] [Panel cut-out] [Drilling holes for mounting] [Panel cut-out] [Drilling holes for mounting] 4P 4P 4P 4P 4P 4P 4P 4P 4P 3P 4P 3P 3P 3P 3P 3P 3P 3P 3P 3P [Terminal [Connection conductor] [Terminal part] [Connection conductor] [Terminal part] part] [Connection conductor] [Terminal part] [Connection conductor] [Terminal part] [Connection conductor] Plug-in mounting [Mounting base] 130 144 45 22.5 57.7 33.5 5 [Panel cut-out] [Drilling holes for mounting] [Plug-in connection part] 27 4-M5 tap M5 mounting screw 18.5 155 298 274 188 227 270 298 37.5 30 37.5 180 (Standard connection torque : 20-30 kgf.cm) 11.5 (Standard connection torque : 20-30 kgf.cm) 45 90 140 39 52.5 90 22.5 119.5 124.5 164.5 27 Installation of signal accessories No. of Auxiliary poles switch [Drilling holes for mounting] Trip alarm Shunt Under switch trip voltage trip [Plug-in connection part] 27 4-M5 tap 3 (Standard connection torque : 20-30 kgf.cm) [ Front ] 155 M5 mounting screw 18.5 Right (Standard connection torque : 20-30 kgf.cm) Handle 11.5 Left 90 27 Molded Case Circuit Breaker_ 165 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | Motor protection / UPB type 125-250AF, 100-130kA | Max.Max. Min.Min. Minute 0.5 0.5 0.2 0.2 5 2 2 1 1 0.1 0.1 0.05 0.04 0.03 0.02 0.05 0.04 0.03 0.02 100 7000 7000 5000 5000 3000 2000 3000 2000 600 400 700 800 600 900 700 1000 800 1100 900 1200 1000 1300 1100 1200 1300 400 300 300 200 125 200 0.01 0.01 125 100 0.01 0.01 Percentage Percentage for rated for rated current current (%) (%) Percentage Percentage for rated for rated current current (%) (%) Current Current Current Current Instantaneous trip current UPB100 Rated current 6 (A) 2.5 Multiple for rated current 15 7 8 9 10 11 12 13 17.5 20 22.5 25 27.5 30 32.5 3.2 19.2 22.4 25.6 28.8 32 35.2 38.4 41.6 6.3 37.8 44.1 50.4 56.7 63 69.3 75.6 81.9 12.5 75 87.5 100 112.5 125 137.5 150 162.5 20 120 140 160 180 200 220 240 260 32 192 224 256 288 320 352 384 416 50 300 350 400 450 500 550 600 650 63 378 441 504 567 630 693 756 819 80 480 560 640 720 800 880 960 1040 100 600 700 800 900 1000 1100 1200 1300 ※ Tolerance for setting current: -20% - +30% UPB250 Rated current (A) 5 6 7 8 9 10 125 625 750 875 1000 1125 1250 Multiple for rated current 150 750 900 1050 1200 1350 1500 175 875 1050 1225 1400 1575 1750 200 1000 1200 1400 1600 1800 2000 225 1125 1350 1575 1800 2025 2250 ※ Tolerance for setting current: -20% - +30% 166 Max.Max. Min.Min. 0.2 0.2 0.05 0.04 0.03 0.02 100 5 Instantaneous Instantaneous trip trip current current (500-1000%) (500-1000%) 0.5 0.5 0.1 0.1 0.05 0.04 0.03 0.02 10 7000 1 10 7000 5000 1 30 20 5000 2 1 30 20 3000 5 2 2 1 2000 3000 5 2 1500 2000 10 30 20 14 10 6 4 500 400 600 700 500 800 600 900 700 1000 800 900 1000 1500 10 Instantaneous Instantaneous trip trip current current (600-1300%) (600-1300%) 30 20 14 10 6 4 250A250A 400 300 30 20 1 300 200 30 20 2 1 Hour 1 Hour 2 1 4 2 Minute 2 Minute 30 20 14 10 6 4 4 Second 30 20 14 10 6 4 Tripping time Tripping time 1 125A125A Second 1 Hour 2 125 200 •UPB250L 4 2 125 100 •UPB250H 4 Second •UPB100L Second •UPB100H Tripping time Tripping time Minute Hour Tripping curves MCCB Dimensions : Center line ※ : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 23 35 (Standard connection torque : 100-120 kgf.cm) 35 [Panel cut-out] 4P 3P 112 A 4P 3P 144 144 165 144 165 146 20 11 35 [Drilling holes for mounting] M8 bolt 75.5 4P 140 27.5 3P 105 35 (Standard connection torque : 15-20 kgf.cm) 11 90 113 45 35 35 23 [Terminal part] [with terminal bus bar] M4 tap 0.7 35 30 (Standard connection torque : 15-20 kgf.cm) 24 Line side : 24mm for UPB100 26mm for UPB250 Load side : 24mm 24 8.5 (Max.)9 9.5 9.5 Dimension A t4 Plug-in mounting A [Panel cut-out] [Mounting base] 96 41 24 5 109 35 15 4- 6 mounting hole [Drilling holes for mounting] [Plug-in connection part] 4-M5 tap 26.5 (Standard connection torque : 20-30 kgf.cm) 31 37 30 75 4- 6 tap 15 92.5 110 35 70 105 190 179 113 144 175 190 35 107 30 31 (Standard connection torque : 100-120 kgf.cm) 35 option 23(Max.) M8 bolt 10 128 [Connection conductor] 9 11 20 11 19 45 71 86.5 R5 M4×0.7 tapped hole 70 M8 mounting screw (Standard connection torque : 100-120 kgf.cm) 22.5 26 Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch Shunt trip Under voltage trip 3 Left Right [ Front ] Handle Molded Case Circuit Breaker_ 167 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | Q-class (for nuclear power plant application) / HBL type 100AF, 85kA | 4 3 2 1 50 40 30 Inst. trip current (A) 15 20 30 150±30 200±40 300±60 10 8 6 5 4 3 2 30 20 Tripping time 2 Hour Rated current (A) Inst. trip current (A) 60 75 100 600±120 750±150 1000±200 Minute 20 10 8 6 5 4 3 Derating rate for rated current (%) 2 1 50 40 Tripping time 30 20 10 8 6 5 4 3 Second 2 1 0.8 0.6 0.5 0.4 0.3 Min. 0.1 0.08 0.06 0.05 0.04 0.03 Max. 0.02 Current Installation of signal accessories Handle [ Front ] 168 Under voltage trip 6000 7000 8000 5000 4000 2500 3000 2000 1500 600 700 800 900 1000 1200 500 400 250 300 200 100 105 125 150 Percentage for rated current (%) Right 6000 7000 8000 5000 110 105 100 95 90 85 80 5 10 15 20 25 30 35 40 Ambient temperature (˚C) 0.01 0.008 0.006 0.005 Left 115 0 0.2 3 4000 Current 60-100A 1 50 40 30 Shunt trip 2000 Percentage for rated current (%) Current 4 3 2 1500 Percentage for rated current (%) Max. 600 700 800 900 1000 1200 6000 7000 8000 5000 4000 2500 3000 2000 1500 600 700 800 900 1000 1200 500 400 250 300 0.02 0.01 0.008 0.006 0.005 200 0.02 0.01 0.008 0.006 0.005 100 105 125 150 Min. 0.1 0.08 0.06 0.05 0.04 0.03 2500 3000 0.2 Max. 250 300 Min. 1 0.8 0.6 0.5 0.4 0.3 500 1 0.8 0.6 0.5 0.4 0.3 400 S Second 2 10 8 6 5 4 3 100 105 125 150 Tripping time 10 8 6 5 4 3 0.2 Trip alarm switch 400±80 500±100 10 8 6 5 4 3 2 0.1 0.08 0.06 0.05 0.04 0.03 No. of Auxiliary poles switch Inst. trip current (A) 40 50 1 50 40 30 20 Second •HBL103UQ Rated current (A) 20 1 50 40 •HBL103U 40-50A 1 50 40 30 200 Minute 20 4 3 2 Hour 15-30A Rated current (A) Minute Hour Tripping & temperature derating curves 45 50 55 60 MCCB Dimensions ※ : Center line : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 112 35 [with terminal bus bar] A Terminal cover option Dimension A Line side : 24mm Load side : 24mm M8 bolt t4 144 185 146 (Standard connection torque : 100-120 kgf.cm) A [Connection conductor] 10 71 86.5 Terminal cover 24 8.5 70 105 9(Max.) 9.5 9.5 9 [Terminal part] 23(Max.) 24 M4 tap 0.7 (Standard connection torque : 15-20 kgf.cm) [Panel cut-out] [Drilling holes for mounting] 3P 27.5 144 75.5 3P R5 M4×0.7 tapped hole 35 (Standard connection torque : 15-20 kgf.cm) 30 Molded Case Circuit Breaker_ 169 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | Q-class (for nuclear power plant application) / HBL type 100AF, 85kA / Motor protection | Tripping curves 4 100A Hour 2 1 30 20 14 10 Minute 6 4 2 1 1 30 Tripping time •HBL103UM Instantaneous trip current (600-1300%) 20 10 5 2 •HBL103UMQ Min. Second 1 Max. 0.5 0.2 0.1 0.05 0.04 0.03 0.02 7000 5000 3000 2000 600 700 800 900 1000 1100 1200 1300 400 300 200 125 100 0.01 Percentage for rated current (%) Current Instantaneous trip current Rated current 6 (A) 2.5 15 Multiple for rated current 7 8 9 10 11 12 13 17.5 20 22.5 25 27.5 30 32.5 41.6 3.2 19.2 22.4 25.6 28.8 32 35.2 38.4 6.3 37.8 44.1 50.4 56.7 63 69.3 75.6 81.9 12.5 75 87.5 100 112.5 125 137.5 150 162.5 20 120 140 160 180 200 220 240 260 32 192 224 256 288 320 352 384 416 50 300 350 400 450 500 550 600 650 63 378 441 504 567 630 693 756 819 80 480 560 640 720 800 880 960 1040 100 600 700 800 900 1000 1100 1200 1300 ※ Tolerance for setting current: -20% - +30% Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch 3 Left Right [ Front ] 170 Handle Shunt trip Under voltage trip MCCB Dimensions ※ : Center line : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 112 35 [with terminal bus bar] A Terminal cover option Dimension A Line side : 24mm Load side : 24mm M8 bolt t4 144 185 146 (Standard connection torque : 100-120 kgf.cm) A [Connection conductor] 10 71 86.5 Terminal cover 24 8.5 70 105 9(Max.) 9.5 9.5 9 [Terminal part] 23(Max.) 24 M4 tap 0.7 (Standard connection torque : 15-20 kgf.cm) [Panel cut-out] [Drilling holes for mounting] 3P 27.5 144 75.5 3P R5 M4×0.7 tapped hole 35 (Standard connection torque : 15-20 kgf.cm) 30 Molded Case Circuit Breaker_ 171 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | Q-class (for nuclear power plant application) / HBL type 225AF, 85kA | Hour Tripping & temperature derating curves 4 3 125-225A 2 Rated current (A) Minute 1 50 40 30 1500 20 175 1750 10 8 6 5 4 3 2 200 2000 225 2250 +375 -250 +450 -300 +525 -350 +600 -400 +675 -450 Derating rate for rated current (%) •HBL203UQ 1250 150 1 50 40 30 20 Tripping time •HBL203U Inst. trip current (A) 25 10 8 6 5 4 3 Second 2 1 0.8 0.6 0.5 0.4 0.3 Min. Max. 0.2 0.02 60 Current 1 50 40 30 20 10 8 6 5 4 3 2 Derating rate for rated current (%) 1 50 40 30 20 10 8 6 5 4 3 2 1 0.8 0.6 0.5 0.4 0.3 Min. Max. 0.2 110 105 100 95 90 85 80 0 5 10 15 20 25 30 35 40 Ambient temperature (˚C) 0.1 0.08 0.06 0.05 0.04 0.03 0.02 6000 7000 8000 5000 4000 3000 2500 2000 1500 1200 600 700 800 900 1000 500 400 300 250 200 150 125 0.01 .008 .006 .005 100 105 115 Installation of signal accessories Percentage for rated current (%) Current No. of Auxiliary poles switch Trip alarm switch 3 Left Right [ Front ] 172 Handle Shunt trip Under voltage trip 45 50 6000 7000 8000 4000 55 Percentage for rated current (%) 2 5000 3000 2500 2000 1500 1200 600 700 800 900 1000 500 400 300 250 200 150 125 100 105 0.01 0.008 0.006 0.005 125-225A 110 105 100 95 90 85 80 0 5 10 15 20 25 30 35 Ambient temperatur 0.1 0.08 0.06 0.05 0.04 0.03 4 3 115 MCCB Dimensions ※ : Center line : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 112 35 [with terminal bus bar] A Terminal cover option Dimension A Line side : 26mm Load side : 24mm M8 bolt t4 144 185 146 (Standard connection torque : 100-120 kgf.cm) A [Connection conductor] 10 71 86.5 Terminal cover 24 8.5 70 105 9(Max.) 9.5 9.5 9 [Terminal part] 23(Max.) 24 M4 tap 0.7 (Standard connection torque : 15-20 kgf.cm) [Panel cut-out] [Drilling holes for mounting] 3P 27.5 144 75.5 3P R5 M4×0.7 tapped hole 35 (Standard connection torque : 15-20 kgf.cm) 30 Molded Case Circuit Breaker_ 173 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | Q-class (for nuclear power plant application) / HBL type 225AF, 85kA / Motor protection | Tripping curves Hour 4 225A 2 1 Minute 30 20 14 10 6 4 2 1 Tripping time 30 20 •HBL203UM Instantaneous trip current (500-1000%) 10 5 •HBL203UMQ 2 Min. Second 1 Max. 0.5 0.2 0.1 0.05 0.04 0.03 0.02 7000 5000 3000 2000 1500 500 600 700 800 900 1000 400 300 200 125 100 0.01 Percentage for rated current (%) Current Instantaneous trip current Rated current (A) 5 6 7 8 9 10 125 625 750 875 1000 1125 1250 1500 Multiple for rated current 150 750 900 1050 1200 1350 175 875 1050 1225 1400 1575 1750 200 1000 1200 1400 1600 1800 2000 225 1125 1350 1575 1800 2025 2250 ※ Tolerance for setting current: -20% - +30% Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch 3 Left Right Handle [ Front ] 174 Shunt trip Under voltage trip MCCB Dimensions ※ : Center line : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 112 35 [with terminal bus bar] A Terminal cover option Dimension A Line side : 26mm Load side : 24mm M8 bolt t4 144 185 146 (Standard connection torque : 100-120 kgf.cm) A [Connection conductor] 10 71 86.5 Terminal cover 24 8.5 70 105 9(Max.) 9.5 9.5 9 [Terminal part] 23(Max.) 24 M4 tap 0.7 (Standard connection torque : 15-20 kgf.cm) [Panel cut-out] [Drilling holes for mounting] 3P 27.5 144 75.5 3P R5 M4×0.7 tapped hole 35 (Standard connection torque : 15-20 kgf.cm) 30 Molded Case Circuit Breaker_ 175 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | Miniature type / Molded case circuit breaker | Tripping & temperature derating curves 240 240 15-30A 120 15-30A 60 60 10 10 Max. 10 20 Derating rate for rated current (%) Max. 20 1 40 6 10 4 6 2 4 Second •UMB30Rb Tripping time •UMB30Ra 1 40 2 Second Tripping time 2 Min. 1 2 Derating rate for rated current (%) Minute Minute 120 150 100 100 Min. 1 150 50 50 0 0 10 20 30 40 50 Ambient temperature (°C) 10 20 30 40 50 Ambient temperature (°C) 0.2 0.1 Instantaneous trip (800-2000%) 0.2 0.1 0.02 0.02 0.01 0.01 1 Max. total breaking time Instantaneous trip (800-2000%) 1 1.5 1.5 2 2 3 3 4 Max. total breaking time 5 6 7 8 10 15 20 30 Multiple for rated current (times) 4 5 6 7 8 10 15 20 Current 30 40 50 40 50 70 70 100 100 Multiple for rated current (times) Dimensions ※ Current : Center line : Handle center line • The allowance of 1.5mm is given around the handle frame. Direct mounting 33 UMB30Ra:45/UMB30Rb:63 20 UMB30Ra:42/UMB30Rb:60 [Terminal part] 6.2 IEC35mm DIN-rail 10.2 5.2 5.2 Load side UMB30Ra:56.5/UMB30Rb:76 [Panel cut-out] 59 38 [Drilling holes for mounting] 35 176 10.2 6.2 70 56 36 Line side UMB30Ra:7.5 UMB30Rb:25.5 (Unit: mm) MCCB Tripping & temperature derating curves 240 15-50A 120 240 60 15-50A Minute 120 60 Derating rate for rated current (%) 10 2 •UMB50Sg 1 Max. 40 10 20 6 4 Max. 10 6 2 4 1 Min. 2 Second •UMB30Sg 2 20 SecondTripping time Tripping time 1 40 Min. 150 Derating rate for rated current (%) Minute 10 150 100 50 100 0 1 20 30 40 50 °C) 40 50 Ambient temperature (°C) 0.2 Instantaneous trip 0.1 0.2(800-2000%) 0.02 1 0.02 0.01 Max. total breaking time Instantaneous trip (800-2000%) 0.1 0.01 10 50Ambient temperature ( 0 10 20 30 1.5 2 3 4 Max. total breaking time 5 6 7 8 10 15 20 30 40 50 100 Multiple for rated current (times) 1 1.5 2 3 4 5 6 7 8 10 Current 15 20 30 40 50 100 Multiple for rated current (times) Dimensions ※ : Center line Current : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting IEC 35mm DIN-rail M5×12 [Terminal part] 80 35 7 4.5 20.5 70 50 68 80 20.5 (Standard connection torque : 20-30 kgf.cm) 10.5 5 Line side 32 Load side 30 8 60 66 67.5 76 19 35 [Drilling holes for mounting] 35 [Panel cut-out] M4 or 5 (Standard connection torque : 15-20 kgf.cm) 70 52 R2 Molded Case Circuit Breaker_ 177 U-Series / Molded Case Circuit Breaker 180 120 15-50A 60 40 Minute | Miniature type / Molded case circuit breaker | 20 Tripping & temperature derating curves 10 6 4 180 120 2 Tripping time 15-50A 60 1 40 40 Max. Minute 20 6 10 4 0.6 0.4 0.2 0.1 •UMB30Hg 0.06 0.04 •UMB50Hg 2 1 1 40 Tripping time Second Min. Instantaneous trip (800-1200%) 20 Max. total breaking time 6 4 2 1.5 2 Min. Second 0.01 Max. 10 0.02 1 Derating rate for rated current (%) 6 4 2 1 3 4 5 6 7 8 910 15 20 30 40 50 0.6 Multiple for rated current (times) 0.4 0.2 70 300 250 200 160 120 100 80 60 40 100 0 20 0.1 Max. total breaking time 0.06 0.04 30 300 250 200 40 160 50 Ambient temperature (°C) Instantaneous trip (800-1200%) Current 10 Derating rate for rated current (%) 10 20 0.02 120 100 80 60 40 0.01 1 1.5 2 3 4 5 6 7 8 910 15 20 30 40 50 70 100 0 Multiple for rated current (times) Current Dimensions ※ : Center line 10 20 30 : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 7 4.5 10.5 5 Line side 32 Load side 30 8 60 19 66 35 67.5 76 [Drilling holes for mounting] [Panel cut-out] M4 or 5 35 (Standard connection torque : 15-20 kgf.cm) 70 52 R2 178 M5×12 (Standard connection torque : 20-30 kgf.cm) 80 68 50 35 [Terminal part] 6 18.5 70 47.5 IEC 35mm DIN-rail Trip button 40 50 Ambient temperature (°C) 240 180 150 120 100 80 60 40 240 180 20 150 120 100 10 808 606 40 3-30A 3-30A •UDB50H Min. 2 0.2 1 0.1 0.8 0.08 0.6 0.06 0.4 0.04 0.2 Min. 0.02 0.1 0.01 0.08 1.5 0.06 1 0.04 Min. 0.01 1 Minute Minute 4 20 2 10 8 1 6 40 4 20 2 10 1 8 40 6 4 20 2 10 8 1 6 0.8 4 0.6 0.4 2 0.2 1 0.8 0.1 0.6 0.08 0.4 0.06 0.04 0.2 0.02 0.1 0.08 0.01 0.06 1 0.04 Second Second Second Tripping time Tripping time Minute 3 Second Under voltage trip Tripping time Tripping time Shunt trip Minute Trip alarm switch 0.01 1 1.5 1.5 2 1.5 3 2 240 180 150 120 100 80 60 40 240 180 20 150 120 100 10 808 606 40 2 4 3 4 Instantaneous trip (800-1200%) Max. Instantaneous trip Max. total (800-1200%) breaking time Instantaneous trip Max. total (800-1200%) breaking time 5 6 7 8 9 10 15 20 30 40 50 60 Instantaneous trip Multiple for rated current (times) Max. total (800-1200%) breaking time Current 3 4 5 6 7 8 9 10 15 20 30 40 50 60 80 100 80 100 Multiple for rated current Max. total (times) breaking time Current 5 6 7 8 9 10 15 20 30 40 50 60 80 100 3 4 Current 5 6 7 8 9 10 15 20 30 40 50 60 40 40 120 100 80 60 40 0 10 20 30 40 50 Ambient temperature (°C) 0 10 20 30 40 50 Ambient temperature (°C) 0 10 20 30 40 50 Ambient temperature (°C) 0 10 20 30 40 50 Ambient temperature (°C) 40-100A Max. 40-100A Max. Max. Min. 2 0.2 1 0.1 0.8 0.08 0.6 0.06 0.4 0.04 0.2 Min. 0.02 0.1 0.01 0.08 1.5 0.06 1 0.04 Min. 2 1 2 1.5 3 2 4 Instantaneous trip (800-1200%) Max. Min. 0.02 1.5 120 40 100 80 60 40-100A 3 4 Instantaneous trip Max. total (800-1200%) breaking time Instantaneous trip (800-1200%) Max. total breaking time 5 6 7 8 9 10 15 20 30 40 50 60 Instantaneous trip Multiple for rated current (times) (800-1200%) Max. total Current breaking time 3 4 5 6 7 8 9 10 15 20 30 40 50 60 Multiple for rated current (times) Max. total breaking time Current 5 6 7 8 9 10 15 20 30 40 50 60 80 100 Multiple for rated current (times) 1 120 300 100 250 80 200 60 160 120 300 100 250 80 200 60 160 40-100A 4 1.5 300 250 200 160 300 250 200 160 Current 20 2 10 81 6 40 4 20 2 10 18 406 4 20 2 10 81 0.8 6 0.6 4 0.4 0.01 80 100 Multiple for rated current (times) 0.02 0.01 2 Max. Multiple for rated current (times) •UDB100H 240 180 150 120 100 80 60 40 240 180 150 20 120 100 10 80 8 60 6 40 Min. 0.02 0.02 •UDB100S No. of Auxiliary poles switch 3-30A Max. Derating rate for rated current (%)current (%) Derating rate for rated Minute Second 20 2 10 1 8 40 6 4 20 2 10 8 1 6 0.8 4 0.6 0.4 2 0.2 1 0.8 0.1 0.6 0.08 0.4 0.06 0.04 0.2 0.02 0.1 0.08 0.01 0.06 1 0.04 3-30A Max. 2 3 4 Current 5 6 7 8 9 10 15 20 30 40 50 60 80 100 Multiple for rated current (times) 80 100 80 100 300 250 200 160 120 300 100 250 80 200 60 160 120 40 100 80 60 40 Derating rate for rated current (%)current (%) Derating rate for rated •UDB50S 4 20 2 10 81 6 40 4 20 2 10 18 406 4 20 2 10 81 0.8 6 0.6 4 0.4 Derating rate for rated (%)current (%) Derating ratecurrent for rated •UDB30H 4 20 2 10 8 1 6 40 4 Second Minute Second Tripping time Tripping time Second •UDB30S 240 180 150 120 100 80 60 40 240 180 150 20 120 100 10 80 8 60 6 40 Tripping time Tripping time Minute Tripping & temperature derating curves Derating rate for rated (%)current (%) Derating ratecurrent for rated Minute MCCB 300 250 200 160 120 300 100 250 80 200 60 160 40 120 100 80 60 0 40 10 20 30 40 50 Ambient temperature (°C) 0 10 20 30 40 50 Ambient temperature (°C) 0 10 20 30 40 50 Ambient temperature (°C) 0 10 20 30 40 50 Ambient temperature (°C) Current Installation of signal accessories No. of poles Auxiliary switch Trip alarm switch Shunt trip 3 Left Right ※ - In case of 2P, all signal accessories shall be installed in left side of breaker. - SHT is not applicable to 2P. Handle [ Front ] Molded Case Circuit Breaker_ 179 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | Miniature type / Molded case circuit breaker | Dimensions ※ Direct mounting : Center line : Handle center line • The allowance of 1.5mm is given around the handle frame. UDB30, UDB50 IEC 35mm DIN-rail 13 1 3 Trip button 35 97.5 64 80 96 50 9 25 64 80 96 50 9 25 Mounting hole 19. 1 19. 1 Trip button 25 50 2P 50 75 50 53 60 65 80 3P M5×12 [Terminal part] 4.5 88 (Standard connection torque : 20-30 kgf.cm) Line side 32 Load side 30 17 [Drilling holes for mounting] 49 25 (Standard connection torque : 15-20 kgf.cm) (Standard connection torque : 15-20 kgf.cm) 3P 80-84 80-84 52 2P Direct mounting M4 or 5 R2 R2 52 [Panel cut-out] M4 or 5 74 2P 3P UDB100 Mounting hole IEC 35mm DIN-rail 19. 1 19. 1 Trip button 88 4.5 Line side 32 Load side 30 17 50 53 60 65 80 50 75 [Drilling holes for mounting] [Panel cut-out] M4 or 5 (Standard connection torque : 15-20 kgf.cm) 74 25 80-84 52 R2 180 M8×14 (Standard connection torque : 100-120 kgf.cm) 35 97.5 64 80 50 9 25 [Terminal part] (Unit: mm) MCCB Tripping & temperature derating curves 240 240 15-30A 120 15-30A 60 60 10 10 •UMG30Rb Max. 10 20 6 10 4 6 2 4 Second •UMG30Ra Max. 20 1 40 Derating rate for rated current (%) •UMG30Cb Tripping time •UMG30Ca 1 40 2 Second Tripping time 2 Min. 1 2 Derating rate for rated current (%) Minute Minute 120 100 100 50 Min. 1 150 150 50 0 0 10 20 30 40 50 Ambient temperature (°C) 10 20 30 40 50 Ambient temperature (°C) 0.2 0.1 Instantaneous trip (800-2000%) 0.2 0.1 0.02 0.02 0.01 0.01 1 Max. total breaking time Instantaneous trip (800-2000%) 1 1.5 1.5 2 2 3 3 4 Max. total breaking time 5 6 7 8 10 15 20 30 Multiple for rated current (times) 4 5 6 7 8 10 15 20 Current 30 40 50 40 50 70 70 100 100 Multiple for rated current (times) Dimensions ※ Current : Center line : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting UMG30Ca,Ra:45 UMG30Cb,Rb:63 33 [Terminal part] UMG30Ca,Ra:42 UMG30Cb,Rb:60 20 6.2 IEC35mm DIN-rail 10.2 5.2 Earth leakage test button 5.2 Load side UMG30Ra,Rb:56.5 UMG30Cb,Rb:76 [Drilling holes for mounting] 10.2 6.2 70 36 56 Line side UMG30Ca,Ra:7.5 UMG30Cb,Rb:25.5 [Panel cut-out] M4 or 5 59 38 (Standard connection torque : 15-20 kgf.cm) 35 Molded Case Circuit Breaker_ 181 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions | Miniature type / Earth leakage circuit breaker | Tripping & temperature derating curves 240 15-50A 120 240 60 15-50A 120 Minute 60 Derating rate for rated current (%) 10 2 1 Tripping time Max. 40 10 6 20 4 10 2 Min. 4 Max. 6 100 50 1 2 Second Second •UMG30Rd 1 20 Tripping time •UMG30Cd 2 40 150 Derating rate for rated current (%) Minute 10 150 100 0 Min. Instantaneous trip (800-2000%) 0.2 40 50 10 20 30 40 50 Max. total breaking time Instantaneous trip (800-2000%) 0.02 1 30 Ambient temperature (°C) 0.1 0.01 20 0 1 0.2 0.1 10 Ambient temperature (°C) 50 1.5 0.02 2 3 0.01 Multiple for rated current (times) 1 1.5 4 Max. total breaking time 2 5 6 7 8 10 3 4 15 20 5 6 7 8 10 Current 30 15 40 50 20 30 100 40 50 100 Multiple for rated current (times) Dimensions ※ : Center line Current : Handle center line • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 62 9 21 42 10 Line Earth leakage test button 5.2 Load 58 19.5 [Drilling holes for mounting] (Standard connection torque : 15-20 kgf.cm) 52 64 [Panel cut-out] M4 or 5 62 182 14 10 82 62 50 [Terminal part] 7.5 MCCB 180 120 15-50A 60 Minute 40 20 10 Tripping & temperature derating curves 6 4 180 120 2 Tripping time 1 40 40 Minute 6 4 10 1 2 0.6 0.4 1 40 0.1 0.06 0.04 20 10 4 1.5 2 3 Second •UMG50Sg 2 1 4 Max. Max. total breaking time 6 0.02 0.01 Instantaneous trip (800-1200%) Min. 5 6 718 910 15 20 30 40 50 70 300 250 200 160 120 100 80 60 40 100 0 Multiple for0.6rated current (times) Current 0.2 10 0.1 Max. total breaking time 0.06 0.04 0.02 0.01 1 1.5 2 3 4 5 6 7 8 910 15 20 30 40 50 70 20 30 : Center line : Handle center line 80 60 40 0 10 20 30 40 50 Ambient temperature (°C) Current ※ 120 100 100 Multiple for rated current (times) Dimensions 300 250 40200 50 160 ° Ambient temperature ( C) Instantaneous trip (800-1200%) 0.4 •UMG50Hg Derating rate for rated current (%) 6 4 Min. Tripping time Second 20 Derating rate for rated current (%) 10 0.2 •UMG30Hg Max. 20 2 •UMG30Sg 15-50A 60 • The allowance of 1.5mm is given around the handle frame. (Unit: mm) Direct mounting 20.5 35 50 68 80 50 68 80 70 47.5 6 18.5 20.5 70 80 IEC 35mm DIN-rail Earth leakage test button 10.5 10.5 5 Earth leakage test button Trip button 19 35 UMG30Sg / UMG50Sg 60 19 35 66 67.5 76 UMG30Hg / UMG50Hg [Drilling holes for mounting] [Panel cut-out] M4 or 5 35 (Standard connection torque : 15-20 kgf.cm) [Terminal part] 70 52 8 7 4.5 R2 Line 32 Load 30 Molded Case Circuit Breaker_ 183 U-Series / Molded Case Circuit Breaker Characteristic Curves & Dimensions 240 180 150 120 100 80 60 40 240 180 20 150 120 100 10 80 8 60 6 40 4 3-30A 3-30A •UDG50S Max. 20 2 10 1 8 0.8 6 0.6 4 0.4 2 0.2 1 0.1 0.8 0.08 0.6 0.06 0.4 0.04 Min. Max. Instantaneous trip (800-1200%) Min. Max. Instantaneous trip Max. total (800-1200%) breaking time Min. 10 1 8 0.8 6 0.6 4 0.4 0.2 0.02 0.1 0.01 0.08 1 0.06 0.04 2 0.2 1.5 2 Min. 1 0.1 0.8 0.08 0.6 0.06 0.4 0.04 0.02 0.01 1 1.5 2 0.2 0.02 0.1 0.01 0.08 1 0.06 0.04 •UDG50H 1.5 2 0.01 1.5 10 1 8 40 6 4 20 Minute Minute 20 2 Second 20 2 3 4 5 6 7 8 9 10 15 20 Multiple for rated current (times) Max. total 6 7 8 9 10 15 Current 20 30 40 50 60 80 100 breaking time 2 240 180 150 120 100 80 60 40 240 180 20 150 120 100 10 80 8 60 6 40 4 3 4 5 6 7 8 9 10 15 20 Max. Min. 10 1 8 0.8 6 0.6 4 0.4 2 0.2 1.5 2 3 4 5 6 Instantaneous trip (800-1200%) Max. total 7 8 9 10 15 20 breaking 30 40 50 time 60 80 1 1.5 2 3 4 5 3 4 5 6 7 8 9 10 15 20 Multiple for rated current (times) Max. total 6 7 8 9 10 15 Current 20 breaking 30 40 50 time 60 80 100 Current 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 80 100 Multiple for rated current (times) Current Installation of signal accessories No. of Auxiliary poles switch Trip alarm switch 3 Right Left [ Front ] 184 Handle 100 300 250 200 160 120 100 300 250 80 200 60 160 30 40 50 60 80 100 40 120 Multiple for rated current (times) 1.5 40 50 0 10 20 30 40 50 Ambient temperature (°C) 0 10 20 30 40 50 Ambient temperature (°C) 0 Instantaneous trip Max. total (800-1200%) breaking time Instantaneous trip Multiple for rated current (times) Max. total (800-1200%) breaking time Current 0.2 0.02 1 30 10 20 30 40 50 Ambient temperature (°C) 40-100A Instantaneous trip (800-1200%) Max. Min. 1 0.1 0.8 0.08 0.6 0.06 0.4 0.04 0.02 20 40-100A 20 2 2 10 Ambient temperature (°C) Max. 0.02 1.5 0 40 Max. 10 1 8 40 6 4 20 Min. 0.1 0.01 0.08 1 0.06 0.04 100 80 60 40-100A 20 2 0.01 40 120 100 300 250 80 200 60 160 40 120 40-100A 0.1 0.01 0.08 1 0.06 0.04 1 0.1 0.8 0.08 0.6 0.06 0.4 0.04 80 100 100 80 60 300 250 200 160 Current 0.2 0.02 2 0.2 30 40 50 60 Multiple for rated current (times) Min. 10 1 8 0.8 6 0.6 4 0.4 0.01 120 100 300 250 80 200 60 160 30 40 50 60 80 100 40 120 Multiple for Instantaneous rated current (times) trip Max. total (800-1200%) Current breaking time 2 10 8 1 6 40 4 Second Tripping time Tripping time Minute Minute 240 180 150 120 100 80 60 40 240 180 20 150 120 100 10 80 8 60 6 40 4 2 10 8 1 6 40 4 Second Tripping time Tripping time 5 5 6 Current 1 •UDG100H Second 4 4 Multiple for rated current (times) 0.02 •UDG100S 3 3 300 Instantaneous trip 250 (800-1200%) 200 Max. total 160 7 8 9 10 15 20 30 40 50 60 80 100 breaking time Derating rateDerating for ratedrate current for rated (%) current (%) Minute Second 20 2 3-30A ※ In case of 2P, all signal accessories shall be installed in left side of breaker. 100 80 60 40 Derating rateDerating for ratedrate current for rated (%) current (%) 10 1 8 40 6 4 20 Max. 10 1 8 40 6 4 20 2 10 8 1 6 40 4 Second 20 2 3-30A 20 2 Derating rateDerating for ratedrate current for rated (%) current (%) •UDG30H Tripping time Tripping time Minute Second •UDG30S 240 180 150 120 100 80 60 40 240 180 20 150 120 100 10 80 8 60 6 40 4 2 10 8 1 6 40 4 Second Tripping time Tripping time Minute Tripping & temperature derating curves Derating rateDerating for ratedrate current for rated (%) current (%) Minute | Miniature type / Earth leakage circuit breaker | 300 250 200 160 120 100 300 250 80 200 60 160 40 120 100 80 60 0 40 10 20 30 40 50 Ambient temperature (°C) 0 10 20 30 40 50 Ambient temperature (°C) 0 10 20 30 40 50 Ambient temperature (°C) 0 10 20 30 40 50 Ambient temperature (°C) MCCB Dimensions : Center line ※ Direct mounting : Handle center line • The allowance of 1.5mm is given around the handle frame. Earth leakage indicator Mounting hole Earth leakage indicator 64 80 96 64 80 96 50 75 torque : 20-30 kgf.cm) 3P M5×12 (Standard connection Line side 32 torque : 20-30 kgf.cm) Load side 30 [Panel cut-out] 8 8 [Drilling holes for mounting] 52 52 Earth leakage indicator UGD100 3P 64 80 96 50 9 25 Trip button 19.1 64 80 96 50 19.1 75 Earth leakage test button 19.1 Earth leakage test button 50 75 [Drilling holes for mounting] 74 [Drilling holes for mounting] R2 IEC 35mm DIN-rail 4.5 50 53 60 65 80 50 53 60 65 80 R2 [Terminal part] M8×14 [Terminal part] M8×14 (Standard connection torque : 15-20 kgf.cm) M4 or 5 (Standard connection side 32 torqueLine : 100-120 kgf.cm) Line side 32 Load side 30 17 M4 or 5 (Standard connection torque : 100-120 kgf.cm) Load side 30 17 4.5 (Standard connection torque : 15-20 kgf.cm) 74 52 Trip button 52 50 9 25 19.1 3P DIN-rail Earth leakage indicator Mounting hole 3P 2P IEC 35mm 35 97.5 2P 2P 35 97.5 Mounting hole 3P 25 80-84 (Standard connection torque : 15-20 kgf.cm) 80-84 M4 or 5 (Standard connection torque : 15-20 kgf.cm) R2 2P 25 [Panel cut-out] M4 or 5 52 52 R2 (Standard connection torque : 15-20 kgf.cm) R2 74 49 M4 or 5 (Standard connection torque : 15-20 kgf.cm) 80-84 [Drilling R2 holes for mounting] M4 or 5 80-84 49 Line side 32 74 side 30 Load 17 4.5 [Panel cut-out] 25 [Panel cut-out] 25 80-84 [Terminal part] Earth leakage test button 3P 80-84 17 Earth leakage test button M5×12 Trip button (Standard connection 50 53 60 65 80 50 53 60 65 80 19.1 19.1 8 8 2P 8 8 [Terminal part] 25 50 50 75 4.5 Earth leakage test button 8 8 2P Earth leakage test button Trip button 50 9 25 25 13 50 13 Trip button IEC 35mm DIN-rail 19.1 19.1 64 80 96 50 9 25 Trip button IEC 35mm DIN-rail 35 97.5 Earth leakage indicator 35 97.5 Mounting hole 50 9 25 Earth leakage indicator 64 80 96 50 9 25 UGD30, UGD50 13 13 Direct mounting (Unit: mm) Molded Case Circuit Breaker_ 185 Accessories | Signal Accessories | Operating Accessories | Mounting Accessories | | Terminal Accessories | Portable Test Equipment | + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + U-Series / Molded Case Circuit Breaker < Accessories for UAB100 > | Signal accessories | •auxiliary switch •trip alarm switch •shunt trip •under voltage trip | Operating accessories | •operating handle (surface and extended type) •motor operator •mechanical interlock •padlock plate •extension handle | Mounting accessories | •DIN-rail adaptor •mounting base for plug-in mounting Auxiliary switch [ AUX ] | Terminal accessories | •terminal bus bar •cage terminal block •terminal cover •interpole barrier Trip alarm switch [ ALT ] | Portable test equipment | •MCCB trip unit tester Surface type operating handle [ TFG ] Extended type operating handle [ TFH ] Motor operator [ MOT ] ※The applicable accessories of each MCCB are not same as above. For exact application to each MCCB, please reter to next pages. 188 MCCB Cage terminal block [ CTB ] Terminal cover [ TCF ] Interpole barrier [ TQQ ] DIN-rail adaptor [ DRA ] Plug-in mounting base [ TDM ] Shunt trip [ SHT ] Under voltage trip [ UVT ] Cage terminal block [ CTB ] Terminal cover [ TCF ] Interpole barrier [ TQQ ] Molded Case Circuit Breaker_ 189 U-Series / Molded Case Circuit Breaker Signal Accessories •Signal accessories adopts cassette type assembly method, so they can be easily installed and removed. Auxiliary AUX - Electrically indicates ON and OFF status of breaker Shunt trip SHT - Electrically trips breaker at remote place 190 Trip alarm switch ALT - Electrically indicates TRIP status of breaker Under voltage trip UVT - Automatically trips breaker when control voltage drops below predetermined value MCCB | Installation and wiring of signal accessories | Item Installation 3 pole Wiring 2 pole 1EA of 1ab type AUX 2EA of 1ab type AUX Auxiliary switch [AUX] 3EA of 1ab type AUX 4EA of 1ab type AUX Trip alarm switch [ALT] Limit switch for coil protecton 1) Shunt trip [SHT] for SHT 10A H, SHT 10B H, SHT 20C H 2) Under voltage trip [UVT] ※ - For detail installation to each MCCB model, please refer to “Characteristic curves & Dimensions” from page 136 to 185. 1) Common for AC200-480V. Applicable for SHT 10A H, SHT 10B H and SHT 20C H only. 2) The coil is continuously energized, so that limit switch is not required. | Operation of AUX and ALT | MCCB Status Auxiliary switch [AUX] Trip alarm switch [ALT] ON OFF TRIP Molded Case Circuit Breaker_ 191 U-Series / Molded Case Circuit Breaker Signal Accessories | Auxiliary switch (AUX) and trip alarm switch (ALT) | Applicable MCCB UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R UCB50R, UCB100R, UCB100S / UCD100S UCB250R, UCB250S, UCB250N / UCD250S UCB50H, UCB50L, UCB100H, UCB100L, UCB160H, UCB160L, UCB250H, UCB250L / UCD50H, UCD100H, UCD160H, UCD250H UCB400R, UCB400S, UCB400H, UCB400L, UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD400S, UCD630S, UCD800S UCB1000S, UCB1000L, UCB1250S, UCB1250L / UCD1000S, UCD1250S UCB1600S UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ1) UDB30S, UDB30H, UDB50S, UDB50H, UDB100S, UDB100H / UDG30S, UDG30H, UDG50S, UDG50H, UDG100S, UDG100H Auxiliary switch (AUX) Trip alarm switch (ALT) Order code AUX 10A R1 AUX 10A R2 AUX 10UA R1 AUX 10UA L1 AUX 10B L1 AUX 20C L1 Specification Order code 1C, right-hand-side ALT 10A R1 2C, right-hand-side 1C, right-hand-side ALT 10UA R1 1C, left-hand-side ALT 10UA L1 1C, left-hand-side ALT 10B L1 1C, left-hand-side ALT 20C L1 Specification AUX 12FG L1 1C, left-hand-side ALT 12FG R1 1C, right-hand-side AUX 12FG L2 2C, left-hand-side ALT 12FG L1 1C, left-hand-side AUX 46D R1 1C, right-hand-side ALT 46D L1 1C, left-hand-side AUX 80NE R1 AUX 80NE R2 AUX 80NE R3 AUX 160NE R1 AUX 160NE R2 1C, right-hand-side 2C, right-hand-side ALT 80NE R1 3C, right-hand-side 1C, right-hand-side 2C, right-hand-side AUX 12UP R1 1C, right-hand-side ALT 12UP L1 1C, left-hand-side AUX 46UP L1 1C, left-hand-side ALT 46UP R1 1C, right-hand-side AUX 12UP R1 1C, right-hand-side ALT 12UP L1 1C, left-hand-side 1C, right-hand-side 1C, right-hand-side 1C, left-hand-side 1C, left-hand-side 1C, left-hand-side 1C, right-hand-side MCCB MB - ALT 10UD 2L1 ALT 10UD 2L1T 2) 1C, left-hand-side ALT 10UD 3L1 AUX 10UD L1T2) ALT 10UD 3L1T 2) AUX 10UD L1 Category 1C, left-hand-side for 2 pole 1C, left-hand-side for 3 pole ※ 1) Signal accessories for HBL type shall be installed in breaker before ex-working. 2) Terminal block type | Shunt trip (SHT) | Applicable MCCB UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R UCB50R, UCB100R, UCB100S / UCD100S UCB250R, UCB250S, UCB250N / UCD250S UCB50H, UCB50L, UCB100H, UCB100L, UCB160H, UCB160L, UCB250H, UCB250L / UCD50H, UCD100H, UCD160H, UCD250H UCB400R, UCB400S, UCB400H, UCB400L, UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD400S, UCD630S, UCD800S UCB1000S, UCB1000L, UCB1250S, UCB1250L / UCD1000S, UCD1250S UCB1600S UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ2) UDB30S, UDB30H, UDB50S, UDB50H, UDB100S, UDB100H 192 Order code / Exciting current (peak value) DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V DC24V SHT 10A A SHT 10A C SHT 10A F SHT 10A H 5.2A 1.1A 0.76A 0.28A SHT 10UA A SHT 10UA F SHT 10UA H SHT 10UA B SHT 10UA D 5.7A 0.88A 0.42A 0.42A 0.42A SHT 10B A SHT 10B F SHT 10B H 5.2A 0.76A 0.4A SHT 20C A SHT 20C F SHT 20C H 5.2A 0.76A 0.4A SHT 12FG A SHT 12FG C SHT 12FG F SHT 12FG H SHT 12FG B SHT 12FG D 5.2A 2.2A 0.76A 0.4A 0.4A 0.4A SHT 46D A SHT 46D C SHT 46D F SHT 46D H SHT 46D B SHT 46D D 0.01A 0.01A 0.012A 0.011A 0.01A 0.01A SHT 120NE A SHT 120NE C SHT 120NE F SHT 120NE H SHT 120NE B SHT 120NE D 2A 0.11A 0.24A 0.23A 0.23A 0.23A SHT 160NE A SHT 160NE C SHT 160NE F SHT 160NE H SHT 160NE B1) 2A 1A 0.76A 0.4A 0.35A SHT 12UP A SHT 12UP C SHT 12UP F SHT 12UP H SHT 12UP B SHT 12UP D 0.023A 0.023A 0.023A 0.023A 0.023A 0.023A SHT 46UP A 0.023A SHT 12UP A 0.023A SHT 10UD A SHT 10UD AT3) 1.65A SHT 46UP C 0.023A SHT 12UP C 0.023A SHT 10UD C SHT 10UD CT3) 0.36A SHT 46UP F 0.023A SHT 12UP F 0.023A SHT 10UD F SHT 10UD FT3) 0.4A SHT 46UP H 0.023A SHT 12UP H 0.023A SHT 10UD H SHT 10UD HT3) 0.2A SHT 46UP B 0.023A SHT 12UP B 0.023A SHT 10UD B SHT 10UD BT3) 0.08A SHT 46UP D 0.023A SHT 12UP D 0.023A SHT 10UD D SHT 10UD DT3) 0.1A ※ - The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC. 1) SHT 160NE B is applicable for AC380V only. 2) Signal accessories for HBL type shall be installed in breaker before ex-working. 3) Terminal block type Category MCCB MB MCCB | Under voltage trip (UVT) | Order code Applicable MCCB DC24V UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R UCB50R, UCB100R, UCB100S / UCD100S UCB250R, UCB250S, UCB250N / UCD250S UCB50H, UCB50L, UCB100H, UCB100L, UCB160H, UCB160L, UCB250H, UCB250L / UCD50H, UCD100H, UCD160H, UCD250H UCB400R, UCB400S, UCB400H, UCB400L, UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD400S, UCD630S, UCD800S UCB1000S, UCB1000L, UCB1250S, UCB1250L / UCD1000S, UCD1250S UCB1600S UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ2) ✽UVT 10A J DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V ✽ UVT 10A L ✽ UVT 10A N ✽ UVT 10A P ✽UVT 10A Q ✽UVT 10A R UVT 10UA J UVT 10UA L UVT 10UA N UVT 10UA P UVT 10UA Q UVT 10UA R UVT 10B J UVT 20C J UVT 10B L UVT 20C L UVT 10B N UVT 20C N UVT 10B P UVT 20C P UVT 10B Q UVT 20C Q UVT 10B R UVT 20C R UVT 12FG J UVT 12FG L UVT 12FG N UVT 12FG P UVT 12FG Q UVT 12FG R ✽ UVT 46D J ✽UVT 46D L ✽ UVT 46D N ✽UVT 46D P Category ✽UVT 46D Q ✽UVT 46D R MCCB MB UVT 120NE J UVT 120NE L UVT 120NE N UVT 120NE P UVT 120NE Q UVT 120NE R - - - UVT 160NE P UVT 160NE Q1) UVT 160NE R1) ✽ UVT 12UP J ✽ UVT 12UP L ✽ UVT 12UP N ✽ UVT 12UP P ✽UVT 12UP Q ✽UVT 12UP R ✽ UVT 46UP J ✽ UVT 46UP L ✽ UVT 46UP N ✽ UVT 46UP P ✽UVT 46UP Q ✽UVT 46UP R ✽ UVT 12UP J ✽ UVT 12UP L ✽ UVT 12UP N ✽ UVT 12UP P ✽UVT 12UP Q ✽UVT 12UP R ※ - The permissible operating voltage: 85-110% of rated voltage for AC, 85~125% for DC. The tripping voltage: 20-70% of rated voltage. - Be sure not to use UVT for the electrical interlock system. ✽ Reset is possible without power. 1) UVT 160NE Q is applicable for AC380V only, and UVT 160NE R is applicable for AC440V only. 2) Signal accessories for HBL type shall be installed in breaker before ex-working. •UVT controller is supplied as standard for UVT 10A, UVT 10UA, UVT 10B, UVT 20C, UVT 12FG, UVT 46D J, UVT 12UP and UVT 46UP type. Fixing hole (R/H M4 X L11 + P/W + S/W) U2 88 100 8 16 15 18 15 16 16 ON MCCB U1 UC2 (-) 16.5 Mounting hole( 4.5) (R/H M4 X L9 + P/W + S/W) 22 UC1 (+) OFF Terminal screw M3.5 4 63 56 45 UVT controller Supportor [ Wiring ] [ Dimensions ] ※ Terminal U1 an U2 are connected by the cable of vw-1, 22AWG (0.324㎟×700㎜). Different cables are available on request. ※ Internal accessories do not support plug-in connection when installed seperately. Please contact us before order. Molded Case Circuit Breaker_ 193 U-Series / Molded Case Circuit Breaker Operating Accessories • Operating accessories offers convenience and safety in operation of breaker. Operating handle TFG, TFH - Enables manual operation of breaker without panel door-open - Offers panel door-lock and reverse interlock function - Satisfies IP54 Surface type / TFG Extended type / TFH - Useful in case that panel door is far from breaker - Mechanism part is installed on front of breaker and connected with operating part by shaft Motor operator MOT - Enables automatic remote ON and OFF operation as well as manual operation - Applied to electric supervision and control system - Equips an emergency trip button in all range Padlock plate MIF - Mechanically prevents simultaneous closing of two breakers PLD - Locks the breaker in OFF position 194 Mechanical interlock Extension handle THA - Reduces strength in operation of breaker A MCCB | Operating handle (TFG/TFH) | Surface type (TFG) Extended type (TFH) S type L type Right1) Left1) Upper1) Left1) Upper1) power supply power supply power supply power supply power supply type type type type type Applicable MCCB UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R UCB50R, UCB100R, UCB100S / UCD100S UCB250R, UCB250S, UCB250N / UCD250S UCB50H, UCB50L, UCB100H, UCB100L / UCD50H, UCD100H UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H UCB400R, UCB400S, UCB400H, UCB400L, UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD400S, UCD630S, UCD800S UCB1600S UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ S type L type TFG 10AL L4 TFH 10AS TFH 10AL TFG 10UAS U4 TFG 10UAS R4 TFG 10UAS L4 TFG 10UAL U4 TFG 10UAL L4 TFH 10UAS TFH 10UAL TFG 10BS U4 TFG 10BS R4 TFG 10BS L4 TFG 10BL U4 TFG 10BL L4 TFG 20CS U4 TFG 20CS R4 TFG 20CS L4 TFG 20CL U4 TFG 20CL L4 TFH 10BS TFH 20CS TFH 10BL TFH 20CL TFG 10UFS U4 TFG 10UFS R4 TFG 10UFS L4 TFG 10UFL U4 TFG 10UFL L4 TFH 10UFS TFH 10UFL TFG 20UGS U4 TFG 20UGS R4 TFG 20UGS L4 TFG 20UGL U4 TFG 20UGL L4 TFH 20UGL TFG 10AS U4 TFG 10AS R4 TFG 10AS L4 TFG 10AL U4 TFH 20UGS TFG 46DS U4 TFG 46DS R4 TFG 46DS L4 TFH 46DS TFH 160NE TFG 12UPS U4 TFG 12UPS R4 TFG 12UPS L4 TFG 12UPL U4 TFG 12UPL L4 TFH 12UPS TFH 12UPL TFG 46UPS U4 TFG 46UPS R4 TFG 46UPS L4 TFH 46UPS - - - - - - - - TFG 20U U4 TFG 20U L4 TFG 20UQ U4 TFG 20UQ L4 ※ - In case of surface type (TFG), there are three types for diverse panel door-lock application, above mentioned codes are standard type. For detail, please refer to following explanation. 1) Upper, right and left indicates the power supply direction of MCCB. Power supply direction of MCCB •Surface type (TFG) operating handles are divided into three types by power supply direction of MCCB. [Upper power supply type] MCCB MCCB MCCB MCCB [Right power supply type] Power (Line side) Power (Line side) Power (Line side) MCCB Power (Line side) Power (Line side) MCCB Power (Line side) Power (Line side) Power (Line side) Power (Line side) MCCB MCCB MCCB [Left power supply type] ※ ON, OFF and TRIP are not marked on real products. Panel door-lock •Surface type (TFG) operating handles offer four options in panel door-lock application. - OFF OPEN type: Panel door opens when operating handle is in OFF position. Indicating code (last digit of full order code) is 1. ex. TFG 10AS U1 - OFF OPEN type with reverse interlock: Panel door opens when operating handle is in OFF position. Reverse interlock keeps MCCB not to be "ON" when panel door opens. This is standard type for 400-800AF MCCB and indicating code (last digit of full order code) is 2. ex.TFG 46DS U2 - RESET OPEN type: Panel door opens when operating handle is in RESET position. Indicating code (last digit of full order code) is 3. ex.TFG 10AS U3 - RESET OPEN type with reverse interlock: Panel door opens when operating handle is in RESET position. Reverse interlock keeps MCCB not to be “ON” when panel door opens. This is standard type for 30-250AF MCCB and indicating code (last digit of full order code) is 4. ex. TFG 46DS U4 •When panel door is required to open in ON position of operating handle, please turn the RELEASE knob to indicated direction and open the panel door. •For more operating function, please refer to following pages. Molded Case Circuit Breaker_ 195 U-Series / Molded Case Circuit Breaker Operating Accessories Operation •Operating direction - Turn the handle in a clockwise direction for ON. •Operation in panel door-closed - MCCB ON: Turn the handle to ON position. (Fig. 1) - MCCB OFF: Turn the handle to OFF position. (Fig. 2) - MCCB TRIP: When MCCB trips, handle turns to TRIP position automatically. -A fter MCCB trips, turn the handle to RESET position first and turn to ON position for ※O N, OFF and TRIP are not marked on real products. MCCB ON. (Fig. 3 and Fig. 1) -W hen panel door is required to open in ON position of operating handle, please turn the RELEASE knob to indicated direction and open the panel door. (Fig. 4) •Lock and release of panel door - When MCCB is in ON, OFF and TRIP status, both operating handle and panel door are locked. - When MCCB is in OFF and TRIP status, panel door can be opened by turning the handle to RESET position. (Fig. 3) -P anel door shall be locked automatically when you close the door in MCCB ON status. Please turn the handle to ON position before closing the door. •Lock of operating handle - If required, you can lock operating handle in ON or OFF position with padlock ( 6-8 for S type, 4-6 for L type). Padlock is not supplied. (Fig. 5) - When MCCB trips, handle turns to TRIP position automatically. •Handle position shall be same with MCCB position (ON, OFF, TRIP) before closing the panel door. Fig.1 Fig.2 Fig.3 Fig.4 Fig.5 [ S type ] Fig.1 Fig.2 Fig.3 Fig.4 [ L type ] ※ ON, OFF and TRIP are not marked on real products. 196 Trip button Fig.5 MCCB Dimensions and standard order code / Surface type (TFG) •30-250AF S type [ Upper power supply type ] Panel door Line side 59 A 37 44 Handle center line 59 MCCB center line B C Handle center line MCCB center line Panel door 37 A 44 [ Right power supply type ] 8 59 Line side A 59 8 B C [ Left power supply type ] Handle center line MCCB center line 4 Panel door Line side 59 37 4- A 59 A 8 Order code Applicable MCCB UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R UCB50R, UCB100R, UCB100S / UCD100S UCB250R, UCB250S, UCB250N / UCD250S UCB50H, UCB50L, UCB100H, UCB100L / UCD50H, UCD100H UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S Upper power supply type Right power supply type B C Dimensions (mm) Left power supply type A B C TFG 10AS U4 TFG 10AS R4 TFG 10AS L4 7 43 56 TFG 10UAS U4 TFG 10UAS R4 TFG 10UAS L4 0 43 56 TFG 10BS U4 TFG 20CS U4 TFG 10BS R4 TFG 20CS R4 TFG 10BS L4 TFG 20CS L4 9 10.25 47 47 54 54 TFG 10UFS U4 TFG 10UFS R4 TFG 10UFS L4 9 47 55 TFG 20UGS U4 TFG 20UGS R4 TFG 20UGS L4 10.25 47 55 TFG 12UPS U4 TFG 12UPS R4 TFG 12UPS L4 16.25 41 86.5 Category MCCB MB Molded Case Circuit Breaker_ 197 U-Series / Molded Case Circuit Breaker Operating Accessories •30-250AF L type [ Upper power supply type ] Panel door B 1.2-3.2 4- 8 Panelline door Handle center B 1.2-3.2 4- 8 A A 88 100 A 88 100 A Handle center line MCCB center line 88 100 4-M4 bolt hole 88 100 MCCB center line 4-M4 bolt hole [ Left power supply type ] Handle center line MCCB center line Handle center line 4- 8 A Handle center line MCCB center line Handle center line 4- 8 A A B Panel door 1.2-3.2 B MCCB center line 1.2-3.2 88 100 88 100 A Panel door MCCB center line 88 100 88 100 ※ ON, OFF and TRIP are not marked on real products. Dimensions (mm) Order code Applicable MCCB UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R UCB50R, UCB100R, UCB100S / UCD100S UCB250R, UCB250S, UCB250N / UCD250S UCB50H, UCB50L, UCB100H, UCB100L / UCD50H, UCD100H UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S 198 Upper power supply type Left power supply type A B TFG 10AL U4 TFG 10AL L4 5 106-111 TFG 10UAL U4 TFG 10UAL L4 5 106-111 TFG 10BL U4 TFG 20CL U4 TFG 10BL L4 TFG 20CL L4 9 9 111-116 111-116 TFG 10UFL U4 TFG 10UFL L4 9 111-116 TFG 20UGL U4 TFG 20UGL L4 9 111-116 TFG 12UPL U4 TFG 12UPL L4 14.25 136-140 Category MCCB MB MCCB •400-630AF S type Handle center line Panel door 55 Line side MCCB center line 100 [ Right power supply type ] 100 A 10 5 100 4- 5 [ Upper power supply type ] 5-10 Handle center line Panel door 55 5 A 4- A 100 10 5 Line side 100 B 100 MCCB center line [ Left power supply type ] 5-10 Handle center line 55 Panel door 5 A Line side 4- 100 10 5 100 A B 100 MCCB center line 5-10 B ※ ON, OFF and TRIP are not marked on real products. Dimensions (mm) Order code Applicable MCCB Upper power supply type Right power supply type Left power supply type A B TFG 46DS R4 TFG 46DS L4 0 222 Category UCB400R, UCB400S, UCB400H, UCB400L, UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L TFG 46DS U4 / UCD400S, UCD630S, UCD800S MCCB MB UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X TFG 46UPS U4 TFG 46UPS R4 TFG 46UPS L4 14.75 234 / UPD400S, UPD630S Molded Case Circuit Breaker_ 199 U-Series / Molded Case Circuit Breaker Operating Accessories Dimensions and standard order code / Extended type (TFH) A 5 Panel door 227 59 D 37 4- 4 •30-250AF S type 59 15 15 247 Applicable MCCB Order code 38 B C Dimensions (mm) A B C D TFH 10AS 381-386 43 56 7 UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R TFH 10UAS 381-386 43 56 0 UCB50R, UCB100R, UCB100S / UCD100S TFH 10BS 383-388 47 54 9 UCB250R, UCB250S, UCB250N / UCD250S TFH 20CS 383-388 47 54 10.25 UCB50H, UCB50L, UCB100H, UCB100L / UCD50H, UCD100H TFH 10UFS 383-388 47 55 9 UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H TFH 20UGS 383-388 47 55 10.25 TFH 12UPS 414-419 41.5 86.5 16.25 UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S 200 Category MCCB MB Panel door Handle center line 77 B 1.2-3.2 50 C MCCB 19 77 80 0 R1 A 80 Handle center line D 4-M4 bolt hole MCCB center line •30-250AF L type [ Upper power supply ] B Panel door Handle center line 50 19 A 77 80 0 R1 77 C 1.2-3.2 80 MCCB center line D 4-M4 bolt hole [ Left power supply ] Panel door B 1.2-3.2 Handle center line 77 50 77 80 0 R1 A C 19 80 Handle center line D 4-M4 bolt hole MCCB center line ※ ON, OFF and TRIP are not marked on real products. Applicable MCCB Order code Dimensions (mm) B PanelAdoor B 210-360 1.2-3.2 C C 160 D 106 160 106 UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C TFH 10AL 5 UAB50S, UAB50H, UAB100R, 77 UAB100S / UAD50S, UAD100R TFH 10UAL UCB50R, UCB100R, UCB100S / UCD100S TFH 10BL 550 9 210-360 164 110 UCB250R, UCB250S, UCB250N / UCD250S TFH 20CL 9 210-360 164 110 UCB50H, UCB50L, UCB100H, UCB100L / UCD50H, UCD100H TFH 10UFL 9 210-360 164 110 UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H TFH 20UGL 9 210-360 164 110 UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, 80 UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S TFH 12UPL 14.25 210-360 186 135 Handle center line 77 80 0 R1 A 210-360 19 Category MCCB MB MCCB center line •400-630AF S type 4- 5 55 5-10 Panel door 250 125 A 10 5 100 D 4-M4 bolt hole 100 B Applicable MCCB Order code UCB400R, UCB400S, UCB400H, UCB400L, UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD400S, UCD630S, UCD800S TFH 46DS UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S TFH 46UPS Dimensions (mm) A B 0 428-433 14.75 440-445 Category MCCB MB Molded Case Circuit Breaker_ 201 U-Series / Molded Case Circuit Breaker Operating Accessories Dimensions and standard order code / Q-class (for nuclear power plant application) •Surface type (TFG) Panel door 35 Line 4- 8 88 Panelcenter door line Handle 1.2-3.2 Max. 140 - Min. 136 1.2-3.2 A Handle center line 14.5 A 58.5 58.5 35 Line 87.5 88 100 14.5 88 100 14.5 4- 8 Max. 140 - Min. 136 14.5 [ Upper power supply type ] MCCB center line 87.5 100 88 MCCB center5.5 line 4-M4 bolt hole 100 B C D 5.5 4-M4 bolt hole B C D [ Left power supply type ] Panel door Handle center line MCCB center line Handle center line 4- 8 A Handle center line 1.2-3.2 Max. 140 - Min. 136 Panel door MCCB center line Handle center line MCCB center line 1.2-3.2 4- 8 88 100 35 Line 88 100 35 Line A Max. 140 - Min. 136 MCCB center line 88 58.5 87.5 100 73 73 14.5 87.5 88 58.5 100 73 5.5 B C D 5.5 73 B C D 14.5 ※ ON, OFF and TRIP are not marked on real products. Dimensions (mm) Order code Applicable MCCB 202 Upper power supply type Left power supply type A B C D HBL103U, HBL103UM, HBL203U, HBL203UM TFG 20U U4 TFG 20U L4 14.25 51.5 78 129.5 HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ TFG 20UQ U4 TFG 20UQ L4 14.25 51.5 78 129.5 Category MCCB MB U-Series / Molded Case Circuit Breaker Operating Accessories | Motor operator (MOT) | MOT-12NE Applicable MCCB Model UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R UCB50R, UCB100R, UCB100S / UCD100S UCB50H, UCB50L, UCB100H, UCB100L / UCD50H, UCD100H UCB250R, UCB250S, UCB250N / UCD250S UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H UCB400R, UCB400S, UCB400H, UCB400L / UCD400S UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD630S, UCD800S UCB1000S, UCB1000L, UCB1250S, UCB1250L / UCD1000S, UCD1250S UCB1600S UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ MOT-10A Control voltage (V) Operational Operation time (ms) Power Mechanical consumption life (times) current (A) Closing Opening (W) DC24V AC/DC110V AC/DC220V ≤ 2.5 ≤ 0.5 ≤ 0.5 DC24V AC/DC110V AC/DC220V DC24V AC/DC110V AC/DC220V ≤ 2.5 ≤ 0.5 ≤ 0.5 ≤ 5.0 ≤ 3.0 ≤ 2.0 MOT-40D DC24V AC/DC110V AC/DC220V MOT-68E Dimensions (mm) A B C D 310 200 14 25,000 90 132 93 30 310 200 14 10,000 90 132 93 30 350 230 14 8,000 90 126 93 35 ≤ 5.0 ≤ 3.0 ≤ 2.0 350 230 14 5,000 130 215 150 44 DC24V AC/DC110V AC/DC220V ≤ 5.0 ≤ 3.0 ≤ 2.0 500 350 35 5,000 130 243 137 70 MOT-80NE DC24V AC/DC110V AC/DC220V ≤ 5.0 ≤ 3.0 ≤ 2.0 820 500 120 3,000 130 340 150 70 MOT-160NE AC 220V ≤ 2.0 820 500 120 3,000 MOT-12UP DC24V AC/DC110V AC/DC220V ≤ 5.0 ≤ 3.0 ≤ 2.0 700 420 35 10,000 130 130 150 45 DC24V AC/DC110V AC/DC220V DC24V AC/DC110V AC/DC220V ≤ 5.0 ≤ 3.0 ≤ 2.0 ≤ 5.0 ≤ 3.0 ≤ 2.0 700 420 35 5,000 130 130 150 45 700 420 35 10,000 130 130 150 45 MOT-10UA MOT-10UB MOT-10F MOT-20UC MOT-20G MOT-46NE MOT-12UP MCCB MCCB AA DD MOT-68E MCCB MCCB - - - - MCCB MCCB CC Motor Motor operator operator 150 150 142 142 32 32 B B 376 376 147 147 Handle Handle 97 97 Motor Motor operator operator Motor Motor operator operator [MOT-10/20/40/68/80/12/46] 204 210 210 122 122 [MOT-160NE] Motor Motor operator operator MCCB ■ Control circuit and wiring diagram S3 1 Control power 2 Power K4 K5 3 K4 P1 S1 P2 S2 S4 POWER K4 Ue K3 ON OFF K5 ON 4 K1 K1 ON circuit S1 S2 K3 M : Motor K3 K3 K1 : ON relay K4 K2 : OFF relay K5 K2 OFF OFF circuit 5 K5 Motor control relay S1 : ON limit switch S2 : OFF limit switch S3 : Auto/Manual K2 ■ Standard order code Applicable MCCB Order code DC24V AC/DC110V AC/DC220V UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C MOT 10A DC24 MOT 10A ADC110 MOT 10A ADC220 UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R MOT 10UA DC24 MOT 10UA ADC110 MOT 10UA ADC220 UCB50R, UCB100R, UCB100S / UCD100S MOT 10UB DC24 MOT 10UB ADC110 MOT 10UB ADC220 UCB50H, UCB50L, UCB100H, UCB100L / UCD50H, UCD100H MOT 10F DC24 MOT 10F ADC110 MOT 10F ADC220 UCB250R, UCB250S, UCB250N / UCD250S MOT 20UC DC24 MOT 20UC ADC110 MOT 20UC ADC220 UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H MOT 20G DC24 MOT 20G ADC110 MOT 20G ADC220 UCB400R, UCB400S, UCB400H, UCB400L / UCD400S MOT 40D DC24 MOT 40D ADC110 MOT 40D ADC220 MOT 68E DC24 MOT 68E ADC110 MOT 68E ADC220 MOT 80NE DC24 MOT 80NE ADC110 MOT 80NE ADC220 - - MOT 160NE AC2201) MOT 12UP DC24 MOT 12UP ADC110 MOT 12UP ADC220 MOT 46NE DC24 MOT 46NE ADC110 MOT 46NE ADC220 MOT 12UP DC24 MOT 12UP ADC110 MOT 12UP ADC220 UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD630S, UCD800S UCB1000S, UCB1000L, UCB1250S, UCB1250L / UCD1000S, UCD1250S UCB1600S UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ Category MCCB MB ※ - Motor operator is not recommended for marine application. 1) MOT 160NE AC220 is not applicable for DC220V. Molded Case Circuit Breaker_ 205 U-Series / Molded Case Circuit Breaker Operating Accessories | Mechanical interlock (MIF) | A B C D [ Lock in OFF of left side breaker ] A: Distance between MCCBs B: Distance between bottom of MCCB and top of MIF Applicable MCCB Pole Order code 3P MIF 10A 3 4P MIF 10A 4 3P MIF 10UA 3 4P MIF 10UA 4 UCB50R, UCB50H, UCB50L UCB100R, UCB100S, UCB100H, UCB100L / UCD100S, UCD 50H, UCD100H 2, 3P MIF 10UF 3 4P MIF 10UF 4 UCB250R, UCB250S, UCB250N UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250S, UCD250H 2, 3P MIF 20UG 3 4P MIF 20UG 4 UCB400R, UCB400S, UCB400H, UCB400L / UCD400S 2, 3P MIF 40D 3 4P MIF 40D 4 UCB630R, UCB630S, UCB630H, UCB630L UCB800R, UCB800S, UCB800H, UCB800L / UCD630S, UCD800S 2, 3P MIF 80E 3 4P MIF 80E 4 3P MIF 12UP 3 UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R UPB100S, UPB100H, UPB100L, UPB100X UPB160S, UPB160H, UPB160L, UPB160X UPB250S, UPB250H, UPB250L, UPB250X HBL103U, HBL103UQ, HBL103UM, HBL103UMQ HBL203U, HBL203UQ, HBL203UM, HBL203UMQ / UPD100S, UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S 206 [ Lock of two breaker ] 4P MIF 12UP 4 3P MIF 46UP 3 4P MIF 46UP 4 [ Lock in OFF of right side breaker ] C: MIF width D: Distance between lower-side of MCCB and MIF Dimension (mm) A B C D 30 84 46.5 41.5 30 84 46.5 41.5 30 83 46.5 54.5 30 83 46.5 59.5 42.5 138 66.5 95 42.5 138 66.5 106.5 30 109 46.5 70 40 148 66.5 100.5 MCCB | Padlock plate (PLD) | Applicable MCCB Pole UAB30C, UAB30R, UAB50C, UAB50R, UAB50S, UAB50H, UAB60C, UAB60R, UAB100C, UAB100R, UAB100S PLD 10UA / UAD50C, UAD50S, UAD100R UCB50R, UCB50H, UCB50L, UCB100R, UCB100S, UCB100H, UCB100L / UCD50H, UCD100S, UCD100H PLD 10UF UCB160H, UCB160L, UCB250R, UCB250S, UCB250N, UCB250H, UCB250L / UCD160H, UCD250S, UCD250H UCB400R, UCB400S, UCB400H, UCB400L, UCB630R, UCB630S, UCB630H, UCB630L, PLD 40D UCB800R, UCB800S, UCB800H, UCB800L MCCB MB / UCD400S , UCD630S , UCD800S UCB1000S, UCB1000L, UCB1250S, UCB1250L / UCD1000S, UCD1250S PLD 120NE UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X, UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X PLD 12UP / UPD100S, UPD160S, UPD250S, UPD400S, UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ | Extension handle (THA) | Applicable MCCB B Order code Dimensions (mm) A B Category UCB400R, UCB400S, UCB400H, UCB400L, UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L THA 46D 42 40 THA 120NE 56 40 42 30 / UCD400S, UCD630S, UCD800S UCB1000S, UCB1000L, UCB1250S, UCB1250L / UCD1000S, UCD1250S A Mounting hole MCCB MB UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X THA 46UP / UPD400S, UPD630S ※ Excessive force in ON and OFF may break the handle of breaker. Molded Case Circuit Breaker_ 207 U-Series / Molded Case Circuit Breaker Mounting Accessories • Mounting accessories enable easy installation, maintenances and remove of breakers. DIN-rail adaptor DRA - Mounted on back side of UAB type breaker and enables direct installation on 35mm DIN-rail Mounting base TDM - Installed on back plate of panel and breaker can be easily replaced or maintained without cable disconnection | DIN-rail adaptor (DRA) | Applicable MCCB UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R 208 Order code DRA 10UA Category MCCB MB MCCB | Mounting base (TDM) and components for plug-in mounting | •Switchboard application Conductor Mounting base (TDM, TDF) Connection block at MCCB side Circuit conductor Mounting angle Lead cable for signal accessories Connection block (CBM, TYA) at mounting base side ※ The shape of mounting bases of each MCCB are not same as above. For exact appearances, please refer to "Characteristic Curves & Dimensions" from page 136-185. For line side only plug-in mounting For both line & load side plug-in mounting Applicable MCCB UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R UCB50R, UCB50H, UCB50L, UCB100R, UCB100S, UCB100H, UCB100L / UCD100S, UCD50H, UCD100H UCB160H, UCB160L, UCB250R, UCB250S, UCB250N, UCB250H, UCB250L / UCD160H, UCD250S, UCD250H UCB400R, UCB400S, UCB400H, UCB400L / UCD400S UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD630S, UCD800S UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ Mounting base Required Order quantity code TDM 10AP TDM 10BP TDM 20CF CBM 10AB 2 2C 1EA CBM 10AB 3 3C 1EA CBM 10AB 2 2C 1EA CBM 10AB 3 3C 1EA CBM 20C 2 2C 1EA CBM 20C 5 5C 1EA TYA 5/22) TYA 5/52) 2C 5C 1EA 1EA TYA 5/22) 2C 1EA 2EA TDM 5BA 2EA TDM 12NEP Conn. block barrier Contact Required quantity 1EA 2EA TDM 46NEP Order code 1EA TDM 4BA TDM 12NEP Connection block 1) TYA 5/52) 5C 1EA CBM 26NE 6 6C 1EA CBM 26NE 6 12C 2EA CBM 26NE 6 6C 1EA CBM 26NE 6 12C 2EA CBM 26NE 6 6C 1EA CBM 26NE 6 12C 2EA 1EA 1EA 1EA Mounting base Order code Required quantity Order code Required quantity CBM BARR 1EA TDM 10AF 1EA CBM BARR 1EA TDM 10BF 1EA - - TDM 20CF 1EA - - TDM 4BA 1EA - - TDM 5BA 1EA - - TDM 12NEF 1EA - - TDM 46NEF 1EA - - TDM 12NEF 1EA Category MCCB MB ※ - Plug-in mounting is applicable for 3P breaker. - Internal accessories do not support plug-in connection when installed seperately. Please contact us before order. 1) Connection blocks (CBM, TYA) are required for internal signal accessory installation in both line & load side plug-in type 3P breaker. 2) TYA type connection blocks are to be installed with separate mounting angle. Separate mounting angle is not supplied. Molded Case Circuit Breaker_ 209 U-Series / Molded Case Circuit Breaker Mounting Accessories •TDF 10A (Unit : mm) [ Mounting base ] [ Connection conductor ] 81 75 25 12.5 59 40.8 3 153.3 130 A 76.5 78.3 A 7 76.5 7.5 15 (Max:18) 25 RH M6 screw+S/W+P/W 76.5 79 9 [ Panel cut-out ] 2 25 25 76.8 9 RH M6 screw+S/W+P/W SEC A-A 20 13.5 21 5-M4 tapped hole 41 36 8.5 50 21.5 22 3 22 •TDF 10B (Unit : mm) [ Mounting base ] [ Connection conductor ] 92 89 30 75 58.5 30 SEC A-A 13.5 36 8.5 20 RH M6 screw+S/W+P/W 2 21.8 21 5-M4 tapped hole 21.5 3 210 27 41 9 97.3 172.3 155 3 75 A 7 75 86.3 A 39.3 7.5 15 (Max:18) RH M6 screw+S/W+P/W 12.5 30 30 9 [ Panel cut-out ] 27 MCCB •Distribution board application Application Item Order code Required quantity Mounting base unit Mounting base For Branching conductor component order Arc protection barrier TDA 10AD ASSY TDA 10AS 2RT-PH A 22S-PH10 A BRAN-BARR A CONN-PL A ARC-PL A TDA 10BD ASSY TDA 10BS 2RT-PH 22S-PH10 BRAN-BARR CONN-PL ARC-PL TDA 10AS 1R-PH A 1S-PH 1T-PH 1R-PH10 A 1S-PH10 1T-PH10 TDA 10BS 1R-PH 1S-PH 1T-PH 1R-PH10 1S-PH10 1T-PH10 1EA 2EA 2EA 1EA 2EA 1EA 1EA 1EA 2EA 2EA 1EA 2EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA Applicable MCCB UAB50R, UAB50S, UAB50H, UAB60R, UAB100C, UAB100R, UAB100S Connection plate Double mounting Mounting base unit Mounting base For Branching conductor component order Arc protection barrier UCB50H, UCB50L, UCB100R, UCB100S, UCB100H, UCB100L Connection plate Mounting base UAB50R, UAB50S, UAB50H, UAB60R, UAB100C, UAB100R, UAB100S Branching conductor Single mounting 5-63A 75-125A Mounting base UCB50H, UCB50L, UCB100R, UCB100S, UCB100H, UCB100L 5-63A Branching conductor 75-125A Mounting screw M5 x L18 4EA for mounting angle M5 x L12 1EA for bus bar M4 x L8 2EA for brancing conductor M4 x L25 4EA M5 x L20 4EA for mounting angle M5 x L12 1EA for bus bar M4 x L8 2EA for brancing conductor M4 x L25 4EA M4 x L30 4EA for mounting angle M5 x L12 1EA for bus bar M4 x L8 1EA for brancing conductor M5 x L32 4EA for mounting angle M5 x L12 1EA for bus bar M4 x L8 1EA for brancing conductor ※ Mounting base shall be connected to load side of MCCB. Branching conductor M5×L12 1S-PH 1S-PH10 M4×L8 M4×L8 M4×L8 M4×L8 M4×L8 M5×L12 M5×L12 M5×L12 M4×L8 M4×L8 M4×L8 2RT-PH 2RT-PH A Connection plate CONN-PL CONN-PL A 22S-PH 22S-PH10 22S-PH A 22S-PH10 A 1R-PH 1R-PH10 1R-PH A 1R-PH10 A 1T-PH 1T-PH10 Arc protection barrier ARC-PL ARC-PL A Molded Case Circuit Breaker_ 211 U-Series / Molded Case Circuit Breaker Mounting Accessories •TDA 10AD / Double mounting Load side terminal 18.5 43.7 179.5 Arc protection barrier (BRAN-BARR A) 28 Connection plate (ARC-PL A) 4- 4.5 hole Line RH screw M4×L25+S/W+P/W 87 6 50 Line 43.3 63 360 63 Line 25 235 Connection plate (CONN-PL A) 235 6 50 M5 tapped hole for branching conductor (22S-PH10 A) Line Mounting angle 37 12.5 RH screw M4×L18+S/W+P/W 87 M5 tapped hole for branching conductor (2RT-PH A) 25 [ Drilling holes for mounting ] M4 nut+S/W+P/W hole nting 5 mou 28 M5 tapped hole for branching conductor (2RT-PH A) 15 12.5 50 25 22 80 80 21 •TDA 10AS / Single mounting M5 tapped hole for branching conductor (1T-PH, 1T-PH10) M5 tapped hole for branching conductor (1S-PH, 1S-PH10) RH M4×L10+S/W+P/W Line 50 M4 nut+S/W+P/W 12 RH screw M4×L30+S/W Mounting angle 80.8 162 115.3 18.5 46.5 87 43.3 43.7 18.5 80 212 50 9 50 15 4.5 mounting hole 25 21 22 80 46.5 M5 tapped hole for branching conductor (1R-PH A, 1R-PH10 A) 180 162 Line 27.3 80.8 9 7 7 33 24.2 Line [ Drilling holes for mounting ] Insulation plate 1.6t (not supplied) 25 4- 4.5 hole MCCB •TDA 10BD / Double mounting Load side terminal 18.5 27.5 M5 tapped hole for branching conductor (2RT-PH) M5 tapped hole for branching conductor (22S-PH10) Mounting angle Arc protection barrier (BRAN-BARR) 40 RH screw M4×L25+S/W+P/W 50 99 27.5 49.3 2 49.7 2 Line M5 tapped hole for branching conductor (2RT-PH) 8.5 5.8 mounting hole 94 18.5 M4 tapped hole for branching conductor 60 15 26 24.5 248.5 Connection plate (ARC-PL) 27.5 193.5 65.5 Line 385 248.5 65.5 27.5 Line 4- 5.5 hole Mounting angle Line 6 50 Connection plate (CONN-PL) [ Drilling holes for mounting ] M5 nut+S/W+P/W RH screw M5×L20+S/W+P/W 8.5 30 20 81 30 •TDA 10BS / Single mounting M5 tapped hole for branching conductor (1T-PH, 1T-PH10) 50 Line 16 M4 tapped hole [ Drilling holes for mounting ] 94 27 5.8 mounting hole 26 20 24.5 81 18.5 10 10 172.5 191 99 85.7 49.7 1.5 46 M5 tapped hole for branching conductor (1R-PH, 1R-PH10) 50 191 Line 49.3 95.3 86.8 8.5 46 18.5 Line M5 nut+S/W+P/W 12 RH screw M5×L32+S/W+P/W 33 M5 tapped hole for branching conductor (1T-PH, 1T-PH10) Mounting angle 30 4- 5.5 hole Insulation plate 1.6t (not supplied) Molded Case Circuit Breaker_ 213 U-Series / Molded Case Circuit Breaker Terminal Accessories • Terminal accessories offers convenience of connection, high protection for safety. Terminal bus bar TBB - Increases the distances between terminals Cage terminal block CTB - Offers easy and direct connection of cables Rear barrier REAR-BR - Enhance the insulation of terminal 214 Terminal cover TCF - Prevents direct contact to live terminal as well as insertion of external material Interpole barrier TQQ - Increases the insulation between poles MCCB | Terminal connection screws / standard components | Type Clamp screw Pan head screw Hexagon socket head screw Size Applicable MCCB M5 - UAB30C, UAB30R, UAB50C, UAB50R, UAB50S, UAB50H, UAB60C, UAB60R, UAB100C (5-50A), UAB100R (15-50A), UAB100S (15-50A) / UAD50C, UAD50S - UCB50R - UBD30L, UBD30H, UMB30R, UMB30S, UMB30H, UMB50S, UMB50H, UDB30S, UDB30H, UDB50S, UDB50H, UDB100S (15-50A), UDB100H (15-50A), UGD30L, UGD30H, UMG30R, UMG30S, UMG30H, UMG50S, UMG50H, UDG30S, UDG30H, UDG50S, UDG50H, UDG100S (15-50A), UDG100H (15-50A) M8 - UAB100C (60-100A), UAB100R (60-100A), UAB100S (60-100A) / UAD100R - UCB50H, UCB50L, UCB100R, UCB100S, UCB100H, UCB100L, UCB160H, UCB160L, UCB250R, UCB250S, UCB250N, UCB250H, UCB250L / UCD50H, UCD100S, UCD100H, UCD160H, UCD250S, UCD250H - UDB100S (60-100A), UDB100H (60-100A), UDG100S (60-100A), UDG100H (60-100A) - UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S - HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ M10 - UCB400R, UCB400S, UCB400H, UCB400L / UCD400S - UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S M12 - UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD630S, UCD800S M12 - UCB1000S, UCB1000L, UCB1250S, UCB1250L / UCD1000S, UCD1250S M13 - UCB1600S Hexagon head screw | Terminal bus bar (TBB) | Order code Applicable MCCB UCB250R, UCB250S, UCB250N / UCD250S UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H UCB400R, UCB400S, UCB400H, UCB400L / UCD400S UCB630R, UCB630S, UCB630H,UCB630L / UCD630S UCB800R, UCB800S, UCB800H, UCB800L / UCD800S UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X / UPD400S UPB630S, UPB630H, UPB630L, UPB630X / UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ Mounting Category hole 2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET) TBB 20C 2 TBB 20C 3 TBB 20C 4 ∮11 TBB 4S 2 TBB 4S 3 TBB 4S 4 ∮13 TBB 6S 2 TBB 6S 3 TBB 6S 4 ∮13 TBB 8S 2 TBB 8S 3 TBB 8S 4 ∮13 - TBB 12NE 3 TBB 12NE 4 ∮11 - TBB 40NE 3 TBB 40NE 4 ∮13 - TBB 60NE 3 TBB 60NE 4 ∮13 - TBB 12NE 3 - ∮11 [ 2 pole ] MCCB [ 3 pole ] MB [ 4 pole ] Molded Case Circuit Breaker_ 215 U-Series / Molded Case Circuit Breaker Terminal Accessories CTB 10A CTB 10B CTB 20C CTB 40D CTB 46UP L L S S S CTB 80E S Wire Order code Applicable MCCB L L | Cage terminal block (CTB) | Connection Tightening torque (kgf-㎝) Category Cable connector (EA) S (㎟) L (㎜) CTB 10A 3S50 CTB 10A 4S50 1 1 X 5.5-50 14 60 CTB 10A 3S100 CTB 10A 4S100 1 1 X 5.5-50 14 60 3EA/SET 4EA/SET Wire size UAB30C, UAB30R, UAB50C, UAB50R, UAB50S, UAB50H, UAB60C(5-50A), UAB60R(5-50A), UAB100C(5-50A), UAB100R(15-50A), UAB100S(15-50A) / UAD50L, UAD50S UAB60C(60A), UAB60R(60A), UAB100C(60-100A), UAB100R(60-100A), UAB100S(60-100A) / UAD100R UCB50R, UCB100R, UCB100S / UCD100S UCB50H, UCB50L, UCB100H, UCB100L CTB 10B 3S CTB 10B 4S 1 1 X 8-50 14 60 CTB 20C 3S CTB 20C 4S 1 1 X 14-120 19 140 CTB 40D 3S CTB 40D 4S 2 2 X 60-120 30-60 353 MCCB MB CTB 80E 3S CTB 80E 4S 3 3 X 85-160 30-60 353 CTB 12UP 3S CTB 12UP 4S 1 1 X 14-120 19 140 CTB 46UP 3S CTB 46UP 4S 2 2 X 60-185 30-60 353 CTB 12UP 3S CTB 12UP 4S 1 1 X 14-120 19 / UCD50H, UCD100H UCB250R, UCB250S, UCB250N / UCD250S UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H UCB400R, UCB400S, UCB400H, UCB400L / UCD400S UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD630S, UCD800S UPB100S, UPB100H, UPB100L, UPB100X / UPD100S UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X / UPD400S UPB630S, UPB630H, UPB630L, UPB630X / UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM HBL203U, HBL203UM, HBL203UQ, HBL203UMQ 216 140 MCCB | Terminal cover (TCF) | C B A 2 pole Applicable MCCB 3 pole Dimensions Order code A B TCF 10AP 2 50 UCB50R, UCB100R, UCB100S / UCD100S TCF 10BP 2 60 UCB250R, UCB250S, UCB250N / UCD250S TCF 20CP 3 105 4 pole Dimensions C Order code A B 5.5 60 TCF 10AP 3 75 Category Dimensions C Order code A B C 5.5 60 TCF 10AP 4 100 5.5 60 UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R UCB50H, UCB50L, UCB100H, UCB100L / UCD50H, UCD100H UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H UCB400R, UCB400S, UCB400H, UCB400L / UCD400S 10 59 TCF 10BP 3 90 10 59 TCF 10BP 4 120 10 59 10.5 59 TCF 20CP 3 105 10.5 59 TCF 20CP 4 140 10.5 59 90 10 59 TCF 10FP 3 90 10 59 TCF 10FP 4 120 10 59 TCF 20GP 3 105 10 59 TCF 20GP 3 105 10 59 TCF 20GP 4 140 10 59 TCF 40D 3 190 120 100 TCF 40D 3 190 120 100 TCF 40D 4 234 120 100 TCF 80E 3 230 139 100 TCF 80E 3 230 139 100 TCF 80E 4 300 139 100 - - - - TCF 160NE 3 210 51 151 - - - - - - - - TCF 12UP 3 105 10 82.5 TCF 12UP 4 140 10 82.5 - - - - TCF 46UP 3 140 10 108 TCF 46UP 4 185 10 108 - - - - TCF 12UP 3 105 10 82.5 - - - - TCF 10FP 3 UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L MCCB MB / UCD630S, UCD800S UCB1600S UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ ※ For both line and load side of MCCB, 2EA shall be ordered. | Rear barrier (REAR-BR) | Applicable MCCB Order code 2 pole 3 pole 4 pole UAB30C, UAB30R, UAB50L, UAB50R, UAB50S,UAB50H, UAB60C, UAB60R, UAB100C, UAB100R, UAB100S / UAD50C, UAD50S, UAD100R REAR-BR 10A 2 REAR-BR 10A 3 - UCB50R, UCB100R, UCB100S / UCD100S REAR-BR 10B 2 REAR-BR 10B 3 - UCB250R, UCB250S, UCB250N / UCD250S REAR-BR 20C 3 REAR-BR 20C 3 REAR-BR 20C 4 Category MCCB MB ※ For both line and load side of MCCB, 2EA shall be ordered. Molded Case Circuit Breaker_ 217 U-Series / Molded Case Circuit Breaker Terminal Accessories | Interpole barrier (TQQ) | 3P 3P 4P 4P B B AA AA 2P 2P B B Applicable MCCB Order code Required quantity for both Description (Quantity supplied as line and load side of MCCB standard components 2 pole 3 pole 4 pole of 3 pole MCCB) Dimensions A B 50 53 Category UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C UAB50S, UAB50H, UAB100R, UAB100S TQQ 10A 3PLINE 2EA/SET 2 4 6 / UAD50S, UAD100R UCB50R, UCB100R, UCB100S / UCD100S TQQ 10B 3PLINE 2EA/SET 2 4 6 50 53 UCB250R, UCB250S, UCB250N / UCD250S TQQ 20C 3PLINE 2EA/SET 4 4 6 50 53 TQQ 12FG 3PLINE 2EA/SET 4 4 6 51 53 TQQ 4BA 3PLINE 2EA/SET 4 4 6 120 97 TQQ 5BA 3PLINE 2EA/SET 4 4 6 110 95 TQQ 80NE 3P 2EA/SET - 4 6 125 92 TQQ 160NE 3P1) 4EA/SET - 4 - 102 68 TQQ 12NE 3P 4EA/SET - 4 6 71 54.5 TQQ 46NE 3P 4EA/SET - 4 6 122 103 TQQ 12NE 3P 4EA/SET - 4 - 71 54.5 TQQ 10A 3PLINE 2EA/SET 2 4 - 50 53 UCB50H, UCB50L, UCB100H, UCB100L, UCB160H, UCB160L, UCB250H, UCB250L / UCD50H, UCD100H, UCD160H, UCD250H UCB400R, UCB400S, UCB400H, UCB400L / UCD400S UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD630S, UCD800S UCB1000S, UCB1000L, UCB1250S, UCB1250L / UCD1000S, UCD1250S UCB1600S UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ UDB30S, UDB30H, UDB50S, UDB50H, UDB100S, UDB100H, UDG30S, UDG30H, UDG50S, UDG50H, UDG100S, UDG100H ※ 1) This item is not sold separately 218 MCCB MB MCCB Portable Test Equipment | MCCB trip unit tester | •MCCB trip unit tester (MCCB OCR TESTER) can test LTD and STD (below 600%) function of trip unit in the field MCCB OCR TESTER Order code Rated voltage input AC100-230V output DC 9V Dimension W320 x H115 x D265 mm Weight 2.7 kg Standard kit Tester, DC9V adaptor, connector Applicable MCCB - UCB1000S, UCB1000L, UCB1250S, UCB1250L - UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X, UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X Molded Case Circuit Breaker_ 219 Technical Information + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + U-Series / Molded Case Circuit Breaker Current Setting for UPB type and UCB 1000-1600 type | UPB100, UPB160, UPB250 / Thermal magnetic type | •Protection characteristics and current setting Rated current [In] (A) LTD ① Rated current setting [Ir] (A) 15 In x 40 50 60 63 75 80 100 125 150 160 175 200 225 250 0.8 12162432 40 48 50 60 64 80 100 120140 160 180 200 0.9 14182736 45 54 57 68 72 90 113 135158 180 203 225 1.0 15 50 60 63 75 80 100 125 150 160 175 200 225 250 Fixed (In x 10) Tolerance INST ② Instantaneous current setting [Ii] (A) Trip unit Adjustable1) 16 16 20 20 25 25 30 30 32 32 40 150 160 200 250 300 320 400 500 600 630 750 800 1000 1250 1500 1600 1750 2000 2250 2500 + 20% UPB100: MTM-10-JF, UPB160: MTM-16-JF, UPB250: MTM-25-JF - In x 5-6-7-8-9-10 Tolerance Trip unit - In x 5-9: +30%, -20% In x 10: + - 20% UPB160: MTM-16-JJ, UPB250: MTM-25-JJ ※ 1) Adjustable instantataneous is available for UPB160 and UPB250. 1 LTD current [Ir] setting knob 2 INST current [Ii] setting knob | UPB100, UPB160, UPB250 / Electronic type | •Protection characteristics and current setting Model Trip unit Rated (CT) current [In] (A) LTD STD INST PTA ① Rated current setting [Ir] (A) UPB100 UPB160 MOR-10-ES MOR-16-ES 125 160 50, 55, 63, 70, 80, 90, 100, 115, 125 UPB250 MOR-25-ES 250 63, 70, 80, 90, 100, 110, 125, 140, 160100, 110, 125, 140, 160, 175, 200, 225, 250 Long time setting [tr] 6.25 sec. at Ir x 600% Tolerance ② Short time pick-up current [Isd] (A) Ir x NON-2-3-4-5-6-7-8-9-10 Tolerance ④ Time delay setting [tsd] 0.05-0.1-0.2-0.3 sec. at definite time-limit section Tolerance+50ms, -20ms Instantaneous current setting In x 1100% + Tolerance20% - Ir x 90% Tolerance [Ii] (A) Pre-trip alarm current [Ip] (A) + - 20% ※ The default values are underlined. Please check and adjust the setting condition of each characteristic before use. 1 LTD current [Ir] setting knob 2 STD current [Isd] setting knob 3 Pick-up LED 4 STD time [tsd] setting knob 5 Frequency selection switch 6 Tester connection port 222 MCCB | UPB400, UPB630 / Electronic type | •Protection characteristics and current setting Model Trip unit UPB400 UPB630 MOR-40-ES2) / MOR-40-GS 400 0.8 0.85 0.9 0.95 1.0 Io Ir Io Ir 0.63 200 215 225 240 250 0.63 ① Rated current setting [Ir] (A) 0.8 255 270 290 300 320 0.8 1.0 320 340 360 380 400 1.0 ② Long time setting [tr] 2-4-6-8-12 sec. at Ir x 600% ③ Short time pick-up current [Isd] (A) Ir x NON-2-4-6-8-10 ④ Time delay setting [tsd]1) 0-0.1-0.2-0.3 sec. at definite time-limit section ⑥ Instantaneous current setting In x NON-3-6-8-10-11 [Ii] (A) ⑦ Ground fault current [Ig] (A) In x NON-0.2-0.3-0.4 ⑧ Ground fault delay setting [tg] 0.1-0.2-0.3-0.4-0.8 sec. at definite time-limit section ⑫ Pre-trip alarm current [Ip] (A) Ir x 0.9 MOR-63-ES2) / MOR-63-GS Rated (CT) current [In] (A) LTD STD INST GFT2) PTA 0.8 320 400 500 630 0.85 0.9 0.95 1.0 340 360 380 400 430 450 480 500 540 570 600 630 Tolerance + -20% Tolerance + -15% Tolerance +50ms, -20ms Tolerance + -20% Tolerance Tolerance Tolerance + -15% +50ms, -20ms + - 10% ※ - The default values are underlined. Please check and adjust the setting condition of each characteristic before use. 1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob ❹. 2) GFT protection is option and not applicable for MOR-40-ES and MOR-63-ES trip unit. 1 2 3 4 5 6 LTD current [Ir] setting knob LTD time [tr] setting knob STD current [Isd] setting knob STD time [tsd] setting knob I2t ON-OFF indication INST current [Ii] setting knob GFT current [Ig] setting knob GFT time [tg] setting knob 9 Tester connection port 10 Frequency selection switch 11 Base current [Io] setting knob 12 PTA [Ip] LED 7 8 | UCB1000, UCB1250 / Electronic type | •Protection characteristics and current setting MCCB Trip unit UCB1000 UCB1250 MOR-100-ES2) / MOR-100-GS 1000 0.8 0.85 0.9 0.95 1.0 Io Ir Io Ir 0.63 505 535 565 600 630 0.63 ① Rated current setting [Ir] (A) 0.8 640 680 720 760 800 0.8 1.0 800 850 900 950 1000 1.0 2-4-6-8-12 sec. at Ir x 600% ② Long time setting [tr] ③ Short time pick-up current [Isd] (A) Ir x NON-2-4-6-8-10 0-0.1-0.2-0.3 sec. at definite time-limit section ④ Time delay setting [tsd]1) ⑥ Instantaneous current setting In x NON-3-6-8-10-11 [Ii] (A) In x NON-0.2-0.3-0.4 ⑦ Ground fault current [Ig] (A) 0.1-0.2-0.3-0.4-0.8 sec. at definite time-limit section ⑧ Ground fault delay setting [tg] Ir x 0.9 ⑫ Pre-trip alarm current [Ip] (A) MOR-125-ES2) / MOR-125-GS Rated (CT) current [In] (A) LTD STD INST GFT2) PTA 0.8 630 800 1000 1250 0.85 0.9 0.95 1.0 670 710 750 790 850 900 950 1000 1060 1125 1190 1250 Tolerance + -20% Tolerance + -15% Tolerance +50ms, -20ms Tolerance + -20% Tolerance Tolerance Tolerance + -15% +50ms, -20ms + - 10% ※ - The default values are underlined. Please check and adjust the setting condition of each characteristic before use. 1) I2t characteristic can be activate by adjusting [tsd] knob ❹. 2) GFT protection is option and not applicable for MOR-100-ES and MOR-125-ES trip unit. 1 2 3 4 5 6 LTD current [Ir] setting knob LTD time [tr] setting knob STD current [Isd] setting knob STD time [tsd] setting knob I2t ON-OFF indication INST current [Ii] setting knob GFT current [Ig] setting knob GFT time [tg] setting knob 9 Tester connection port 10 Frequency selection switch 11 Base current [Io] setting knob 12 PTA [Ip] LED 7 8 Molded Case Circuit Breaker_ 223 U-Series / Molded Case Circuit Breaker Current Setting for UPB type and UCB 1000-1600 type | Current setting procedure / Electronic type 400-1250A| In 400A In Io 0.63 0.8 1.0 Io 0.63 0.8 1.0 Ir 0.8 0.85 0.9 1.0 Ir 0.8 0.85 0.9 10 Isd 0.95 630A 2 4 6 8 2 4 6 STD = 6×Ir = 2160A Ii 3 6 8 0.2 0.3 10 Ii 11 3 6 Ig 0.4 1000A In 0.8 1.0 Io 0.63 Ir 0.8 0.85 0.9 Ir 0.8 0.3 0.95 1.0 6 8 0.8 1.0 3 6 Isd 10 2 0.85 0.9 4 8 0.2 0.3 0.95 1.0 6 8 10 10 11 STD = 6×Ir = 6750A 10 Ii 11 3 6 INST = 8×In = 8000A Ig 0.4 LTD = 1200×0.9×1.0 = 1125A STD = 6×Ir = 5400A Ii 11 1250A LTD = 1000×0.9×1.0 = 900A 4 10 GFT = 0.3×In = 190A 0.63 2 8 0.2 Io Isd 10 INST = 8×In = 5040A GFT = 0.3×In = 120A In 8 STD = 6×Ir = 3420A INST = 8×In = 3200A Ig 1.0 LTD = 630×0.9×1.0 = 570A LTD = 400×0.9×1.0 = 360A Isd 0.95 8 INST = 8×In = 10000A Ig 0.4 0.2 GFT = 0.3×In = 300A 0.3 0.4 GFT = 0.3×In = 375A | UCB1600 / Electronic type | •Protection characteristics and current setting Rated (CT) current [In] (A) 0.4 0.5 0.6 0.7 0.8 0.9 0.95 1.0 640 800 960 1120 1250 1440 1520 1600 LTD Rated current setting [I1] (A) INST Instantaneous current setting [Ii] (A) I1 x 2-3-4-5-6-7-8-10 Red light I > 0A Green light I > 0.4 x In Yellow light I > I1 LED indication 224 1600 In x MCCB Selection By Application | Model selection for transformer | •AC220V Capacity of Three phase transformer Single phase (kVA) ≤30 70-100 ≤50 ≤16 ≤30 ≤50 2.5 Breaking capacity of MCCB (kA)(Sym) 500-750 ≤150 5 25 UAB30C UAB30R UAB50C UAB50R UAB60C UAB60R 35 42 50 ≤2000 65 UAB50H, UCB50R UCB250R ≤1500 ≤300 10 UAB100C MCCB 150-300 UCB50H UAB100S, UCB100R 100 125 UCB50L UPB100H, UPB100L UCB100S UCB100H UCB100L UCB250H UCB250L UPB250H, UPB250L UCB250S UCB250N UCB400R UCB400S UCB400H UCB630R 85 UPB400H, UCB400L UPB400S, UPB400L, UPB400X UCB630S, UCB630H UCB800R UCB800S, UCB800H UPB630S, UPB630H, UPB630L, UPB630X UCB800L UCB1000L, UCB1250L UCB1000S, UCB1250S •AC460V Capacity of transformer (kVA) ≤50 75-200 1.5 Breaking capacity of MCCB (kA)(Sym) ≤300 10 UAB30C UAB30R UAB50C UAB50R UAB60C UAB60R UAB100C ≤1500 18 25 42 UCB50H UCB250S UCB400R UCB630R ≤2000 35 UAB50H, UCB50R UAB100S, UCB100R UCB250R MCCB ≤750 5 ≤3000 50 65 75 85 100 UCB50L UCB100S UCB100H UCB100L UPB100H UPB100L UCB250N UCB250H UCB250L UPB250H UPB250L UCB400S UCB400LUPB400L, UPB400X UCB400H UCB800R UCB630S UCB630H UCB630L UPB630L, UPB630X UCB800S UCB800H UCB800L UCB1000L,UCB1250L UCB1000S, UCB1250S | Rated current selection for condenser | Capacity of condenser (kVAR) 5 Rated current of MCCB (A) Single phase (1 pole) AC220V 50Hz 60 Three phase (3 pole) AC440V AC220V AC440V 60Hz 50 50Hz 30 60Hz 30 50Hz 40 60Hz 50 50Hz 30 60Hz 20 10 75 60 40 40 50 50 30 30 15 100 100 60 50 60 60 40 40 20 175 175 75 60 100 75 50 40 25 200 200 100 100 100 100 50 50 30 225 225 100 100 175 150 60 60 40 400 400 150 125 200 200 100 75 50 400 400 175 175 225 225 100 100 75 600 500 300 300 400 400 150 150 100 800 800 400 400 400 400 225 225 150 1000 1000 600 500 600 600 300 300 200 - 1200 800 800 800 800 400 400 300 - - 1000 1000 - - 600 600 400 - - - - - - - 800 ※ -The start-up inrush current is about 10 times of rated current. -The mentioned value can be applied to maximum rated current of MCCB. -The rated current of MCCB is recommended to be 150% of rated current of condenser. Molded Case Circuit Breaker_ 225 U-Series / Molded Case Circuit Breaker Selection By Application | Model selection for lighting and heater | •The maximum operational current shall not exceed 80% of MCCB rated current. Breaking capacity (kA) Maximum operational Rated current sym 2.5 5 current (A) of MCCB (A) 12 15 16 20 24 30 32 40 40 50 48 60 60 75 10 25 UAB30R UAB30C 35 50 65 UAB50H, UCB50H UCB50R UAB50C UAB50R UAB60C UAB60R UAB100S, UCB100R UAB100C 85 100 125 UCB50L UCB100S UCB100H UCB100L UPB100H, UPB100L UCB250N UCB250H UCB250L UPB250H, UPB250L, 80 100 100 125 120 150 140 175 160 200 180 225 200 250 240 300 280 350 320 400 400 500 500 630 560 700 640 800 800 1000 UCB1000S UCB1000L 1000 1250 UCB1250S UCB1250L UCB250R UCB250S UCB400R UCB400S UCB400H UPB400S, UPB400H, UPB400L, UPB400X UCB400L UCB630R UCB630S, UCB630H UPB630S, UPB630H, UPB630L, UPB630X UCB800R UCB800S, UCB800H UCB800L •AC460V Breaking capacity (kA) Maximum operational Rated current sym 1.5 5 current (A) of MCCB (A) 226 10 18 25 35 42 50 65 75 85 100 12 15 16 20 24 30 32 40 40 50 48 60 60 75 80 100 100 125 120 150 140 175 160 200 180 225 200 250 240 300 280 350 320 400 400 500 500 630 560 700 640 800 800 1000 UCB1000S UCB1000L 1000 1250 UCB1250S UCB1250L UAB30C UAB30R UAB50H UCB50H UCB50R UAB50C UAB50R UAB60C UAB60R UAB100C UAB100S UCB100S UCB100H UCB100L UPB100H UPB100L UCB250S UCB250N UCB250H UCB250L UPB250H UPB250L UAB100R UCB250R UCB400R UCB50L UCB400S UCB400H UCB400L UCB630R UCB630S UCB630H UCB630L UCB800R UCB800S UCB800H UCB800L UPB400L, UPB400X UPB630L, UPB630X MCCB | Rated current selection for motor and other loads | Circuit diagram Condition IM1 Permissible current of cable [Iw] ΣIM≦ΣIL Iw≧ΣIM+ΣIL 50A≧ΣIM > ΣIL Iw≧1.25ΣIM+ΣIL 50A < ΣIM > ΣIL Iw≧1.1ΣIM+ΣIL IM2 IN IW IL1 IL2 IM : Load current of motor IL : Load current of other loads Rated current of MCCB [In] Less value among IN≦3ΣIM+ΣIL or IN≦2.5Iw. In case of Iw>100A, when calculated value is not matched with the rated current of MCCB, it is recommended to select the right above value. Molded Case Circuit Breaker_ 227 U-Series / Molded Case Circuit Breaker Selection By Application ■ Rated current of MCCB for AC220V three phase induction motor Maximum Total capacity of operational current 0.75 / 1.5 / motors (below kW) (below A) 4.8 8 3 4.5 6.3 8.2 12 15.7 19.5 23.2 30 37.5 45 52.5 63.7 75 86.2 97.5 112.5 125 150 175 220 15 20 30 40 50 75 90 100 125 150 175 100 150 300 350 400 450 500 600 700 800 20 30 40 50 60 100 100 125 150 175 200 225 300 350 400 500 500 600 700 800 900 30 30 40 50 60 100 100 125 150 175 200 225 300 350 400 500 500 600 700 800 900 Capacity of the biggest motor: Capacity of motor (kW) / Full load current (A) 2.2 / 11.1 3.7 / 17.4 5.5 / 26 7.5 / 34 11 / 48 15 / 18.5 / 22 / 65 79 93 30 / 125 37 / 160 45 / 190 5/ 230 75 / 310 90 / 360 110 / 132 / 440 500 30 30 40 50 60 100 100 125 150 175 200 225 300 350 400 500 500 600 700 800 900 50 50 50 60 100 100 125 150 175 200 225 300 350 400 500 500 600 700 800 900 60 75 75 100 100 125 150 175 200 225 300 350 400 500 500 600 700 800 900 100 100 100 100 125 150 175 200 225 300 350 400 500 500 600 700 800 900 125 125 125 150 175 200 225 300 350 400 500 500 600 700 800 900 150 150 150 150 175 200 225 300 350 400 500 500 600 700 800 900 300 300 300 300 350 400 500 500 600 700 800 900 400 400 400 400 400 500 500 600 700 800 900 500 500 500 500 500 500 600 700 800 900 500 500 500 500 500 600 700 800 900 600 600 700 700 700 800 900 700 700 700 800 800 900 1000 1000 1000 900 175 175 175 200 200 225 300 350 400 500 500 600 700 800 900 200 225 225 225 225 300 350 400 500 500 600 700 800 900 1000 1000 1000 ※ -The rated currents are for MCCBs. -The mentioned values are applicable when MCCB trips within 10 sec. at 600% of full load current and the start-up inrush current is within 1700% of full load current. -Above selection is also applied in case that several loads starts up at same time. ■ Rated current of MCCB for AC440V three phase induction motor Maximum Total capacity of operational current 0.75 / 1.5 / motors (below kW) (below A) 2.4 4 3 4.5 6.3 8.2 12 15.7 19.5 23.2 30 37.5 45 52.5 63.7 75 86.2 97.5 112.5 125 150 175 200 250 300 350 400 450 500 7.5 10 15 20 25 38 45 50 63 75 88 100 125 150 175 200 225 250 300 350 400 500 600 700 700 900 1000 Capacity of the biggest motor: Capacity of motor (kW) / Full load current (A) 2.2 / 3.7 / 5.5 / 7.5 / 11 / 15 / 18.5 / 22 / 30 / 37 / 45 / 55 / 75 / 90 / 110 / 132 / 5.5 8.7 13 17 24 32 39 46 62 80 95 115 155 180 220 250 15 15 15 15 15 15 30 20 20 20 30 40 30 30 30 30 40 50 30 30 30 30 40 50 50 50 50 50 50 50 60 75 50 50 50 50 50 50 60 75 100 60 60 60 60 60 60 60 75 100 125 75 75 75 75 75 75 75 100 100 125 100 100 100 100 100 100 100 100 100 125 150 100 100 100 100 100 100 100 100 100 125 150 175 125 125 125 125 125 125 125 125 125 125 150 175 225 150 150 150 150 150 150 150 150 150 150 150 200 225 250 175 175 175 175 175 175 175 175 175 175 175 200 225 250 200 200 200 200 200 200 200 200 200 200 200 200 225 300 350 225 225 225 225 225 225 225 225 225 225 225 225 225 300 350 400 250 250 250 250 250 250 250 250 250 250 250 250 250 300 350 400 300 300 300 300 300 300 300 300 300 300 300 300 300 300 350 400 500 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 400 500 500 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 ※ -The rated currents are for MCCBs. -The mentioned values are applicable when MCCB trips within 10 sec. at 600% of full load current and the start-up inrush current is within 1700% of full load current. -Above selection is also applied in case that several loads starts up at same time. 228 MCCB Insulation Distance Insulation plate Upper plate of panel Side plate of panel B1 B2 B1 B1 B2 B2 A A A Direct cable connection D Taping Bus bar connection Applicable MCCB Rear or plug-in connection C A B1 Distances B2 C D 75 50 30 from 0 25 80 50 30 from 0 25 80 60 50 from 0 25 80 60 50 from 0 40 100 100 80 from 0 80 50 120 80 from 0 80 80 50 30 from 0 10 100 100 70 from 0 10 120 100 80 from 0 80 UAB30C, UAB30R, UAB50C, UAB50R, UAB50S, UAB50H, UAB60C, UAB60R, UAB100C, UAB100R, UAB100S / UAD50C, UAD50S, UAD100R UCB50R, UCB50H, UCB50L, UCB100R, UCB100S, UCB100H, UCB100L / UCD50H, UCD100R, UCD100H UCB250R UCB160H, UCB160L, UCB250S, UCB250N, UCB250H, UCB250L / UCD160H, UCD250S, UCD250H UCB400R, UCB400S, UCB400H, UCB400L, UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L / UCD400S, UCD630S, UCD800S UCB1000S, UCB1000L, UCB1250S, UCB1250L, UCB1600S / UCD1000S, UCD1250S UPB100S, UPB100H, UPB100L, UPB100X / UPD100S UPB160S, UPB160H, UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X / UPD160S, UPD250S UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S HBL103U, HBL103UM, HBL103UQ, HBL103UMQ 80 50 30 from 0 10 HBL203U, HBL203UM, HBL203UQ, HBL203UMQ 100 100 70 from 0 10 Molded Case Circuit Breaker_ 229 U-Series / Molded Case Circuit Breaker Cascading Table | AC240V | Downstream Upstream UAB-C Recognition category UAB/UCB-S UAB100C UCB250R UCB400R UCB630R UCB800R UAB100S UCB250S UCB400S UCB630S UCB800S Model Rated current (A) 5-100 125-250 250-400 500,630 700,800 15-100 125-250 250-400 500,630 700,800 Breaking capacity [Icu] (kA r.m.s) 25 35 35 50 50 50 50 50 100 100 UAB30C 3-30 10 25 30 30 35 35 35 UAB50C 5-50 10 25 30 30 35 35 35 UAB60C 5-60 10 25 30 30 35 35 35 UAB100C 5-100 25 35 35 42 42 42 42 65 65 UAB30R 5-30 25 35 35 42 42 42 42 42 65 65 UAB50R 5-50 25 35 35 42 42 42 42 42 65 65 UAB60R 5-60 25 35 35 42 42 42 42 42 65 65 UAB100R 15-100 42 50 50 50 50 75 75 UCB50R 15-50 50 85 85 UCB100R 15-100 50 85 85 UCB250R 125-250 35 65 65 UCB400R 250-400 35 UAB50S 15-50 42 UAB100S 15-100 UAB/UCB-S UCB100S UAB-C UAB/UCB-R UCB-L UPB-H UPB-L 50 50 50 50 50 50 65 50 50 50 75 75 50 85 85 15-100 65 85 85 UCB250S 125-250 50 85 85 UCB400S 250-400 50 UAB50H 15-50 50 UCB50H 15-50 85 100 100 15-125 85 100 100 UCB250H 125-250 85 100 100 UCB400H 250-400 85 UCB50L 15-50 100 UCB100L 15-125 100 UCB250L 125-250 100 UCB400L 250-400 125 UPB100H 15-125 130 UPB250H 100-250 130 UPB100L 15-125 150 UPB250L 100-250 150 UAB/UCB-H UCB100H 230 UAB-R 85 100 MCCB UCB-H UCB-L UPB-H UPB-L UCB100H UCB250H UCB400H UCB630H UCB800H UCB100L UCB250L UCB400L UCB630L UCB800L UPB100H UPB250H UPB100L UPB250L 15-125 125-250 250-400 500,630 700,800 15-125 125-250 250-400 500,630 700,800 15-125 100-250 15-125 85 85 85 100 100 100 100 125 125 125 130 130 150 50 50 50 50 50 65 50 50 50 50 50 65 50 50 50 50 50 65 65 65 65 65 65 85 85 85 65 65 65 65 65 65 65 85 85 85 85 85 100 100 65 65 65 65 65 65 65 85 85 85 85 85 100 100 65 65 65 65 65 65 65 85 85 85 85 85 100 100 75 75 75 75 75 100 100 100 85 85 85 85 100 100 100 100 85 85 85 85 100 100 100 100 65 65 65 100 100 100 85 100 100 100 100 100-250 150 130 130 100 130 130 100 65 100 100 100 100 100 85 100 125 125 125 100 130 85 85 100 125 125 125 100 130 85 85 125 125 125 85 85 75 75 85 85 85 85 85 85 100 100 125 125 125 100 125 125 125 100 125 125 125 100 100 100 100 130 130 125 85 100 100 130 130 130 130 130 130 150 150 130 150 125 100 125 125 125 125 125 125 125 125 125 130 130 150 130 150 150 150 150 150 Molded Case Circuit Breaker_ 231 U-Series / Molded Case Circuit Breaker Cascading Table | AC415V | Downstream Upstream UAB-C Recognition category UAB/UCB-S UAB100C UCB250R UCB400R UCB630R UCB800R UAB100S UCB250S UCB400S UCB630S UCB800S Model Rated current (A) 5-100 125-250 250-400 500,630 700,800 15-100 125-250 250-400 500,630 700,800 Breaking capacity [Icu] (kA r.m.s) 10 18 30 45 45 30 25 42 65 65 18 18 30 30 UAB30C 3-30 5 10 7.5 10 10 10 UAB50C 5-50 5 10 7.5 10 10 10 UAB60C 5-60 5 10 7.5 10 10 10 UAB100C 5-100 10 14 14 14 14 UAB30R 5-30 10 14 14 14 14 18 18 18 30 30 UAB50R 5-50 10 14 14 14 14 18 18 18 30 30 UAB60R 5-60 10 14 14 14 14 18 18 18 30 30 UAB100R 15-100 25 30 35 35 35 42 42 UCB50R 15-50 25 30 35 35 35 42 42 UCB100R 15-100 25 30 35 35 35 42 42 UCB250R 125-250 18 30 35 35 30 35 35 UCB400R 250-400 30 UAB50S 15-50 25 UAB100S 15-100 UAB/UCB-S UCB100S UAB-C UAB/UCB-R UCB-L UPB-H UPB-L 30 35 30 35 35 30 35 15-100 36 UCB250S 125-250 25 UCB400S 250-400 42 UAB50H 15-50 30 35 35 UCB50H 15-50 42 45 15-125 42 UCB250H 125-250 42 UCB400H 250-400 65 UCB50L 15-50 UCB100L 30 50 30 35 42 42 35 35 42 42 45 45 42 50 50 35 35 35 42 42 45 65 42 42 42 45 50 50 45 45 50 50 45 45 50 50 50 65 65 15-125 50 65 65 UCB250L 125-250 50 65 65 UCB400L 250-400 100 UPB100H 15-125 100 UPB250H 100-250 100 UPB100L 15-125 130 UPB250L 100-250 130 UAB/UCB-H UCB100H 232 UAB-R MCCB UCB-H UCB-L UPB-H UPB-L UCB100H UCB250H UCB400H UCB630H UCB800H UCB100L UCB250L UCB400L UCB630L UCB800L UPB100H UPB250H UPB100L UPB250L 15-125 125-250 250-400 500,630 700,800 15-125 125-250 250-400 500,630 700,800 15-125 100-250 15-125 42 42 65 85 85 50 50 100 100 100 100 100 130 14 14 18 25 25 25 14 14 18 25 25 25 14 14 18 25 25 25 18 30 30 30 30 35 35 35 18 18 30 30 30 30 30 35 35 35 35 35 42 42 18 18 30 30 30 30 30 35 35 35 35 35 42 42 18 18 30 30 30 30 30 35 35 35 35 35 42 42 35 42 50 50 35 50 50 50 35 42 50 50 42 50 50 50 35 42 50 50 42 50 50 50 35 42 42 42 42 42 35 42 35 42 50 50 42 45 50 42 50 42 42 42 50 50 50 50 50 50 42 50 50 50 50 50 65 65 65 50 65 65 65 50 75 75 75 65 65 50 50 50 50 50 50 50 50 50 85 75 42 50 130 50 50 35 50 100-250 45 50 50 50 50 65 65 65 50 50 65 65 60 75 75 50 50 85 85 85 85 85 85 85 60 75 75 50 85 85 85 60 75 75 85 85 85 85 85 100 85 65 85 85 100 100 100 65 85 85 100 100 100 65 85 85 100 100 100 100 100 100 100 100 100 130 130 130 Molded Case Circuit Breaker_ 233 U-Series / Molded Case Circuit Breaker Cascading Table | AC440V | Downstream Upstream UAB-C Recognition category UAB/UCB-S UAB100C UCB250R UCB400R UCB630R UCB800R UAB100S UCB250S UCB400S UCB630S UCB800S Model Rated current (A) 5-100 125-250 250-400 500,630 700,800 15-100 125-250 250-400 500,630 700,800 Breaking capacity [Icu] (kA r.m.s) 10 18 25 35 35 25 25 35 50 50 14 14 21 21 UAB30C 3-30 5 7.5 7.5 7.5 7.5 7.5 UAB50C 5-50 5 7.5 7.5 7.5 7.5 7.5 UAB60C 5-60 5 7.5 7.5 7.5 7.5 7.5 UAB100C 5-100 10 10 10 10 10 UAB30R 5-30 10 10 10 10 10 14 14 14 21 21 UAB50R 5-50 10 10 10 10 10 14 14 14 21 21 UAB60R 5-60 10 10 10 10 10 14 14 14 21 21 UAB100R 15-100 21 25 30 30 25 30 30 35 UCB50R 15-50 25 35 35 35 35 42 UCB100R 15-100 25 35 35 35 35 42 UCB250R 125-250 18 25 25 25 35 35 UCB400R 250-400 25 UAB50S 15-50 21 UAB100S 15-100 25 UAB/UCB-S UCB100S 15-100 35 UCB250S 125-250 25 UCB400S 250-400 35 UAB50H 15-50 25 UCB50H 15-50 UAB-C UAB/UCB-R UCB-L UPB-H UPB-L 25 35 25 30 30 35 35 42 25 25 30 30 35 35 35 42 42 50 35 42 42 50 35 50 42 50 50 15-125 42 50 50 UCB250H 125-250 42 50 50 UCB400H 250-400 50 UCB50L 15-50 50 UCB100L 15-125 50 UCB250L 125-250 50 UCB400L 250-400 85 UPB100H 15-125 85 UPB250H 100-250 85 UPB100L 15-125 100 UPB250L 100-250 100 UAB/UCB-H UCB100H 234 UAB-R 35 35 35 35 35 35 MCCB UCB-H UCB-L UPB-H UPB-L UCB100H UCB250H UCB400H UCB630H UCB800H UCB100L UCB250L UCB400L UCB630L UCB800L UPB100H UPB250H UPB100L UPB250L 15-125 125-250 250-400 500,630 700,800 15-125 125-250 250-400 500,630 700,800 15-125 100-250 15-125 42 42 50 65 65 50 50 85 85 85 85 100 85 10 10 14 18 18 18 10 10 14 18 18 18 10 10 14 18 18 18 14 25 25 25 25 30 30 30 14 14 25 25 25 25 25 30 30 30 30 35 30 35 14 14 25 25 25 25 25 30 30 30 30 35 30 35 14 14 25 25 25 25 25 30 30 30 30 35 30 35 30 35 35 35 30 35 35 35 45 45 35 35 35 35 40 45 45 45 45 45 35 35 35 35 40 45 45 45 45 45 30 30 30 30 30 30 45 45 35 40 30 35 35 35 35 38 40 42 50 38 38 38 42 42 42 40 45 50 50 50 45 50 50 50 45 55 55 55 50 50 40 40 45 45 45 35 45 45 55 55 35 45 130 42 40 30 45 100-250 40 45 45 42 42 45 45 45 35 45 35 45 50 55 55 50 50 65 65 65 65 65 65 65 50 55 55 50 65 65 65 65 65 50 55 55 65 65 65 85 85 85 85 85 65 65 65 85 85 85 65 65 85 85 85 65 65 85 85 85 85 85 Molded Case Circuit Breaker_ 235 Order Information + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + MCCB Order Information ◆ Fixed thermal & fixed instantaneous / UAB, UCB, UPB type UPB250X 3P Type Code Code Pole UAB UAB30C .. UAB100S 2P1) 2 pole 3P UCB UCB50R .. UCB800L 4P2) UPB UPB100S .. UPB250X ※ For the applicable breaker, please refer to page 12-24. T4 S Code Terminal connection Direct mounting 3 pole S1) Screw 4 pole B2) Bus bar ※ 1)"2P" (2 pole) is not applicable to UPB. 2) "4P" (4 pole) is not applicable to UAB30. Code Compensating temperature T4 40/45℃ T51) 50℃ ※ 1)"T5" (50°C) is not applicable to hydraulic magnetic type UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R & UAB100C. 00 Plug-in mounting3) X for both line & load side without accessories P5) for both line & load side with accessories and connection block F6) for line side only 4) ※ 1)"S" (screw terminal connection) is default for whole range. 2) "B" (bus bar terminal connection) is available for 250AF and above breaker. - Bus bar [TBB] can be ordered separately. For details, please refer to page 215. 3) Plug-in mounting is available for 3pole breaker only. - Mounting base [TDM] and components for plug-in mounting shall be ordered separately. For details, please refer to page 209. 4)- "X" is recommended when the internal signal accessory does not need to be wired through the mounting base. - "XOOOO" code is only applicable when the accessories are not mounted. 5) - "P" is recommended when the internal signal accessory shall be plug-in also. Internal signal accessory shall be ordered along with breaker for wiring before ex-work. - "POOOO" code is not applicable. "P" code is only applicable when the accessories are mounted. - We do not provide connection block seperately. 6) "F" (plug-in mounting for line side only) is recommended when the screw terminal connection is required at load side. 00 C 00250 Code Internal accessory Code Frequency 001) without C 50/60Hz Code Rated current 00003 .. 00800 3A .. 800A Auxiliary switch (AUX) 10 20 AUX 1C AUX 2C Trip alarm switch (ALT) 01 ALT 1C Auxiliary switch (AUX) & Trip alarm switch (ALT) 11 AUX 1C & ALT 1C 21 AUX 2C & ALT 1C ※ For the applicable rated current to each breaker, please refer to page 12-24. ※ 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 136-163. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. Code Internal accessory 001) without Shunt trip (SHT) S1 SHT AC110V S2 SHT AC220V S3 SHT AC380V S4 SHT AC440V S5 SHT DC24V S6 SHT DC110V Under voltage trip (UVT) U1 UVT AC110V U2 UVT AC220V U3 UVT AC380V U4 UVT AC440V U5 UVT DC24V U6 UVT DC110V ※ 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 136-163. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. Molded Case Circuit Breaker_ 237 U-Series / Molded Case Circuit Breaker Order Information ◆ Adjustable thermal - UAB, UCB, UPB type UPB250X Type UAB 3P Code Code Pole UAB50S 2P1) 2 pole UAB50H 3P 3 pole UAB100R 4P 4 pole B2) ※ 1)"2P" (2 pole) is available for UCB only. UCB50H UPB Code S1) UAB100S UCB T4 UCB50L X4) P5) UCB100R .. UCB800L F 6) UPB100S .. UPB250X ※ For the applicable breaker, please refer to page 12-24. Code Compensating temperature T4 40/45℃ T5 50℃ S 00 Terminal connection Direct mounting 00 Internal accessory Code Rated current 001) without 00005 .. 00800 5A .. 800A Shunt trip (SHT) S1 SHT AC110V Plug-in mounting3) S2 SHT AC220V for both line & load side without accessories S3 SHT AC380V for both line & load side with accessories and connection block S4 SHT AC440V S5 SHT DC24V for line side only S6 SHT DC110V ※ 1)"S" (screw terminal connection) is default for whole range. 2) "B" (bus bar terminal connection) is available for 250AF and above breaker. - Bus bar [TBB] can be ordered separately. For details, please refer to page 215. 3) Plug-in mounting is available for 3 pole breaker only. - Mounting base [TDM] and components for plug-in mounting shall be ordered separately. For details, please refer to page 209. 4)- "X" is recommended when the internal signal accessory does not need to be wired through the mounting base. - "XOOOO" code is only applicable when the accessories are not mounted. 5) - "P" is recommended when the internal signal accessory shall be plugin also. Internal signal accessory shall be ordered along with breaker for wiring before ex-work. - "POOOO" code is not applicable. "P" code is only applicable when the accessories are mounted. - We do not provide connection block seperately. 6) "F" (plug-in mounting for line side only) is recommended when the screw terminal connection is required at load side. F ※For the applicable rated current to each breaker, please refer to page 12-24. Code Frequency C 50/60Hz Under voltage trip (UVT) U1 UVT AC110V U2 UVT AC220V U3 UVT AC380V U4 UVT AC440V Code Instantaneous characteristic U5 UVT DC24V F Fixed instantaneous UVT DC110V H Adjustable instantaneous U6 ※ 1) Default for whole range - For the applicable accessory to each breaker, please refer to page 138-163. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. Code Internal accessory 001) without Auxiliary switch (AUX) 10 20 AUX 1C AUX 2C Trip alarm switch (ALT) 01 ALT 1C Auxiliary switch (AUX) & Trip alarm switch (ALT) 11 AUX 1C & ALT 1C 21 AUX 2C & ALT 1C ※ 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 138-163. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. 238 00250 Code Screw Bus bar C 1) ※ 1) "H" (adjustable instantaneous) is available for UPB160 & UPB250. MCCB ◆ Electronic / UCB, UPB type UPB630X Type UCB 3P Code Code Pole UCB1000S 3P 3 pole UCB1000L 4P1) 4 pole UCB1250S ※ 1) " 4P" (4 pole) is not applicable to UCB1600S. UCB1250L Code UPB100S .. UPB630X ※For the applicable breaker, please refer to page 12-24. Code Protection characteristic ES1) LTD, STD, INST trip & PTA EG2) LTD, STD, INST, GFT trip & PTA ※ 1)"ES" (LTD, STD, INST trip & PTA) is default for whole range. - STD trip & PTA are not applicable to UCB1600S. 2) "EG" (LTD, STD, INST, GFT trip & PTA) is available for UCB1000, UCB1250, UPB400 & UPB630. S 00 Terminal connection Direct mounting S1) Screw B2) Bus bar X4) UCB1600S UPB ES 00 X Code Internal accessory Code Frequency 001) without C 50/60Hz X 50Hz Y 60Hz AUX 1C Plug-in mounting3) 20 AUX 2C for both line & load side without accessories 30 AUX 3C for both line & load side with accessories and connection block F6) for line side only ※ 1)"S" (screw terminal connection) is default for whole range. 2) "B" (bus bar terminal connection) is default for UCB. - "B" (bus bar terminal connection) is available for 250AF and above breaker. - Bus bar [TBB] for UPB can be ordered separately. For details, please refer to page 215. 3)Plug-in mounting is available for 3 pole breaker only. - Mounting base [TDM] and components for plug-in mounting shall be ordered separately. For details, please refer to page 209. 4)- "X" is recommended when the internal signal accessory does not need to be wired through the mounting base. - "XOOOO" code is only applicable when the accessories are not mounted. 5) - "P" is recommended when the internal signal accessory shall be plugin also. Internal signal accessory shall be ordered along with breaker for wiring before ex-work. - "POOOO" code is not applicable. "P" code is only applicable when the accessories are mounted. - We do not provide connection block seperately. 6) "F" (plug-in mounting for line side only) is recommended when the screw terminal connection is required at load side. 1) Auxiliary switch (AUX) 10 P5) 00630 40 ※ 1)Only UCB1600S is common use for both 50Hz & 60Hz ("C"). AUX 4C Trip alarm switch (ALT) 01 ALT 1C Auxiliary switch (AUX) & Trip alarm switch (ALT) 11 AUX 1C & ALT 1C 21 AUX 2C & ALT 1C 31 AUX 3C & ALT 1C Code Rated current 00100 .. 01600 100A .. 1600A ※For the applicable rated current to each breaker, please refer to page 12-24. ※ 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 154-165. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. Code 001) Internal accessory without Shunt trip (SHT) S1 SHT AC110V S2 SHT AC220V S3 SHT AC380V S4 SHT AC440V S5 SHT DC24V S6 SHT DC110V 2) Under voltage trip (UVT) U12) UVT AC110V U2 UVT AC220V U3 UVT AC380V U4 UVT AC440V U52) UVT DC24V U6 UVT DC110V 2) 2) ※ 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 154-165. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. Molded Case Circuit Breaker_ 239 U-Series / Molded Case Circuit Breaker Order Information ◆ Motor protection / UPB type UPB250L Type UPB 3P Code Code Pole UPB100H 3P 3 pole MP Code S1) UPB100L UPB250H X3) UPB250L ※For the applicable breaker, please refer to page 12-24. P4) F5) Code Trip mechanism MP Adjustable instantaneous only S 00 Terminal connection Direct mounting 00 Internal accessory Code Frequency 001) without C 50/60Hz Code Rated current 002.5 .. 00225 2.5A .. 225A Auxiliary switch (AUX) Plug-in mounting2) 10 for both line & load side without accessories 20 for both line & load side with accessories and connection block 01 ※ 1)"S" (screw terminal connection) is default for whole range. - Bus bar [TBB] can be ordered separately. For details, please refer to page 215. 2) Plug-in mounting is available for 3 pole breaker only. - Mounting base [TDM] and components for plug-in mounting shall be ordered separately. For details, please refer to page 209. 3) - "X" is recommended when the internal signal accessory does not need to be wired through the mounting base. - "XOOOO" code is only applicable when the accessories are not mounted. 4) - "P" is recommended when the internal signal accessory shall be plugin also. Internal signal accessory shall be ordered along with breaker for wiring before ex-work. - "POOOO" code is not applicable. "P" code is only applicable when the accessories are mounted. - We do not provide connection block seperately. 5) "F" (plug-in mounting for line side only) is recommended when the screw terminal connection is required at load side. 00250 Code Screw for line side only C AUX 1C AUX 2C Trip alarm switch (ALT) ALT 1C Auxiliary switch (AUX) & Trip alarm switch (ALT) 11 AUX 1C & ALT 1C 21 AUX 2C & ALT 1C ※ For the applicable rated current to each breaker, please refer to page 12-24. ※ 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 162-163. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. Code 001) Internal accessory without Shunt trip (SHT) S1 SHT AC110V S2 SHT AC220V S3 SHT AC380V S4 SHT AC440V S5 SHT DC24V S6 SHT DC110V Under voltage trip (UVT) U1 UVT AC110V U2 UVT AC220V U3 UVT AC380V U4 UVT AC440V U5 UVT DC24V U6 UVT DC110V ※ 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 162-163. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. 240 MCCB ◆ Q-class (for nuclear power plant application) / HBL type HBL203UMQ Type T4 S 00 00 C 00225 Code Code Pole Code Internal accessory Code Frequency HBL103U 3P 3 pole 001) without C 50/60Hz Code Rated current 002.5 .. 00225 2.5A .. 225A HBL103UQ HBL103UM HBL 3P HBL103UMQ HBL203U HBL203UQ HBL203UM HBL203UMQ ※ For the applicable breaker, please refer to page 12-24. Auxiliary switch (AUX) Code Compensating temperature & trip mechanism T41) 40/45°C T51) 50°C MP2) Adjustable instantaneous only ※ 1)Compensating temperature is applicable to fixed thermal & fixed instantaneous type; HBL103U, HBL103UQ, HBL203U, HBL203UQ 2)Adjustable instantaneous only trip mechanism is applicable to motor protection type; HBL103UM, HBL103UMQ, HBL203UM, HBL203UMQ Code Terminal connection Direct mounting S Screw 10 20 AUX 1C AUX 2C Trip alarm switch (ALT) 01 ALT 1C Auxiliary switch (AUX) & Trip alarm switch (ALT) 11 AUX 1C & ALT 1C 21 AUX 2C & ALT 1C ※For the applicable rated current to each breaker, please refer to page 12-24. ※ 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 168-175. - Internal accessory can be ordered separately. For details, please refer to page 192-193. ※ Bus bar [TBB] can be ordered separately. For details, please refer to page 215. Code Internal accessory 001) without Shunt trip (SHT) S1 SHT AC110V S2 SHT AC220V S3 SHT AC380V S4 SHT AC440V S5 SHT DC24V S6 SHT DC110V Under voltage trip (UVT) U1 UVT AC110V U2 UVT AC220V U3 UVT AC380V U4 UVT AC440V U5 UVT DC24V U6 UVT DC110V ※ 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 168-175. - Internal accessory can be ordered separately. For details, please refer to page 192-193. Molded Case Circuit Breaker_ 241 U-Series / Molded Case Circuit Breaker Order Information ◆ Switch disconnector / UAD, UCD, UPD type UPD630S Type UAD Code Code Pole UAD50C 3P 3 pole S Code S1) UAD100R B2) UCC100S UCD100H UCD160H UCD250S UCD250H UCD400S UCD630S UCD800S UCD1000S UCD1250S UPD100S UPD160S UPD DS UAD50S UCD50H UCD 3P UPD250S UPD400S UPD630S ※For the applicable breaker, please refer to page 14-29. 00 Terminal connection Direct mounting Bus bar DS Switch disconnector X 4) for both line & load side without accessories P5) for both line & load side with accessories and connection block F6) for line side only ※ 1)"S" (screw terminal connection) is default for UAD, UCB50-800 & UPD. 2) "B" (bus bar terminal connection) is default for UCD1000 & UCD1250. - "B" (bus bar terminal connection) is available for 250AF and above breaker. - Bus bar [TBB] can be ordered separately. For details, please refer to page 215. 3) Plug-in mounting is available for 3 pole breaker only. - Mounting base [TDM] and components for plug-in mounting shall be ordered separately. For details, please refer to page 209. 4)- "X" is recommended when the internal signal accessory does not need to be wired through the mounting base. - "XOOOO" code is only applicable when the accessories are not mounted. 5) - "P" is recommended when the internal signal accessory shall be plugin also. Internal signal accessory shall be ordered along with breaker for wiring before ex-work. - "POOOO" code is not applicable. "P" code is only applicable when the accessories are mounted. - We do not provide connection block seperately. 6) "F" (plug-in mounting for line side only) is recommended when the screw terminal connection is required at load side. C 00630 Code Internal accessory Code Frequency 001) without C 50/60Hz Code Rated current 00050 .. 01250 50A .. 1250A Screw Plug-in mounting3) Protection Code characteristic 00 Auxiliary switch (AUX) 10 20 AUX 1C AUX 2C Trip alarm switch (ALT) 01 ALT 1C Auxiliary switch (AUX) & Trip alarm switch (ALT) 11 AUX 1C & ALT 1C 21 AUX 2C & ALT 1C ※For the applicable rated current to each breaker, please refer to page 14-29. 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 136-165. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. Code Internal accessory 00 without 1) Shunt trip (SHT) S1 SHT AC110V S2 SHT AC220V S3 SHT AC380V S4 SHT AC440V S5 SHT DC24V S6 SHT DC110V Under voltage trip (UVT) U1 UVT AC110V U2 UVT AC220V U3 UVT AC380V U4 UVT AC440V U5 UVT DC24V U6 UVT DC110V ※ 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 136-165. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. 242 MCCB ◆ Miniature type - Molded case circuit breaker / UMB, UDB type UMB30Hg Type UMB 2P Code Code Pole UMB30Ra 2P 2 pole UMB30Rb 3P1) 3 pole UMB30Sg UMB30Hg T4 S 00 Code Terminal connection S Screw 00 Code Internal accessory Code Frequency 00 without C 50/60Hz Code Rated current 00003 .. 00100 3A .. 100A ※ 1)"3P"(3 pole) is applicable for UDB only. UMB50Sg Code Compensating temperature UMB50Hg T4 UDB30S 40/45°C ※For the applicable rated current to each breaker, please refer to page 14-30. UDB30H UDB 00015 C UDB50S Code Internal accessory UDB50H 00 without ※Internal accessory for UDB can be ordered separately. For details, please refer to page 176-180. UDB100S UDB100H ※For the applicable breaker, please refer to page 14-30. ◆ Miniature type - Earth leakage circuit breaker / UMG, UDG type UMG30Hg Type Code Code Pole UMG30Ca 2P 2 pole UMG30Cb 3P1) 3 pole UMG30Ra UMG30Rb UMG 2P UMG30Cd UMG30Rd UMG30Sg UMG30Hg UMG50Sg UMG50Hg G4 S Code Terminal connection S Screw 00 00 00015 C Code Internal accessory Code Frequency 00 without C 50/60Hz ※ 1)"3P" (3 pole) is available for UDG only. Code G3 Rated residual current 15mA G4 30mA G51) 100mA ※ 1)"G5" (100mA) is available for UDG only. Code Internal accessory Code Rated current 00 without 00015 .. 00100 15A .. 100A ※ Internal accessory for UDG can be ordered separately. For details, please refer to page 181-185. ※ For the applicable rated current to each breaker, please refer to page 14-30. UDG30S UDG30H UDG UDG50S UDG50H UDG100H ※For the applicable breaker, please refer to page 14-31. Molded Case Circuit Breaker_ 243 U-Series / Molded Case Circuit Breaker Order Information ◆ Fixed instantaneous only / UCB type UCB100L 3P Type Code Code Pole UCB UCB50R .. UCB800L 3P 3 pole ※ For the applicable breaker, please refer to page 12-20. T4 Code S1) B2) X4) Code Trip mechanism MO Magnetic only P5) F6) S 00 Terminal connection Direct mounting 00 Internal accessory Code Rated current without 00003 .. 00800 3A .. 800A Shunt trip (SHT) S1 SHT AC110V S2 SHT AC220V for both line & load side without accessories S3 SHT AC380V for both line & load side with accessories and connection block S4 SHT AC440V S5 SHT DC24V Code Frequency S6 SHT DC110V C 50/60Hz for line side only B 001) Plug-in mounting3) ※ 1)"S" (screw terminal connection) is default for whole range. 2) "B" (bus bar terminal connection) is available for 250AF and above breaker. - Bus bar [TBB] can be ordered separately. For details, please refer to page 215. 3) Plug-in mounting is available for 3 pole breaker only. - Mounting base [TDM] and components for plug-in mounting shall be rdered separately. For details, please refer to page 209. 4)- "X" is recommended when the internal signal accessory does not need to be wired through the mounting base. - "XOOOO" code is only applicable when the accessories are not mounted. 5) - "P" is recommended when the internal signal accessory shall be plugin also. Internal signal accessory shall be ordered along with breaker for wiring before ex-work. - "POOOO" code is not applicable. "P" code is only applicable when the accessories are mounted. - We do not provide connection block seperately. 6) "F" (plug-in mounting for line side only) is recommended when the screw terminal connection is required at load side. ※ For the applicable rated current to each breaker, please refer to page 12-20. Under voltage trip (UVT) U1 UVT AC110V U2 UVT AC220V U3 UVT AC380V Code Instantaneous characteristic U4 UVT AC440V B 10 x In U5 UVT DC24V C 12 x In U6 UVT DC110V D 15 x In ※ 1) Default for whole range - For the applicable accessory to each breaker, please refer to page 140-153. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. Code Internal accessory 001) without Auxiliary switch (AUX) 10 20 AUX 1C AUX 2C Trip alarm switch (ALT) 01 ALT 1C Auxiliary switch (AUX) & Trip alarm switch (ALT) 11 AUX 1C & ALT 1C 21 AUX 2C & ALT 1C ※ 1)Default for whole range - For the applicable accessory to each breaker, please refer to page 140-153. - For "P" type plug-in mounting, internal accessory shall be ordered. - Internal accessory can be ordered separately. For details, please refer to page 192-193. 244 00015 Code Screw Bus bar C Handling Instruction | Inspection and Maintenance + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + U-Series / Molded Case Circuit Breaker Handling Instruction | Storage | •Do not expose to corrosive gases. •Do not expose to harmful gases including sulfur, ammonia and so on. •Do not expose to high humidity for a long period. •Do not expose to direct sunlight for a long period. •Store at -20℃to +60℃without dust and humidity. •Keep the handle in OFF position. | Transportation | •Do not drop or apply shock during transportation. These can cause malfunctions in the breaker. •Hold the breaker body for transportation. Do not hold terminal bus bar or external lead cable of accessories. | Standard operating condition for normal performance | Ambient temperature -5℃ - +40℃, the average temperature for 24 hours shall not exceed 35℃ Relative humidity 45 - 85% Vibration & shock without excessive vibration and shock Altitude Surrounding up to 2,000m without excessive water vapor, oil vapor, smoke, dust, salts and corrosive materials | Installation and connection | •Keep away from direct sunlight. High temperatures can cause malfunctions. •Do not cover the terminal part completely for arc exhaust. Otherwise the breaking capacity may be decreased. 246 •Avoid any vibration or shock. If vibration or shock is expected, install breaker with shock absorber. •Do not take off the black insulation plate in back side of breaker. therwise insulation shall be decreased or O not secured. •Keep away from dust or metal pieces. When any work that accompanies dust or metal cutting is required, please cover the breaker first. MCCB | Installation and connection | •Tighten the terminal screws to proper torque specified in manual. T he loose connection may cause overheating, and excessive torque may damage screws and terminal parts. •Do not apply lubricant on terminal parts. T he lubricant lets screws loose and overheating occurs. •Insulate exposed conductors. To prevent short-circuit, be sure to insulate exposed conductors by interpole barrier, terminal cover, insulating tube, insulating tape and so on. ← Insulating supporter •Do not modify the shape of studs or terminal accessories. E xcessive force to stud and terminal accessories should also be avoided. •Fix each conductor in parallel. hort-circuit current can occur S electromagnetic force between conductors, so each conductor is required to fixed firmly in parallel. [Electromagnetic force per 1m conductor at 3 phase short-circuit] Short -circuit current / Internal power factor (kA) 10/0.4 •Reverse feeding of earth leakage circuit breaker is not allowed. In case of reverse feeding, power is supplied to circuit even the breaker trips, and it shall damage trip coil. (Unit : N [kgf]) Distance between conductors 10cm 20cm 490/50 245/25 932/95 18/0.3 1863/190 25/0.2 4412/450 2206/225 35/0.23 8630/880 4315/440 42/0.2 12455/1270 6277/635 50/0.2 17652/1800 8826/900 65/0.2 29910/3050 14955/1525 85/0.2 51190/5220 25595/2510 100/0.2 70804/7220 35402/3610 125/0.2 110815/11300 55408/5650 | Connection of earth leakage circuit breaker | •Single phase three line circuit P ower line shall be connected to both side poles of breaker, and neutral line to middle pole. •Single phase two line circuit C ircuit shall be connected to both side poles of breaker, and middle pole shall not be connected. •Parallel connection is not allowed. arallel connection causes current P unbalance, malfunction and trip coil damage. Molded Case Circuit Breaker_ 247 U-Series / Molded Case Circuit Breaker Inspection and Maintenance | Initial inspection | •Please check the following prior to breaker operation. Check point Terminal part shall be clean from dust, metal pieces and so on. Breaker shall not have any crack or damage. There should be non condensation on terminal parts. Insulation resistance should be more than 5MΩ. Terminal screws shall be tightened with specified torque. | Dielectric test | •The test shall be done in these conditions. Secondary and control circuit Main circuit Rated insulation voltage (Ui) Test voltage Rated insulation voltage (Uis) Test voltage Ui ≦ AC300V AC2000V Uis ≦ AC60V AC1000V AC300V < Ui ≦ AC600V AC2500V AC60V < Uis ≦ AC60V 2Uis + AC1000V (Max. AC1500V) •Test for earth leakage circuit breaker Test Measuring parts Insulation resistance test Dielectric test Handle position Handle position ON OFF ON OFF Charging parts and earth ◯ ◯ ◯ ◯ R and S phase, S and T phase ◯ ◯ ◯ ◯ Line side × ◯ × ◯ Load side × × × × - ◯ - ◯ R and T phase Power and line side terminal •Insulation resistance test - Please use AC500V insulation resistance tester. - Do not measure between R and T phase. The measured resistance value shall be almost 0Ω. •Dielectric test - Do not apply test voltage, if test voltage is applied by mistake, the breaker can not be used. 248 MCCB | Periodic inspection | •In order to maintain the performance of breaker and prevent the unpredicted accident, the inspection shall be accompanied after installation and operation. - Once after one month of operation, thereafter as below. Circumstance Inspection cycle after installation within 10 years : Clean air, no humidity once 2-3 year more than 10 years : once a year more than 15 years : once 6 month Normal within 10 years : Dust but no corrosive gas once a year more than 10 years : once 6 month more than 15 years : once a month Bad Sulfurous gas, salinity, vapor Excessive corrosive gas within 5 years : once 6 year more than 5 years : once a month once a month | Inspection and processing after breaking of fault current | •If there is no pollution in arc exhaust parts and no other abnormality, the breaker can be re-used. •When carbonizing symptom is found around arc exhaust parts, please measure insulation resistance. If the resistance value is more than 5MΩ, no dielectric breakdown at withstand test voltage and no excessive temperature rise of terminal parts, then the breaker can be re-used. •If the handle part is carbonized or there is metallic melting in internal of breaker, please replace it with a new one. Molded Case Circuit Breaker_ 249 U-Series / Molded Case Circuit Breaker Inspection and Maintenance | Troubleshooting | •In case of any abnormality during breaker operation, please handle it as below. •For cases not mentioned in below, please contact us. Molded case circuit breaker Symptom and possible cause Overheating Inferior dielectric Inability of operation •High temperature of terminal part •Damage in insulation part of terminal •Loose connection between terminal and conductor •Tighten screws with specified torque •Heating by resistance increase of conductor •Replace with a new breaker •Heating from connection part between terminal bus bar and breaker •Tighten screws with specified torque •High temperature of breaker body •Heating by resistance increase of conductor •Loose internal assembly screws •Increase of current density from cable disconnection •Replace with a new breaker •Abnormal voltage of load side •Excessive contact abrasion •Foreign substances on contact •Corrosion of conductor by excessive ON-OFF or corrosive gas •Replace with a new breaker •Inability of reset after trip •OFF the breaker after manual reset •Non-energized UVT •Apply the power •Insufficient cooling of trip unit •Reset the breaker after cooling down •Corrosion, damage or deformation of bimetal •Abnormality or damage in mechanism •Exhaustion of durability •Contact melting by excessive high breaking current •Replace with a new breaker •High ambient temperature •Cool down ambient temperature by ventilation or others •Heating by loose terminal screw connection •Tighten screws with specified torque •Heating from inside of breaker •Replace with a new breaker •Smaller connection conductor than specified size •Use the specified size of conductor or adjust the rated current •Inability of ON and RESET •Trip at under rated current Frequent trip •Trip at start-up inrush current •Trip at change-over in star-delta operation •Instantaneous trip at reverse feeding •Trip at operational current Malfunction •Non trip at the current higher than specified •Instantaneous trip at high start-up inrush current •Instantaneous trip at long start-up inrush current •Adjust the instantaneous trip setting or replace with a higher current breaker •Replace with a higher current breaker •Short-circuit between motors •Repair or replace motors •Misconnection of SHT, UVT control circuit •Inspect circuit wiring •Current breaking by line side fuse or low coordination with primary breaker •Redesign the coordination between equipment •Extremely low ambient temperature •Out of rated frequency 250 Troubleshooting •Adjust the current according to temperature derating curve •Apply the rated frequency or adjust breaker frequency knob MCCB Earth leakage circuit breaker Symptom and possible cause •Earth leakage current higher than trip current since Malfunction •Earth leakage test button is projected as soon as the breaker is ON increase of earth interruption capacity depending on wire length •Parallel connection •Mis-connection or disconnection of neutral line Troubleshooting •Adjust the residual current •Install the breaker closer to the load •Inspect the connection and wiring •Excessive surge •Trip during normal operation •Induction noise by high current generating line •Remove or keep away from causes •Noise of electromagnetic waves Accessories Symptom and possible cause •Voltage drop of control circuit •Shunt trip (SHT) •Coil damage by different voltage and malfunction of coil protection limit switch Inability of operation or •Under voltage trip (UVT) malfunction •Auxiliary switch (AUX) and trip alarm switch (ALT) Troubleshooting •Adjust voltage to rated level •Replace with a new breaker •Inferior mechanism •Replace with a new breaker •Different rated operational voltage •Apply the rated voltage to UVT •Damage in contact or contact operation at the current higher than rated current •Inferior mechanism •Repair or replace with a new breaker •Replace with a new breaker Molded Case Circuit Breaker_ 251 HE-LE-B56-05, 2018.8 Designed by designwat KOREA Headquarter (Financial) Hyundai Bldg, 75, Yulgok-ro, Jongno-gu, Seoul, Korea Tel: +82-2-746-7646 / Fax: +82-2-746-7441 Sales & Marketing (Seongnam) 5th Floor 55, Bundang-ro, Bundang-gu, Seongnam-si, Gyeonggi-do, Korea Tel: +82-31-8006-6786 / Fax: +82-31-8006-6898 Main Factory (Ulsan) 700, Bangeojinsunhwan-doro, Dong-gu, Ulsan, Korea Tel: +82-52-202-8114 / Fax: +82-52-202-8010 Seonam Factory (Ulsan) 223, Sapyong-ro, Nam-gu, Ulsan, Korea Tel: +82-52-202-8114 R&D Center (Yongin) 17-10, 240-gil, Mabuk-ro, Giheung-gu, Yongin-si, Korea Tel: +82-31-289-5114 / Fax: +82-31-289-5040 OVERSEAS Branch Offices U.S.A (Atlanta) 6100 Atlantic Boulevard, 2nd FL., Norcross, GA30071, U.S.A Tel: +1-678-823-7839 / Fax: +1-678-823-7553 Japan (Osaka) 5th Floor Nagahori Plaza Bldg. 2-4-8 Minami Senba, Chuo-ku, Osaka 542-0081, Japan Tel: +81-6-6261-5766~7 / Fax: +81-6-6261-5818 Saudi Arabia (Riyadh) Office number 404, 4th floor,Akaria-3 building, Olaya street, P.O Box 8072, Riyadh, 11482, Kindom of Saudi Arabia Tel: +966-11-464-4696, 9366 / Fax: +966-11-462-2352 Russia (Moscow) World Trade Center, Ent.3, #703, Krasnopresnenskaya Nab.12, Moscow, 123610, Russia Tel: +7-495-258-1381 U.A.E (Dubai) Unit 205, Emaar Square Building No.4 Sheikh Zayed Road, Dubai 252458, U.A.E Tel: +971-4-425-7995 / Fax: +971-4-425-7996 Germany (Frankfurt) Mendelssohn strabe 55-59 Frankfurt 60325, Germany Tel: +49-69-4699-4988 Thailand (Bangkok) 19th Floor, Unit 1908, Sathorn Square Office Tower, 98 North Sathorn Road, Silom, Bangrak, Bangkok 10500, Thailand Tel: +66-02-115-7920 / Fax: +66-2-115-7898 Subsidiaries U.S.A (Alabama) Inc., 215 Folmar Parkway, Montgomery, AL 36105, U.S.A. Tel: +1-334-481-2000 / Fax: +1-334-481-2098 Bulgaria (Sofia) 41, Rojen Blvd., 1271 Sofia, Bulgaria Tel: +359-2-803-3200, 3210, 3220 / Fax: +359-2-803-3203, 3242 China (Yangzhong) No.9, Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip:212212, China Tel: +86-511-8842-0666, 0500 / Fax: +86-511-8842-0668, 0231 India (Anantapur) 5-289-4, Near Aimuktheeshwara Temple, Penukonda Mandal, Penukonda, Anantapur Dist, Andhrapradesh-515110, India Tel: +91-93982-5137 R&D Centers Hungary (Budapest) Hyundai Technologies Center Hungary ltd., 1146, Budapest, Hermina ut 22, Hungary Tel: +36-1-273-3733 / Fax: +36-1-220-6708 China (Shanghai) Room 10102, Building 10, No.498, Guoshoujing Road, Pudong, Shanghai, China Tel: +86-21-5013-3393 #108 / Fax: +86-21-5013-3393 #105 Switzerland (Zurich) Hardturmstrasse 135, CH-8005, Zurich, Switzerland Tel: +41-44-527-0-56 www.hyundai-electric.com